Plan Review Details - Permit 09080496
Plan Review Stops For Permit 09080496
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-11-20 Cont ID  
Sent By jwitmer Date 2009-11-20 Time 15:29 Rev Time 0.33
Received By jwitmer Date 2009-11-20 Time 15:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-09-23 Cont ID  
Sent By jwitmer Date 2009-09-23 Time 14:50 Rev Time 1.30
Received By jwitmer Date 2009-09-23 Time 13:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-09-09 Cont ID  
Sent By jwitmer Date 2009-09-09 Time 08:04 Rev Time 0.77
Received By jwitmer Date 2009-09-08 Time 15:01 Sent To  
Notes
2009-09-09 08:07:00PLANS APPEAR TO BE CODE COMPLIANT, ONCE A LICENSED
 CONTRACTOR HAS SIGNED ON AND LICENSE RESTRICTIONS HAVE
 BEEN REVIEWED PLANS WILL BE STAMPED AND REVIEW WILL BE
 PASSED.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-12-16 Cont ID  
Sent By btrobaug Date 2009-12-16 Time 15:00 Rev Time 0.00
Received By btrobaug Date 2009-12-16 Time 15:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-09-28 Cont ID  
Sent By dwise Date 2009-09-28 Time 09:13 Rev Time 0.00
Received By dwise Date 2009-09-28 Time 09:13 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-08-25 Cont ID  
Sent By btrobaug Date 2009-08-25 Time 16:33 Rev Time 0.00
Received By btrobaug Date 2009-08-25 Time 15:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-12-01 Cont ID  
Sent By mawillia Date 2009-12-01 Time 12:36 Rev Time 0.00
Received By mawillia Date 2009-12-01 Time 12:21 Sent To  
Notes
2009-12-01 12:34:20*****REVISION, DATED 10/28/09, APPROVED*****
  
 REVISED PLAN SHEETS A1.01, A3.01, AND E2.01 WERE
 STAMPED, INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-09-23 Cont ID  
Sent By mawillia Date 2009-09-23 Time 15:29 Rev Time 0.00
Received By mawillia Date 2009-09-23 Time 14:54 Sent To  
Notes
2009-09-23 15:24:20*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS A1.01, A3.01, A8.03, AND E2.01
 WERE STAMPED, INITIALED, AND DATED. SHEET FS1.01 WAS
 FIRE-STAMPED AT THE THE TIME OF THE PREVIOUS REVIEW.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-08-27 Cont ID  
Sent By mawillia Date 2009-08-27 Time 14:16 Rev Time 0.00
Received By mawillia Date 2009-08-27 Time 13:07 Sent To  
Notes
2009-08-27 13:52:33*****DENIED*****
  
 PLAN SHEET FS1.01 WAS STAMPED, INITIALED, AND DATED;
 HOWEVER THE FOLLOWING COMMENTS NEED TO BE SATISFIED FOR
 FIRE REVIEW APPROVAL:
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241- 2004
 EDITION.
  
 2. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 3. BE ADVISED OF THE CURRENTLY ADOPTED CODE EDITIONS AS
 FOLLOWS: FLORIDA BUILDING CODE - 2007 EDITION, FLORIDA
 FIRE PREVENTION CODE - 2007 EDITION, .......ON SHEET
 A1.01, AMEND APPLICABLE CODES
  
 4. ON SHEET A1.01, FIRE EXTINGUISHERS ARE SHOWN IN
 ROOMS 312, 315, AND 328; HOWEVER ON SHEET A1.03, A FIRE
 EXTINGUISHER IS SHOWN IN ONLY ROOM 315........THESE
 SHEETS SHOULD CORRELATE
  
 5. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE WALLS
 AND CEILING IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 6. VERITY/CLARIFY THAT DOORS CLOSERS WILL BE REQUIRED
 FOR DOORS 300 AND 317.................ON SHEET A3.01,
 INCLUDE IN DOOR SCEDULE - REMARKS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-11-09 Cont ID  
Sent By jgomez Date 2009-11-09 Time 08:45 Rev Time 0.00
Received By jgomez Date 2009-11-09 Time 08:45 Sent To  
Notes
2009-11-09 09:00:48SENT TO BOX #C21.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-16 Cont ID  
Sent By kstevens Date 2009-09-16 Time 08:53 Rev Time 0.00
Received By kstevens Date 2009-09-16 Time 08:53 Sent To  
Notes
2009-09-16 08:54:16SENT TO C-37.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-09-09 Cont ID  
Sent By jwitmer Date 2009-09-09 Time 08:04 Rev Time 0.00
Received By jwitmer Date 2009-08-20 Time 17:38 Sent To  
Notes
2009-08-20 17:38:58B-11

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date   Cont ID  
Sent By   Date 2009-12-01 Time   Rev Time 0.00
Received By rregueir Date 2009-12-01 Time 20:41 Sent To  
Notes
2009-12-01 20:47:50REVISED M1.01 DELTA 2

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-09-23 Cont ID  
Sent By rregueir Date 2009-09-23 Time 14:47 Rev Time 0.00
Received By rregueir Date 2009-09-23 Time 14:47 Sent To  
Notes
2009-09-23 14:47:41NEW SHEETS STAMPED. ALL PROVISOS ADDRESSED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-09-01 Cont ID  
Sent By rregueir Date 2009-09-01 Time 17:47 Rev Time 0.00
Received By rregueir Date 2009-09-01 Time 16:54 Sent To  
Notes
2009-09-01 17:46:40**PROVISO**
 1. DUCT SMOKE DETECTORS REQUIRED ON ALL THREE AIR
 HANDLERS PER FBC-M 606.2.2. CONNECT DETECTORS TO
 BUILDING FIRE ALARM SYSTEM PER FBC-M 606.4. REVISE
 PLANS AND RESUBMIT, SHOWING THIS CORRECTION.
  
 2. OUTSIDE AIR INTAKE TO BE INSTALLED PER ATTACHED NOA,
 NOT THE DETAIL ON PAGE M2.01.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 4 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By dwise Date 2009-12-17 Time 13:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-09-28 Cont ID  
Sent By dwise Date 2009-09-23 Time 09:12 Rev Time 0.00
Received By dwise Date 2009-09-23 Time 09:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2009-09-22 Cont ID  
Sent By kstevens Date 2009-09-22 Time 12:53 Rev Time 0.00
Received By kstevens Date 2009-09-22 Time 12:53 Sent To  
Notes
2009-09-22 12:55:17DENIED
 REFERENCE:
 FBC-2007 EXISTING BUILDING
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. THE "CITY PLACE" MANAGEMENT REVIEW/APPROVAL STAMP IS
 REQUIRED ON ALL SHEETS PRIOR TO SUBMITTING TO THE CITY
 WPB FOR REVIEW.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 2. ALL SHEETS WITH BETA DESIGN TITLE BLOCK IS REQUIRED
 TO HAVE THE FIRM NUMBER, (CERTIFICATE OF AUTHORIZATION
 NUMBER) IN THE TITLE BLOCK. FAC 61G1-16.004(2) & FS
 481.025.
 ****RESPONSE NOTED, COMMENT NOT ADDRESSED.
  
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10 OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-08-24 Cont ID  
Sent By kstevens Date 2009-08-24 Time 09:09 Rev Time 0.00
Received By kstevens Date 2009-09-08 Time 15:57 Sent To  
Notes
2009-08-24 09:33:25DENIED
 REFERENCE:
 FBC-2007 EXISTING BUILDING
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. THE "CITY PLACE" MANAGEMENT REVIEW/APPROVAL STAMP IS
 REQUIRED ON ALL SHEETS PRIOR TO SUBMITTING TO THE CITY
 WPB FOR REVIEW.
  
 2. ALL SHEETS WITH BETA DESIGN TITLE BLOCK IS REQUIRED
 TO HAVE THE FIRM NUMBER, (CERTIFICATE OF AUTHORIZATION
 NUMBER) IN THE TITLE BLOCK. FAC 61G1-16.004(2) & FS
 481.025.
  
 4. SHT A1.01 APPLICABLE CODES. ALL PLANS SUBMITTED FOR
 REVIEW AFTER MARCH 1, 2009 SHALL BE DESIGNED TO THE
 FLORIDA BUILDING CODE 2007 CYCLE WITH 2009 SUPPLEMENTS.
 SECTION 106.1.1. FBC-2004 W/2007 REVISIONS IS NOW
 INDICATED.
  
 5. A DESIGN PROFESSIONAL OR OWNER MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION PURSANT TO SECTIONS
 403, 404 & 405 OF THE EXISTING BUILDING CODE. SECTION
 401.4. PLEASE INDICATE LEVEL OF ALTERATION.
  
 6. PLEASE INDICATE THE OCCUPANCY OF THE SPACE/UNIT.
 SECTION 401.3.
  
 7. SHT A1.01 THE CLEAR FLOOR SPACE FOR THE LOUNGE SINK
 SHALL BE FORWARD APPROACH PER SECTION 11-4.24.5.
 PARALLEL APPROACH IS SHOWN. PLEASE SHOW CORRECT CLEAR
 FLOOR SPACE.
  
 8. SHT A1.02 TOILET ROOMS 319 & 320 SHOW PAINT FOR THE
 FINISH OF THE WALLS. PER SECTION 1210.2 WALLS WITHIN 2
 FEET OF THE WATER CLOSETS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE THAT EXTENDS UP TO 4 FEET ABOVE
 THE FLOOR. PAINTED SURFACES DOES NOT MEET THE "HARD"
 REQUIREMENT.
  
 9. SHT A1.04 FIXTURES & ACCESSORY MOUNTING REQUIREMENTS
 FOR THE W/C, & DETAIL J/A1.04 SHOW THE W/C TO BE 1'5"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. PER
 FIGURE 28 IN CHAPER 11 THE W/C SHALL BE 1'6" OFF THE
 WALL TO THE CENTERLINE OF THE FIXTURE. PLEASE SHOW THE
 CORRECT MEASUREMENT TO THE CENTERLINE OF THE FIXTURE.
  
 10 SHT P1.01 KEY NOTES 1, 2 & 4. DEAD ENDS ARE
 PROHIBITED PER SECTION 704.5. ALL DEMO'D PIPING WILL BE
 REQUIRED TO BE CAPPED NO MORE THAN 2 FEET FROM AN
 ACTIVE SANITARY DRAIN LINE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2009-09-28 Cont ID  
Sent By dwise Date 2009-09-28 Time 09:15 Rev Time 0.00
Received By dwise Date 2009-09-28 Time 09:15 Sent To  
Notes
2009-09-28 09:16:14PLANS STAMPED IN OFFICE WITH CITY PLACE APPROVAL BY
 MIKE STELLINO.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-08-20 Cont ID  
Sent By eschneid Date 2009-08-20 Time 18:01 Rev Time 0.25
Received By eschneid Date 2009-08-20 Time 18:00 Sent To  
Notes
2009-08-20 18:01:44CITYPLACE STAMP REQUIRED.
  
 OTHERWISE ZONING HAS NO ISSUES.