Plan Review Details - Permit 09080416
Plan Review Stops For Permit 09080416
Review Stop G GAS REVIEW
Rev No 1 Status P Date 2009-08-18 Cont ID  
Sent By kstevens Date 2009-08-18 Time 09:49 Rev Time 0.00
Received By kstevens Date 2009-08-18 Time 09:49 Sent To  
Notes
2009-08-18 10:57:14PASSED/PROVISO:
  
 CONTRACTOR INDICATED 4 PSI DELIVERY PRESSURE, BUT
 PRESSURE VERIFIED IN THE FIELD AS 1/2 PSI. MINIMUM 1/2
 ID COPPER REQUIRED FOR PIPING UPSTREAM OF FIRST TEE.
 REGULATOR NOT REQUIRED AT COOKTOP.
  
  