Plan Review Details - Permit 09080578
Plan Review Stops For Permit 09080578
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2009-10-14 Cont ID  
Sent By jnguyen Date 2009-10-14 Time 11:43 Rev Time 0.00
Received By jnguyen Date 2009-10-13 Time 10:12 Sent To  
Notes
2009-10-14 11:02:0010-14-09: CHERYL HORTON OF PAPA GOT BACK TO ME
 REGARDING THE ISSUE WITH THE RETAIL TENANT SPACES (A, B
 & C) WITHIN THE 17-DIGIT CONDO PCN# 74434322170010031
 AT 400 N FLAGLER DR # C1 (COMMERCIAL MARINA OF
 WATERVIEW CONDOMINIUM). THE CONTENT OF HER E-MAIL WAS
 AS FOLLOWED:
  
 "RETAIL SPACE A THRU C IS A PORTION OF COMMERCIAL UNIT
 C-1 WHICH ENCOMPASSES THE ENTIRE MARINA. THE PCN YOU
 LISTED IS FOR THE UNIT C1. THERE IS NO SEPARATE LEGAL
 DESCRIPTION FOR TENANT SPACES A THRU C ON THE TAX ROLL.
 THIS INFORMATION WAS PROVIDED TO ME FROM GENE POTTER,
 CONDOMINIUM DEPARTMENT. IF YOU HAVE ANY QUESTIONS,
 PLEASE CONTACT GENE AT 355-3261."
  
 SINCE THE RETAIL TENANT SPACES ARE DIRECTLY A PART OF
 UNIT # C1, I HAVE ADDED THEM AS EXTENSIONS OFF PCN#
 74434322170010031 IN COMMUNITYPLUS (TO BE ABLE TO
 DIFFERENTIATE THEM). THEY WERE IMPLEMENTED AS FOLLOWED:
 SEQUENTIAL UNIT RECORD 0002 - 400 N FLAGLER DR # C1
 TENANT A, SEQUENTIAL UNIT RECORD 0003 - 400 N FLAGLER
 DR # C1 TENANT B & SEQUENTIAL UNIT RECORD 0004 - 400 N
 FLAGLER DR # C1 TENANT C. AS A RESULT, I HAVE MOVED
 PERMIT# 09080578 FROM THE MAIN LOCATION RECORD OF PCN#
 74434322170010031 TO BE INSTEAD REFERENCED TO
 SEQUENTIAL UNIT RECORD 0002 - 400 N FLAGLER DR # C1
 TENANT A. I ALSO MOVED PERMIT# 09080581 TO BE APPLIED
 INSTEAD TO SEQUENTIAL UNIT RECORD 0003 - 400 N FLAGLER
 DR # C1 TENANT B. I MADE THE ADJUSTMENTS ON THEIR
 ORIGINAL PERMIT APPLICATIONS TOO. I RETURNED THE
 ASSOCIATED DOCUMENTS BACK TO THE B14 & B18 BOXES
 DOWNSTAIRS.
  
 JOHN NGUYEN
 GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 MIS DEPARTMENT
 OFFICE: (561) 822-1239
 FAX: (561) 822-1249
 [email protected]
2009-10-13 13:39:38 
  
  
 10-13-09: I CURRENTLY HAVE THE SITE PLANS CHECKED OUT.
 THE RENOVATION SHOWS THAT THIS PART OF THE WATERVIEW
 CONDOMINIUM IS BEING DESIGNATED AS THREE DISTINCT
 TENANT SPACES OF A, B & C. I AM NOT AWARE IF EACH ONE
 OF THESE ALPHA CHARACTERS HAVE THEIR OWN DISTINCT
 17-DIGIT PCN#, SO I CONTACTED CHERYL HORTON OF PAPA
 WITH THE FOLLOWING MESSAGE:
  
 "THE EASTERN PART (DIRECTLY FACING THE DOCK) OF THE
 WATERVIEW TOWERS CONDOMINIUM IS CURRENTLY BEING
 RENOVATED WITH TENANT SPACES A, B & C (SHOWN AS PCN#
 74434322170010031 AT 400 N FLAGLER DR # C1 ON THE
 AERIAL). SINCE IT IS THE DEVELOPER'S JURISDICTION TO
 ASSIGN SUITE ADDRESSES FOR UNITS WITHIN CONDOMINIUMS, I
 AM NOT AWARE OF THE ASSOCIATED PCN#S FOR TENANT SPACES
 A & B. DOES # A & B SHARE THE SAME 17-DIGIT CONDO PCN#
 74434322170010031 ASSOCIATED WITH # C1 OR DO THEY HAVE
 THEIR OWN UNIQUE ONES? IS # A & B ALREADY ON FILE AS
 ONE OF THE UNIT # PH ALPHA CHARACTERS OR ARE THESE PH
 UNITS UNRELATED (AS SHOWN IN THE PAPA SCREENSHOTS
 BELOW)?"
  
 *UNTIL I HEAR BACK FROM CHERYL, I AM NOT SURE IF
 SUITES/UNITS # A & B SHOULD BE EXTENSIONS OFF PCN#
 74434322170010031, HAVE BEEN ASSIGNED NEW 17-DIGIT
 CONDO PCN#S OR IF THEY WERE ALREADY IN EXISTENCE?

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-12-15 Cont ID  
Sent By jwitmer Date 2009-12-15 Time 16:23 Rev Time 0.77
Received By jwitmer Date 2009-12-15 Time 16:23 Sent To  
Notes
2009-12-15 16:24:09BUILDING PLAN REVIEW
 PERMIT: 09100609
 ADD: 400 N FLAGLER / TENANT A
 CONT: SHAKMAN HOSPITALITY
 TEL: (561)756-2553
  
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
  
 REVISION- REVIEW- 09110609
  
  
 1) SHEET A-4/ DETAIL# 1 & M1.01. PLANS INDICATE A
 PLENUM RETURN.
 BUILDING APPROVED WITH EXCEPTION!
  
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF REINSPECTION FEE(S).
  
 PLENUMS- MECHANICAL 602.2.1.5.1, SEPARATION REQUIRED.
 THE FOAM PLASTIC INSULATION SHALL BE SEPARATED FROM THE
 PLENUM BY A THERMAL BARRIER COMPLYING WITH SECTION
 2603.4 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2603.4 THERMAL BARRIER. EXCEPT AS PROVIDED FOR IN
 SECTIONS 2603.4.1 AND 2603.9, FOAM PLASTIC SHALL BE
 SEPARATED FROM THE INTERIOR OF A BUILDING BY AN
 APPROVED THERMAL BARRIER OF 0.5-INCH (12.7 MM) GYPSUM
 WALLBOARD OR EQUIVALENT THERMAL BARRIER MATERIAL THAT
 WILL LIMIT THE AVERAGE TEMPERATURE RISE OF THE
 UNEXPOSED SURFACE TO NOT MORE THAN 250??F (120??C)
 AFTER 15 MINUTES OF FIRE EXPOSURE, COMPLYING WITH THE
 STANDARD TIME-TEMPERATURE CURVE OF ASTM E 119. THE
 THERMAL BARRIER SHALL BE INSTALLED IN SUCH A MANNER
 THAT IT WILL REMAIN IN PLACE FOR 15 MINUTES BASED ON FM
 4880, UL 1040, NFPA 286 OR UL 1715. COMBUSTIBLE
 CONCEALED SPACES SHALL COMPLY WITH SECTION 717.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-12-01 Cont ID  
Sent By jwitmer Date 2009-12-01 Time 08:57 Rev Time 0.55
Received By jwitmer Date 2009-12-01 Time 08:57 Sent To  
Notes
2009-12-01 08:58:508 1/2X11 SHEET A-4 TENANT B
 DATED 11-13-09
  
 BUILDING PROVISO: 2603.4 THERMAL BARRIER.
 EXCEPT AS PROVIDED FOR IN SECTIONS 2603.4.1 AND 2603.9,
 FOAM PLASTIC SHALL BE SEPARATED FROM THE INTERIOR OF A
 BUILDING BY AN APPROVED THERMAL BARRIER OF 0.5-INCH
 (12.7 MM) GYPSUM WALLBOARD OR EQUIVALENT THERMAL
 BARRIER MATERIAL THAT WILL LIMIT THE AVERAGE
 TEMPERATURE RISE OF THE UNEXPOSED SURFACE TO NOT MORE
 THAN 250??F (120??C) AFTER 15 MINUTES OF FIRE EXPOSURE,
 COMPLYING WITH THE STANDARD TIME-TEMPERATURE CURVE OF
 ASTM E 119. THE THERMAL BARRIER SHALL BE INSTALLED IN
 SUCH A MANNER THAT IT WILL REMAIN IN PLACE FOR 15
 MINUTES BASED ON FM 4880, UL 1040, NFPA 286 OR UL 1715.
 COMBUSTIBLE CONCEALED SPACES SHALL COMPLY WITH SECTION
 717.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-09-09 Cont ID  
Sent By jwitmer Date 2009-09-09 Time 15:24 Rev Time 1.25
Received By jwitmer Date 2009-09-09 Time 13:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-10-20 Cont ID  
Sent By dpalmer Date 2009-10-20 Time 08:53 Rev Time 0.00
Received By dpalmer Date 2009-10-20 Time 08:53 Sent To  
Notes
2009-10-20 08:53:49NEW S&S SHEETS INSERTED INTO SETS. REMOVED OLD.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-10-10 Cont ID  
Sent By dpalmer Date 2009-10-10 Time 12:03 Rev Time 0.00
Received By dpalmer Date 2009-10-10 Time 12:03 Sent To  
Notes
2009-10-10 12:03:17** TEMPORARY FAILED **
  
 TENANT *A*
  
 ADDRESS FOR APPLIED LOCATION STILL NEEDS TO BE
 CORRECTED. THERE IS CURRRENTLY NUMEROUS PERMITS APPLIED
 AND ISSUED FOR 400 N FLAGLER #C1. THIS INCLUDES PERMITS
 FOR THREE DIFFERENT DOCKS, ELECTRICAL AND OTHER TENANT
 SPACES. ADDRESS/SUITE/UNIT EXTENSIONS NEED TO BE ADDED.
 NOT ALL PERMITS CAN BE ISSUED TO THE SAME
 TENANT/LOCATION
  
  
 1) NOTE: AS NOTED ON PREVIOUS REVIEW PLEASE REMOVE OLD
 SHEETS FROM SETS AND INSERT NEW SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 2) NOTE: BASED ON A CONVERSATION WITH FAE CONSULTING
 NEW ELECTRICAL SHEETS WERE TO BE BROUGHT IN FOR REVIEW
 BEFORE ELECTRICAL REVIEW WAS TO BE DONE. THE NEW SHEET
 E2.01 SUBMITTED ON OCTOBER 2ND WAS INADVERTENTLY NOT
 SIGNED BY THE ENGINEER OF RECORD. ENGINEER OF RECORD
 CALLED OFFICE. ALSO SPOKE TO REPRESENTATIVE FROM FAE
 AND NEW SHEET WILL BE BROUGHT IN AS ENGINEER WAS OUT OF
 TOWN UNTIL MONDAY THE 12TH OF OCTOBER. SHEET MAY BE
 BROUGHT IN WITHOUT ANY FEE.
 SETS OF PLANS NEED TO BE PLACED TOGETHER BY CONTRACTOR.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-09-18 Cont ID  
Sent By dpalmer Date 2009-09-18 Time 18:41 Rev Time 0.00
Received By dpalmer Date 2009-09-18 Time 18:41 Sent To PC
Notes
2009-09-18 18:41:58 
  
 ** DENIED **
  
 ** REVIEW IS BASED ON PLANS AND SUPPORTING DOCUMENTS
 SUBMITTED.
  
 1A) NOTE: ADDED, PERMIT APPLICATION STATES TENANT SPACE
 #C1, HOWEVER PLANS STATE TENANT SPACE *A*.
  
 1) NOTE: IN THE PACKAGE THERE ARE SUPPORTING METHOD *A*
 WHOLE BUILDING COMPLIANCE ENERGY CALCULATIONS. THIS IS
 NOT A WHOLE BUILDING BY DEFINITION. PLEASE ALSO SEE
 THAT PLANS ARE SHOWING A SEPARATE METHOD OF COMPLIANCE.
 IN FACT PLANS ARE SHOWING PRESCRIPTIVE SPACE BY SPACE
 METHOD *B*.
 PLEASE SEE SECTIONS NOTED:
  
 THE LIGHTING PLANS SUBMITTED CLEARLY INDICATE METHOD
 *B*. IN FACT THE PLANS STATE COMPLIANCE FOR SPACE BY
 SPACE PER 13-415.B.1. PLEASE SEE 13-415.AB.5 OF THE
 FBC. THIS SECTION CLEARLY STATES THE FOLLOWING.
  
 * TRADE-OFFS OF INTERIOR LIGHTING POWER ALLOWANCE AMONG
 PORTIONS OF THE BUILDING FOR WHICH A DIFFERENT METHOD
 OF CALCULATION HAS BEEN USED IS NOT PERMITTED*.
  
 THIS MEANS IT IS NOT PERMISSIBLE TO USE TWO DIFFERENT
 METHODS TO SHOW COMPLIANCE. THE SUBMITTED INPUT DATA
 REPORT OF THE METHOD *A* IN BOTH CASES IS NOT COMPLETE.
  
 ** THEREFORE COMPLIANCE WITH PRESCRIPTIVE FOR NEW BEING
 INSTALLED IS REQUIRED TO BE MET.
 COMPLIANCE FOR METHOD *B* IS SHOWN ON PLANS FOR
 LIGHTING PERFORMANCE LEVELS AND IS ACCEPTABLE TO THIS
 OFFICE.
 13-415.AB.5, 13-415.B.1, 13-400.0.B.4. PLEASE TAKE A
 LOOK AT THE LAST SENTENCE FOR * BUILDINGS NOT MEETING
 THE DEFINITION OF A RENOVATION.
  
 ** IMPORTANT. PLANS STATE FUTURE DISPLAY CASES WHICH
 ARE GOING TO BE LIGHTED. PLEASE SEE 13-415.AB.5 AS
 THESE LIGHTED CASED SHALL BE FIGURED INTO THE TOTAL
 ALLOWANCES.
 THE REVISED CODE DOES NOT CONTAIN DISPLAY AREA
 ALLOWANCES.
  
 ** THE SECURITY OFFICE IS AN OFFICE USE NOT OTHER AS
 SHOWN. 1.1, NOT 1.5.
 ** THERE IS NOT CONFERENCE ROOM ON PLANS. ALLOWANCE MAY
 NOT BE USED.
 ** WORK/COPY ROOM MAY NOT USE 1.5, THIS IS OFFICE.
  
 ** BASED ON THE ABOVE AND THE INFORMATION NOT YET
 SHOWN, THE LIGHTING PERFORMANCE CALCULATIONS ARE
 SUBSTANTIALLY OVER THE ALLOWANCES OF THE FLORIDA ENERGY
 CODE.
  
 2) NOTE: ONE OF THE COPIES OF THE SUBMITTED METHOD *A*
 CALCULATIONS ARE PHOTO-COPIES OF SIGNED DOCUMENTS. THIS
 IS NOT PERMITTED PER FAC 61G15-23.002, FS 471.025
  
 3) NOTE: COMPLIANCE FOR NEW LIGHTING CONTROLS BEING
 INSTALLED SHALL MEET 13-415.AB.1.1,.1.2 AND .1.3.
 PLEASE SEE 13-415.AB.1.3 SPECIFICALLY AS OTHER LIGHTING
 SUCH AS TRACK LIGHTING WHICH IS NOT PART OF THE GENERAL
 LIGHTING SHALL HAVE SEPARATE CONTROLS.
 THIS IS ALSO FOR FUTURE DISPLAY CASES WHICH ARE ALSO
 REQUIRED TO BE PART OF THE AUTOMATED LIGHTING CONTROLS
 INCLUDING SEPARATE CONTROLS.
  
 4) NOTE: PLANS CONTAIN ELECTRICAL FOR OTHER FUTURE
 TENANT SPACE YET THIS SPACE IS ALREADY SUBMITTED FOR
 PERMIT. RECORD PLANS WOULD NOT CONTAIN ELECTRICAL WHICH
 IS NOT PART OF THE APPLIED SCOPE OF WORK.
  
 5) NOTE: EXTERIOR LIGHTING CONTROLS AS NOTED FOR SHELL
 SHALL MEET 13-415.AB.1.4. MUST BE PHOTO-SENSOR TYPE OR
 ASTRONOMICAL TIME CLOCK WITH MINIMUM OF 10HRS BACK UP.
 IT IS PERMISSIBLE TO HAVE BOTH.
  
 6) NOTE: SHOW WINDOW RECEPTACLES REQUIRED PER 210.62
  
 7) NOTE: LOAD CALCULATIONS NEED TO COMPLY WITH NEC FOR
 SHOW WINDOWS FIGURED PER 220.14G AND 220.43A.
 PLEASE ALSO INDICATE ALL CONTINUOUS LOADS AND LARGEST
 MOTOR LOADS AT 125%. IF ALREADY FIGURED INTO SERVICE
 THEN PLEASE SHOW WHERE OR NOTE THIS WAS DONE ON PLANS.
 215.3, 230.42 ETC
  
 8) NOTE: PLEASE ALSO SHOW LOAD CALCULATION COMPLIANCE
 FOR SIZING SERVICE FEEDERS PER 220.43B
  
 9) NOTE: DISCONNECT LOCATION FOR CU DOES NOT MEET
 110.26.
  
 10) NOTE: PLEASE SEE FBC 11-4.28.1.3. THERE IS A
 HORN/STROBE DEVICE ON FA SHEET WHICH IS MISSING CANDELA
 LEVEL. SEE SECTION NOTED FOR MINIMUM REQUIRED.
 PLEASE ALSO SEE 11-4.28.1 AND .2.
  
  
 ** LOW VOLTAGE SYSTEMS, INCLUDING FIRE ALARMS ARE NOT
 INCLUDED. SEPARATE PERMITS AS INDICATED ON PLANS
 REQUIRED.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-10-20 Cont ID  
Sent By mawillia Date 2009-10-20 Time 11:30 Rev Time 0.00
Received By mawillia Date 2009-10-20 Time 11:10 Sent To  
Notes
2009-10-20 11:21:10*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS LS-1, A-1.0, E2.01 AND FA1.01
 WERE STAMPED, INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-09-09 Cont ID  
Sent By mawillia Date 2009-09-09 Time 15:32 Rev Time 0.00
Received By mawillia Date 2009-09-09 Time 15:28 Sent To  
Notes
2009-09-09 15:32:04*****DENIED*****
  
 1. THE PROJECT SITE ADDRESS, INCLUDING THE SUITE
 NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED
 PLAN SHEET.
  
 2.. THE PLANS AND PROJECT LOCATION SHALL CORRELATE WITH
 THE PERMIT APPLICATION AS PER THE CONSTRUCTION SERVICES
 DEPARTMENT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING (ON THE APPROPIATE PLAN SHEET) WHERE
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-11-17 Cont ID  
Sent By btrobaug Date 2009-11-17 Time 15:09 Rev Time 0.00
Received By btrobaug Date 2009-11-17 Time 15:09 Sent To B
Notes
2009-11-17 15:09:46TO JIM'S DESK./WRT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-30 Cont ID  
Sent By shill Date 2009-09-30 Time 12:24 Rev Time 0.00
Received By shill Date 2009-09-30 Time 12:24 Sent To  
Notes
2009-09-30 12:25:42B14
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-09-18 Time   Rev Time 0.00
Received By lmartine Date 2009-08-26 Time 13:58 Sent To  
Notes
2009-08-26 13:59:53B-24

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2009-09-18 Cont ID  
Sent By dpalmer Date 2009-09-18 Time 18:11 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-11-09 Cont ID  
Sent By rregueir Date 2009-11-09 Time 20:37 Rev Time 0.00
Received By rregueir Date 2009-11-09 Time 20:37 Sent To  
Notes
2009-11-09 20:38:13REVISED M1.01 DELTA 3

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-10-17 Cont ID  
Sent By rregueir Date 2009-10-17 Time 12:17 Rev Time 0.00
Received By rregueir Date 2009-10-17 Time 12:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-09-08 Cont ID  
Sent By rregueir Date 2009-09-08 Time 13:29 Rev Time 0.00
Received By rregueir Date 2009-09-08 Time 10:49 Sent To  
Notes
2009-09-08 13:29:16REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. OFFICES SHOW USE OF TRANSFER GRILLS TO ACHIEVE
 BALANCED RETURN. SOME RETURN GRILLS ARE NOT SIZED TO
 MEET THE EXCEPTIONS UNDER FBC-M 601.4. SEE OFFICES A07
 AND A10. SHOW SIZES TO MEET THE EXCEPTION OR A FIELD
 TEST WILL BE REQUIRED TO DETERMINE PRESSURE DIFFERENCES
 ACROSS CLOSED DOORS IN ACCORDANCE WITH THIS SECTION.
  
 2. FIRE DAMPERS AT TENANT SEPARATION WALL ARE CALLED
 FOR IN NOTES BUT ARE NOT SHOWN ON FLOOR PLANS. THE
 SPECIFIC LOCATION OF EACH FIRE DAMPER SHALL BE SHOWN
 AND PROPERLY IDENTIFIED ON THE BUILDING PLANS BY THE
 DESIGNER IN ACCORDANCE WITH FBC-M 607.8.
  
 3. AHU 1 AND AHU 2 SHARE A COMMON RETURN AIR PLENUM.
 EACH UNIT SHALL BE PROVIDED WITH DUCT SMOKE DETECTORS
 IN ACCORDANCE WITH FBC-M 606.2.2. THE DUCT SMOKE
 DETECTORS SHALL BE CONNECTED TO THE BUILDING FIRE ALARM
 SYSTEM IN ACCORDANCE WITH FBC-M 606.4.1.
  
 4. OUTDOOR CONDENSING UNITS SHALL BE DESIGNED AND
 INSTALLED FOR WIND RESISTANCE IN ACCORDANCE WITH FBC-M
 301.12. PROVIDE MANUFACTURER'S DATA FOR CONDENSERS
 SHOWING THESE APPLIANCES ARE DESIGNED FOR WIND
 RESISTANCE. PROVIDE MANUFACTURER'S INSTALLATION
 INSTRUCTIONS FOR WIND RESISTANT INSTALLATION IF
 APPLICABLE.
 NOTE: THE CONDENSER INSTALLATION DETAIL REFERENCES
 FBC-M 301.13.1, WHICH WAS A PRESCRIPTIVE METHOD OF
 INSTALLATION IN THE 2004 FBC FOR R-3 OCCUPANCIES ONLY.
 THIS PRESCRIPTIVE METHOD IS NOT APPLICABLE. AN
 ENGINEERED DESIGN IS REQUIRED. THE MANUFACTURER'S WIND
 CERTIFICATION MAY CONTAIN SPECIFIC REQUIREMENTS FOR A
 WIND RESISTANCE COMPLIANT INSTALLATION.
  
 5. THE VENTILATION CALCULATIONS CLASSIFY ALL AREAS
 SERVED BY THESE SYSTEMS AS "OFFICE." THIS IS NOT
 CORRECT. THESE VENTILATION SYSTEMS SHALL BE DESIGNED TO
 HAVE THE CAPACITY TO SUPPLY THE MINIMUM OUTDOOR AIRFLOW
 RATE DETERMINED IN ACCORDANCE WITH TABLE 403.3 BASED ON
 THE OCCUPANCY OF THE SPACE AND THE OCCUPANT LOAD. THE
 FLOOR PLAN SHOWS DIFFERENT AREAS WITH DIFFERENT
 VENTILATION REQUIREMENTS, SUCH AS (EXAMPLE) RETAIL.
 PROVIDE SPACE-BY-SPACE VENTILATION CALCULATIONS SHOWING
 THE CORRECT OCCUPANCY CLASSIFICATION, OCCUPANT LOAD AND
 VENTILATION RATE FOR EACH SPACE.
 NOTE: COOLING LOADS MAY ALSO BE AFFECTED BY INCREASED
 VENTILATION.
  
 6. NOTE ON PAGE M2.01 CALLS FOR MANUAL VOLUME DAMPER IN
 LIEU OF A MOTORIZED DAMPER ON THE OUTSIDE AIR INTAKES.
 ACCORDING TO FBC-B 13-409.AB.3.3, A GRAVITY OPERATED
 DAMPER MAY BE USED IN LIEU OF A MOTORIZED DAMPER IF THE
 INTAKE IS LESS THAN 300 CFM. IN ADDITION TO THE GRAVITY
 DAMPER, A MANUAL VOLUME DAMPER IS REQUIRED IN
 ACCORDANCE WITH FBC-B 13-409.AB.1.1.
 NOTE: VENTILATION QUANTITIES MAY EXCEED 300 CFM ONCE
 VENTILATION RATES ARE RECALCULATED PER COMMENT ABOVE.
 IF SO, PROVIDE MOTORIZED VOLUME DAMPERS IN ACCORDANCE
 WITH FBC-B 13-409.AB.3.3.
  
 ENERGY CALCULATIONS: THE METHOD A COMPLIANCE FORM
 SUBMITTED WILL NOT BE REVIEWED FOR THIS PROJECT. THIS
 IS AN ALTERATION TO A PORTION OF AN EXISTING BUILDING
 WHICH DOES NOT MEET THE DEFINITION OF A RENOVATION. AN
 ENERGY CODE COMPLIANCE FORM IS NOT REQUIRED. THE
 DESIGNER IS ONLY REQUIRED TO DEMONSTRATE COMPLIANCE
 WITH THE PRESCRIPTIVE MINIMUM REQUIREMENTS FOR NEW
 SYSTEMS BEING INSTALLED IN ACCORDANCE WITH FBC-B
 13-101.6.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-10-01 Cont ID  
Sent By kstevens Date 2009-10-01 Time 09:25 Rev Time 0.00
Received By kstevens Date 2009-10-01 Time 09:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-08-26 Cont ID  
Sent By kstevens Date 2009-08-26 Time 16:00 Rev Time 0.00
Received By kstevens Date 2009-08-26 Time 16:00 Sent To  
Notes
2009-08-26 16:13:03DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
  
 1. SHT A-1.0 A DRINKING FOUNTAIN IS REQUIRED PER TABLE
 403.1. INDICATE THE LOCATION OF THE DRINKING FOUNTAIN
 AND SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 WITH ALL SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10)(A) PROVISIONS FOR THOSE WHO HAVE
 DIFFICULTY BENDING OR STOOPING.
  
 2. SHT A-3.0 SHOW COMPLIANCE FOR THE FOLLOWING
 ACCESSIBILITY REQUIREMENTS:
 ___FOR W/C'S
 A. 11-4.16.3 HEIGHT
 B. 11-4.16.5 FLUSH CONTROLS
 C. FIG. 28 W/C SHALL BE 1'6" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE
 ___FOR LAVS
 A. 11-4.19.4 EXPOSED PIPES & SURFACES
 B. 11-4.19.5 FAUCETS
 C. 1104.19.3 LAV SHALL BE MINIMUM 15" OFF THE WALL TO
 THE CENTERLINE OF THE FIXTURE.
  
 3. SHT P1.01 KEY NOTES #4 THE CONDENSATE SHALL BE PIPED
 OUT SEPARATELY OUT OF THE BUILDING AND DRAIN INTO THE
 STORM LINE WITH A RELIEF VENT, (GOOSENECK), INSTALLED
 AS THE CONDENSATE EXITS THE BUILDING, OR TO A DRYWELL
 OR A PLANTED AREA. THIS SHALL BE CORRECTED ON SHT
 P-2.01 RISER #1 RAIN WATER AS WELL. SECTION 313.2.1.
  
 4. SHT P-2.01 RISER #1 RAIN WATER SHOW ALL PIPE SIZES
 AND INDICATE THE SQUARE FOOTAGE BEING DRAIN BY EACH
 DRAIN. TABLE 1106.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2009-09-14 Cont ID  
Sent By aaponte Date 2009-09-14 Time 10:51 Rev Time 0.00
Received By aaponte Date 2009-09-14 Time 10:51 Sent To  
Notes
***NONE***