| 2009-09-18 13:34:09 | ** FAILED REVIEW ** |
| | |
| | 1) NOTE: PERMIT HAS NOT BEEN APPLIED FOR UNDER A |
| | LICENSED CONTRACTOR. |
| | |
| | 2) NOTE: THE SUBMITTED RISER AS SHOWN ON E5.1 CONTAINS |
| | A SUBSTANTIAL AMOUNT OF CODE VIOLATIONS. THE RISER |
| | SHOWN FOR FEEDS TO FIRE PUMP AND SEVERAL OTHER ASPECTS |
| | OF SERVICE AS SHOWN IN VIOLATION OF TOO MANY CODES TO |
| | NOTE. THE APPLIED SCOPE OF WORK IS FOR THE SECOND FLOOR |
| | TENANT. PLEASE ONLY INCLUDE ELECTRICAL FOR THIS |
| | RELEVANT SPACE AND EQUIPMENT ONLY. |
| | ** IT SHOULD BE NOTED IF THE ELECTRICAL AS SHOWN ON |
| | RISER IS THE ACTUAL INSTALLATION THERE SHOULD BE |
| | CONCERNS OVER THE INSTALLATION AS SHOWN. |
| | THERE ARE SEVERAL ITEMS SHOWN ON RISER WHICH ARE LIFE |
| | SAFETY AND FIRE HAZARDS CONCERNS. IF RISER IS ACCURATE |
| | THEN THESE ITEMS SHOULD BE ADDRESSED BY THE APPROPRIATE |
| | PARTIES RESPONSIBLE FOR THE BUILDING. |
| | PLEASE SEE NFPA-110, NFPA-20 AND NFPA-70 FOR LIFE |
| | SAFETY, LEGALLY REQUIRED SYSTEMS ALONG WITH FIRE PUMP |
| | INSTALLATION MINIMUMS. |
| | |
| | ** THIS WAS NOTED ON A PREVIOUS PLAN REVIEW SEVERAL |
| | YEARS AGO. |
| | |
| | 2) NOTE: THERE ARE INCONSISTENCIES WITH RISER ON PLANS |
| | SUBMITTED FOR THIS SPACE AND PREVIOUSLY REVIEWED PLANS. |
| | THE PLAN REVIEW ON SUITE #200 AND #202 HAD COMMENTS |
| | WITH THE RESPECT TO LOADS ON PANEL 2MA. THIS WOULD |
| | AFFECT THE LOAD SHOWN ON 1MA ON THIS PLANS. |
| | THIS RISER IS COMPLETELY DIFFERENT. |
| | |
| | A) THERE ARE NO OTHER PANELS ON THE LOAD SIDE OF THE |
| | TRANSFORMER FED FROM 2MA EXCEPT 2LA. |
| | B) THE PANEL SCHEDULE FOR 1MA STATES IT HAS A FEED TO |
| | PANEL 1XA, HOWEVER BASED ON THE RISER 1XA IS NOT EVEN |
| | FED FROM 1MA. |
| | C) PANEL 1MA DOES NOT LIST ANY OTHER PANELS SUCH AS |
| | 2MA. IS THIS A FEED-THRU PANEL? |
| | |
| | PLEASE SEE 450 FOR MAXIMUM ALLOWABLE LOADS. PLEASE SEE |
| | NEC 220.12,220.14,220.42,220.44 ETC ALONG WITH |
| | 215.3,230.42. |
| | LOAD CALCULATIONS SHOULD BE DONE TO ACCURATELY DEPICT |
| | ACTUAL LOAD ON SERVICE EQUIPMENT, TRANSFORMER |
| | PLEASE COORDINATE ALL EQUIPMENT FOR COMPLETED REVIEW. |
| | PLEASE SHOW EQUIPMENT SPECIFIC TO SCOPE OF WORK AND ANY |
| | EQUIPMENT WHICH IS BEING AFFECTED BY NEW WORK. |
| | |
| | 3) NOTE: PLEASE BE SURE ALL SHEETS ARE SIGNED THE SAME. |
| | INITIALS ON SOME SHEETS? |
| | FS 471.025 |
| | |
| | 4) NOTE: LIGHTING CIRCUITS FOR SUITE #103 NEED TO BE |
| | SPECIFIC AND IDENTIFIED ON 1MA. ONLY STATES *LTS*. |
| | PLEASE BE SURE THIS IS SPECIFIC AS REQUIRED BY REVISED |
| | 408.4. |
| | ** IF THIS WAS THE ONLY COMMENT OR ONE OF MINOR |
| | COMMENTS IT WOULD HAVE BEEN REDLINED. |
| | |
| | 5) NOTE: PANEL 1LA IS SHOWN AS A THREE PHASE PANEL. |
| | HOWEVER BASED ON THE PANEL SCHEDULE ITSELF, THIS IS |
| | ALSO SHOWN AS A SINGLE PHASE PANEL. WHICH IS IT? |
| | PLEASE COORDINATE SO THAT AN ACCURATE REVIEW OF CODE |
| | REQUIRED CALCULATIONS CAN BE DONE. |
| | 215.5, 230,240, 220. GIVEN AS GENERAL CHAPTERS AS THERE |
| | ARE SEVERAL CODES WHICH WOULD APPLY. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |