| 2009-09-18 10:34:32 | |
| | ** FAILED REVIEW ** |
| | |
| | 1) NOTE: PERMIT HAS NOT BEEN APPLIED FOR UNDER A |
| | LICENSED CONTRACTOR. |
| | |
| | 2) NOTE: PLANS INDICATE TWO LIGHTING CIRCUITS. 16MA-27 |
| | AND 16MA-29, HOWEVER PANEL SCHEDULE DOES NOT LIST |
| | CIRCUIT 27 FOR THIS TENANT. IT DOES LIST CIRCUIT #31, |
| | WHICH IS NOT ON THE PLANS. |
| | IF THIS HAD BEEN THE ONLY COMMENT PLANS WOULD HAVE BEEN |
| | REDLINED. |
| | |
| | 3) NOTE: PLEASE CORRELATE RISER AND PANELS. PLEASE SEE |
| | 16MA PANEL ON RISER. THIS IS THE 277/480V 225AMP PANEL |
| | WHICH IS SHOWN FEEDING TRANSFORMER AND OTHER PANELS. |
| | HOWEVER THE PANEL SCHEDULE FOR 16MA STATES THE SUB FEED |
| | TO THE SAME PANEL 16MA. ( MISPRINT?) |
| | PLEASE SEE THE RISER WHICH INDICATES TWO SECONDARY TAPS |
| | FROM THE 75KVA TRANSFORMER. ONE TAP TO 16LA AND ONE TO |
| | 16LB. PER THE TRANSFORMER SCHEDULE THE SECONDARY |
| | CONDUCTORS ARE ONLY ONE SET OF 250MCM. |
| | THERE ARE TWO COMMENTS HERE. |
| | A) THERE IS ONLY ONE SET INDICATED, WHERE IS THE OTHER |
| | ONE? |
| | B) PANEL 16LA IS SHOWN AS A 100AMP MCB. 250 MCM WILL |
| | NOT FIT UNDER LUGS OF A 100AMP BREAKER. THIS IS |
| | BASICALLY THE SAME COMMENT FOR 16LB WHICH IS A 150AMP |
| | MCB PANEL WITH 250MCM. |
| | |
| | PLEASE MAKE ADJUSTMENTS AND CORRECTIONS. |
| | 310.16,240.4,240.21C, 408.36 ETC SHOW TAPPED CONDUCTORS |
| | TO EACH. |
| | |
| | 4) NOTE: PLEASE SEE KEY PLAN ON SHEET E-0.1. IN THE |
| | LOWER LEFT HAND SIDE IN THE STORAGE ROOM OF THIS NEW |
| | TENANT SPACE THERE APPEARS TO BE NEW PANELS. THERE ARE |
| | DARK SQUARE SHAPES WHICH APPEAR TO BE PANELS. BASED ON |
| | THE REST OF THE PLANS THERE ARE NO PANELS IN THE |
| | STORAGE ROOM. PLEASE SEE 110.26 AND 240.24D AS THESE |
| | WOULD NOT BE PERMITTED IN STORAGE CLOSETS. |
| | |
| | 5) NOTE: PANEL 16LA AS SHOWN ON E0.1 DOES NOT MEET |
| | 110.26 AS SHOWN. PLEASE VERIFY AND RELOCATE AS THIS IS |
| | A SAFETY CODE COMMENT. |
| | |
| | 6) NOTE: THE AMOUNT OF FIXTURES INDICATED FOR THE |
| | CORRIDOR PERFORMANCE CALCULATIONS ARE SHORT BY A |
| | RECESSED LIGHTING FIXTURE. STATES 5 WHEN THERE ARE |
| | 6.THIS WOULD NOT BE CONSIDERED A GROSS ERROR PER |
| | 13-103.1 |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |