| 2009-08-20 09:37:13 | PASSED WITH PROVISOS: |
| | 1. LOCATION MAP IS FOR BANYAN AND AUSTRALIAN NOT PARKER |
| | AND BELVEDERE. |
| | 2. WIDTH IS GIVEN AS 14??? FOR THE POLE BASE, IT IS |
| | SITTING ON THE 30??? CONCRETE BASE ABOVE THE SIDEWALK, |
| | SO THE CLEARANCE IS BASED ON THE CONCRETE BASE. |
| | SIDEWALK ON PARKER IS 5??? WIDE (TOP OF CURB CAN NOT BE |
| | COUNTED), POLE BASE IS 30???. THIS WOULD GIVE A MINIMUM |
| | OF 30??? FOR ADA (WHEEL CHAIR) ACCESS AROUND THE POLE, |
| | THIS IS NOT ENOUGH SPACE. THE CONCRETE BASE FOR THE |
| | POLE NEEDS TO BE MODIFIED, SO THERE IS AT LEAST 36" OF |
| | PASSABLE SPACE FOR A WHEEL CHAIR. AN ADDITIONAL WIND |
| | LOAD DIAGRAM WILL BE REQUIRED FOR THE NEW POLE BASE. |
| | 3. WIND LOAD DIAGRAM AND DRAWING ON SHEET 5 OF 8 DO NOT |
| | MATCH, WHICH HAS THE CORRECT MEASUREMENTS? |
| | 4. ACCORDING TO THE WIND LOAD DRAWINGS; THE CAMERA(S) |
| | STICK OUT 36??? FROM THE FACE OF THE POLE |
| | THE POLE WIDTH IS 4.5??? |
| | FROM THE CENTER OF THE POLE TO BACK OF SIDEWALK IS |
| | 15???. |
| | FROM CENTER OF POLE TO OUTSIDE OF CAMERA IS 38.25???. |
| | THIS MEANS THE CAMERA AND MOUNT ARE STICKING OUT OVER |
| | PRIVATE PROPERTY 23.25???. THIS IS NOT ALLOWED, UNLESS |
| | YOU HAVE AN EASEMENT FROM THE PROPERTY OWNER. |
| | 5. THE CAMERA(S) STICK OUT 36??? FROM THE FACE OF THE |
| | POLE |
| | THE POLE WIDTH IS 4.5??? |
| | FROM THE CENTER OF THE POLE TO BACK OF SIDEWALK IS |
| | 15???. |
| | FROM CENTER OF POLE TO OUTSIDE OF CAMERA IS 38.25???. |
| | FROM THE CENTER OF THE POLE TO THE EDGE OF CURB IS |
| | 40??? |
| | THIS MEANS THE CAMERA AND MOUNT ARE STICKING OUT OVER |
| | THE SIDEWALK AND POSSIBLY OUT INTO THE STREET AT A |
| | HEIGHT OF 10???. THIS CAN NOT BE ALLOWED, THE MINIMUM |
| | HEIGHT FOR ANY OBJECT HANGING OVER THE ROAD IS 14' |
| | 6. DRAWING ON SHEET 5 OF 8 SHOWS A 17.25??? BOX HANGING |
| | ON THE BACK OF THE POLE, ALL OF WHICH WILL BE ON |
| | PRIVATE PROPERTY. DO YOU HAVE AN EASEMENT TO PLACE THIS |
| | ON (OVER) PRIVATE PROPERTY? |
| | 7. SHEET 2 OF 8, SHOWS AN ???EXISTING POWER SOURCE???. |
| | THERE IS NO FP&L POWER SOURCE AT THAT LOCATION, THE |
| | CLOSEST LOCATION FOR POWER AND WHERE YOUR ELECTRIC |
| | METER WILL NEED TO BE MOUNTED IS IN THE UNDEVELOPED |
| | ALLEY TO THE NORTH OF THE GAS STATION PROPERTY |
| | (100+-???). |
| | 8. SHEET 6 OF 8, SHOWS THE FP&L METER ON A CONCRETE |
| | BASE, BUT IT GIVES NO DIMENSIONS, WHAT ARE THE |
| | DIMENSIONS AND IT CAN NOT GO IN THE SIDEWALK. |
| | 9. ROW PERMITS ARE REQUIRED FROM CITY ENGINEERING |
| | DEPARTMENT. |
| | 10. EASEMENTS/REVOKABLE PERMITS MAY BE REQUIRED. |
| | 11. AS-BUILTS ARE REQUIRED, PAPER, SIGNED AND SEALED AS |
| | WELL AS AUTO CADD |
| | |