Plan Review Details - Permit 09080497
Plan Review Stops For Permit 09080497
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-09-10 Cont ID  
Sent By jwitmer Date 2009-09-10 Time 12:21 Rev Time 0.25
Received By jwitmer Date 2009-09-10 Time 12:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-08-25 Cont ID  
Sent By jwitmer Date 2009-08-25 Time 14:46 Rev Time 1.00
Received By jwitmer Date 2009-08-24 Time 16:08 Sent To  
Notes
2009-08-25 15:18:42BUILDING PLAN REVIEW
 PERMIT: 09080497
 ADD: 734 20TH ST
 CONT: BLACK STREET ENTERPRISES, LLC
 TEL: (561)931-5707
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
  
 AUGUST 25/2009
 1ST REVIEW
 ACTION: DENIED
  
 1) ISSUES WITH GLAZED WINDOW UNITS:
 1A) SUBMITTED ALONG WITH THE PERMIT APPLICATION WAS A
 CLOSED SHUTTER PERMIT# 08080461 AN ATTACHED COPY IS
 ENCLOSED. PLEASE NOTE THAT THE BEDROOM WINDOWS UNDER
 THE PLANS SUBMITTED INDICATE THE BEDROOM WINDOW SILLS
 TO BE LOWERED FOR EMERGENCY EGRESS REQUIREMENTS. THE
 SHUTTERS FOR THE BEDROOM WINDOWS WILL NOW BE TO SHORT
 SINCE THEY WERE INDICATED AS BEING INSTALLED VERTICALLY
 TTHE SHUTTER WILL NOT BE ATTACHED AT THE NEW SILL
 HEIGHT. PLEASE ALSO SUBMIT NEW SHUTTER SCHEDULE FOR
 THESE WINDOWS AND PRODUCT APPROVAL FOR STORM SHUTTERS
 OR IF SHUTTERS TO BE INSTALLED HORIZONTALLY THEN SUBMIT
 A NEW SHUTTER SCHEDULE FOR ALL WINDOWS WHERE THE WINDOW
 SILL IS GOING TO BE LOWERED.
  
 1B) PLEASE ALSO REVIEW THE SHUTTER KEY PLAN VERSES THE
 FLOOR PLAN BEDROOM# 3 ON THE SHUTTER KEY PLAN INDICATES
 WINDOW 2 & 3 IN THE WALL WHERE THE FLOOR PLAN ONLY
 INDICCATES ONE WINDOW, PLEASE ALSO SEE THE SAME
 CONDITION HAPPENS IN THE LIVING ROOM WITH WINDOWS 7& 8.
 PLEASE REVIEW AND INDICATE COMPLIANCE WITH THE LARGE
 MISSILE IMPACT REQUIREMENTS.
  
 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2. GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 M)
 ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 2) THE NEW A/C CLOSET PLEASE PROVIDE A WALL SECTION
 INDICATING TMATERIALS TO BE USED IN CREATING THIS NEW
 WALL. 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 3) PLANS ALSO INDICATE THE REMOVAL OF CONCRETE SLAB AND
 REPOURING OF SLAB, PLEASE INDICATE COMPLIANCE WITH
 TERMITE TREATMET 1503.3.6 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN SPOUTS SHALL
 DISCHARGE AT LEAST 1 FT. AWAY FROM THE STRUCTURE
 SIDEWALL, WHETHER BY UNDERGROUND PIPING, TAIL
 EXTENSIONS, OR SPLASH BLOCKS.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-09-10 Cont ID  
Sent By jwitmer Date 2009-09-10 Time 12:35 Rev Time 0.22
Received By jwitmer Date 2009-09-10 Time 12:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-08-25 Cont ID  
Sent By jwitmer Date 2009-08-25 Time 1:22 Rev Time 2.00
Received By jwitmer Date 2009-08-25 Time 11:21 Sent To  
Notes
2009-08-25 12:31:58ELECTRICAL PLAN REVIEW
 PERMIT: 09080497
 ADD: 734 20TH ST
 CONT: BLACK STREET ENTERPRISES, LLC
 TEL: (561)931-5707
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 2005 NEC
  
 AUGUST 25/2009
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS ARE NOT CLEAR AS IF THE ELECTRICAL RISER (NEW
 SERVICE) WILL BE REPLACED AS PART OF THE ELECTRICAL
 SCOPING OF THIS PERMIT, THIS INFORMATION WILL EFFECT
 THE OUTCOME OF THIS REVIEW.
  
 1A) IF THE EXISTING ELECTRICAL SERVICE IS TO BE USED,
 THEN SECTION 220.83 (B) OR 100% OF THE HEATING AND A/C
 LOADS MUST BE USED.
  
 2) RISER DIAGRAM IS MISSING GROUNDING CONDUCTOR SIZING,
 TABLE 250.122 MINIMUM SIZE EQUIPMENT GROUNDING
 CONDUCTORS FOR GROUNDING RACEWAY AND EQUIPMENT,
 100 AMP PANEL / # 8 COPPER AWG.
  
 3) 422.13 STORAGE-TYPE WATER HEATERS A FIXED
 STORAGE-TYPE WATER HEATER THAT HAS A CAPACITY OF 450 L
 (120 GAL) OR LESS SHALL BE CONSIDERED A CONTINUOUS
 LOAD.
 THE REVISION TO 422.13 SPECIFICALLY IDENTIFIES AN
 ELECTRIC WATER HEATER WITH A STORAGE CAPACITY OF 120
 GAL OR LESS AS A CONTINUOUS LOAD. THIS REVISION
 REQUIRES THE BRANCH CIRCUIT OVERCURRENT DEVICE AND
 CONDUCTORS TO BE SIZED BASED ON 125 PERCENT OF THE
 WATER HEATER NAMEPLATE RATING UNLESS THE OVERCURRENT
 DEVICE AND THE ASSEMBLY IT IS INSTALLED IN ARE LISTED
 TO BE USED AT 100 PERCENT OF ITS CONTINUOUS CURRENT
 RATING.
  
 4) NEW MECHANICAL DISCONNECT FOR COMPRESSOR IS
 INDICATED BEHIND THE COMPRESSOR. PLEASE REVIEW SECTION
 440.63 DISCONNECTING MEANS AN APPROVED MANUALLY
 OPERABLE DISCONNECTING MEANS IS INSTALLED IN A READILY
 ACCESSIBLE LOCATION WITHIN SIGHT.
  
 5) THE NEW WALL OF THE AIR HANDLIER CLOSET ADJACENT TO
 BEDROOM # 1 IS MISSING OUTLETS,WHEN NEW WALL SECTIONS
 ARE OVER 2'0" LONG, SEE SECTION 210.52(A)(2)(1) ANY
 SPACE (2 FT) OR MORE IN WIDTH (INCLUDING SPACE MEASURED
 AROUND CORNERS) AND UNBROKEN ALONG THE FLOOR LINE BY
 DOORWAYS, FIREPLACES, AND SIMILAR OPENINGS .
  
 6) PLEASE NOTE THE LOCATION OF SMOKE ALARM LOCATED
 OUTSIDE OF THE BEDROOMS, PLEASE SEE NFPA 72
 REQUIREMENTS AS WELL AS MANUFACTURERS LOCATION AS TO
 SUPPLY / RETURN AIR GRILLES AS WELL AS BATHROOM
 LOCATIONS.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 SFP-100
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-08 Cont ID  
Sent By jwitmer Date 2009-09-08 Time 14:37 Rev Time 0.00
Received By jwitmer Date 2009-09-08 Time 14:37 Sent To  
Notes
2009-09-08 14:37:32INCOMING TO R-12

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-08-27 Cont ID  
Sent By jwitmer Date 2009-08-27 Time 14:37 Rev Time 0.00
Received By jwitmer Date 2009-08-20 Time 10:37 Sent To  
Notes
2009-08-20 10:38:04R-14

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2009-09-21 Cont ID  
Sent By rkussner Date 2009-09-21 Time 10:23 Rev Time 0.00
Received By rkussner Date 2009-09-21 Time 10:23 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-10-20 Cont ID  
Sent By rbrown Date 2009-10-20 Time 09:00 Rev Time 0.00
Received By rbrown Date 2009-10-20 Time 08:53 Sent To  
Notes
2009-10-20 08:59:58MECHANICAL ROUGH INSPECTION FAILED ON 10/1/09 FOR
 "RETURN AIR NOT PER PLAN". SUBMITTED REVISED DETAILS
 ARE JUST MARKED UP ON A COPY OF THE ARCHITECT'S PLAN
 AND CANNOT BE PASSED BY PLAN REVIEW. INSPECTION CAN BE
 PERFORMED WITHOUT A REVISED PLAN AND PLAN REVIEW THIS
 KIND OF FIELD CHANGE. INSPECTION HAS BEEN SCHEDULED FOR
 10/21/09.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 TELEPHONE: (561) 805 6652 ROBERT BROWN
 E-MAIL: [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-08-25 Cont ID  
Sent By jwitmer Date 2009-08-25 Time 15:24 Rev Time 0.70
Received By jwitmer Date 2009-08-25 Time 15:24 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-08-20 Cont ID  
Sent By kstevens Date 2009-08-20 Time 14:04 Rev Time 0.00
Received By kstevens Date 2009-08-20 Time 14:04 Sent To  
Notes
2009-08-20 14:06:25NO PLUMBING PLANS SUBMITTED OR REQUIRED FOR PLUMBING
 WORK INDICATED ON THE APPLICATION.

Review Stop Z ZONING
Rev No 2 Status P Date 2009-09-14 Cont ID  
Sent By jroach Date 2009-09-14 Time 22:31 Rev Time 0.00
Received By jroach Date 2009-09-14 Time 22:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-08-27 Cont ID  
Sent By mcruz Date 2009-08-27 Time 19:29 Rev Time 0.00
Received By mcruz Date 2009-08-27 Time 19:22 Sent To  
Notes
2009-08-27 19:28:34PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-441(C)(2) OF: AS THE VALUE OF THE PROPOSED WORK
 EXCEEDS 50% OF THE STRUCTURE'S VALUE (LISTED AS
 "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 3. INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES. PURSUANT THE ZLDR,
 SECTION 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  