Plan Review Details - Permit 09080239
Plan Review Stops For Permit 09080239
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-09-01 Cont ID  
Sent By kdfreema Date 2009-08-25 Time 08:32 Rev Time 1.00
Received By jwitmer Date 2009-09-01 Time 14:01 Sent To  
Notes
2009-09-01 14:36:31BUILDING PLAN REVIEW
 PERMIT: 09080239
 ADD: 5423 LAKE AVENUE
 CONT: R. O. VIAMONTE CONSTRUCTION CO.
 TEL: (561)523-0244
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
 SEPTEMBER 01,2009
 1ST REVIEW
 ACTION: DENIED
  
 1) I SHEET A1 INDICATES TYPE IV CONSTRUCTION (HEAVY
 TIMBER) SCOPE OF WORK NOTE # 3 INDICATES TO PROVIDE NEW
 TRUSSES OVER EXISTING BUILDING. NOTE PLEASE SEE SECTION
 602.4 THE INTERIOR BUILDING ELEMENTS ARE TO SOLID OR
 LAMINATED WOOD WITHOUT CONCEALED SPACES. SHEET A-3
 TRUSS PROFILE DOES INDICATE CONCEALED SPACE PLEASE
 RE-DEFINE BUILDING TYPE OF CONSTRUCTION.
  
 2) SHEET A-1 ALSO FAILS TO DECLARE TYPE OF ASSEMBLY
 OCCUPANCY 303.1, TABLE 503 AS FAR AS AREA AND ALLOWABLE
 STORY HEIGHT..
  
 3) IS THE BUILDING FIRE SPRINKLERED, THE EXISTING
 BUILDING DOES HAVE A 2 STORY PORTION AND IN RE-DEFINING
 THE MINIMUM BUILDING TYPE THE FIRE SPRINKLERS WILL ADD
 ANOTHER STORY 504.2 AND TABLE 503.
  
 4) THE ELEVATION SHEETS INDICATE APPROXIMATELY 50% OF
 THE WINDOWS BEING REMOVED BUT NO INFORMATION AS TO HOW
 THEY WILL TIE BACK INTO THE EXISTING WALL. 106.1.2
 ADDITIONAL INFORMATION REQUIRED,
 1609.6 & 2109.7.2.3 & 2109.7.2.5.
  
 5) SHEET D-1 INDICATES THE 2 STORY PORTION OF THE
 BUILDING HAS A FLAT ROOF, BUT SHEET A-3 HAS NO TRUSS
 PROFILE FOR THIS PORTION, IS THERE A PARAPET AROUND
 THIS PORTION OF THE BUILDING?
  
 6) BOTH SHEETS A-1 AND A-2 INDICATE NEW GABLE ENDS BUT
 THERE IS NO INFORMATION AS THE NEW GABLE WALL
 CONSTRUCTION ON THE CBS PORTION OF THE BUILDING.
 CONCRETE. 1918.3.1 GENERAL. GABLE END WALLS SHALL BE
 STRUCTURALLY CONTINUOUS BETWEEN POINTS OF LATERAL
 SUPPORT.
 MASONRY. 2115.1.1 GENERAL. GABLE END WALLS SHALL BE
 STRUCTURALLY CONTINUOUS BETWEEN POINTS OF LATERAL
 SUPPORT.
 STEEL STUD2115.1.1 GENERAL. GABLE END WALLS SHALL BE
 STRUCTURALLY CONTINUOUS BETWEEN POINTS OF LATERAL
 SUPPORT.
 WOOD STUDS2304.3.4.1 GENERAL. GABLE END WALLS SHALL BE
 STRUCTURALLY CONTINUOUS BETWEEN POINTS OF LATERAL
 SUPPORT.
 PLEASE PROVIDE A CUT SECTION THROUGH THIS WALL
 PROVIDING THE WALL CONSTRUCTION, TYPE OF ANCHORS AND
 COMPONENTS.
  
 7) THE TWO STORY SECTION OF THIS CBS BUILDING WITH A
 NEW SLOPED ROOF CREATING ATTIC SPACE. 1209.2 ATTIC
 SPACES. AN OPENING NOT LESS THAN 20 INCHES BY 30 INCHES
 (559 MM BY 762 MM) SHALL BE PROVIDED TO ANY ATTIC AREA
 HAVING A CLEAR HEIGHT OF OVER 30 INCHES (762 MM). A
 30-INCH (762 MM) MINIMUM CLEAR HEADROOM IN THE ATTIC
 SPACE SHALL BE PROVIDED AT OR ABOVE THE ACCESS OPENING.
  
 8) IN BOTH AREAS THE NEW 2 STORY PORTION AS WELL AS THE
 LARGER NEW SLOPED ROOF WILL NEED TO INDICATE :
 1203.2 ATTIC SPACES.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 FRAMING MEMBERS SHALL HAVE CROSS VENTILATION FOR EACH
 SEPARATE SPACE BY VENTILATING OPENINGS PROTECTED
 AGAINST THE ENTRANCE OF RAIN. BLOCKING AND BRIDGING
 SHALL BE ARRANGED SO AS NOT TO INTERFERE WITH THE
 MOVEMENT OF AIR. A MINIMUM OF 1 INCH (25 MM) OF
 AIRSPACE SHALL BE PROVIDED BETWEEN THE INSULATION AND
 THE ROOF SHEATHING. THE NET FREE VENTILATING AREA SHALL
 NOT BE LESS THAN 1 / 150 OF THE AREA OF THE SPACE
 VENTILATED, WITH 50 PERCENT OF THE REQUIRED VENTILATING
 AREA PROVIDED BY VENTILATORS LOCATED IN THE UPPER
 PORTION OF THE SPACE TO BE VENTILATED AT LEAST 3 FEET
 (914 MM) ABOVE EAVE OR CORNICE VENTS WITH THE BALANCE
 OF THE REQUIRED VENTILATION PROVIDED BY EAVE OR CORNICE
 VENTS.
  
 9) THE NEW OVERHANG OR COVERED WALKWAY DOES NOT
 INDICATE THE TYPE OF FINISH THAT WILL BE APPLIED TO THE
 UNDER SIDE OF THE BOTTOM CHORD OF THE HORIZONTAL
 FRAMING MEMBER OF THE TRUSS. PLEASE PROVIDE ADDITIONAL
 INFORMATION AS WELL AS TYPE OF EAVE VENTS THAT WILL BE
 USED. ADDITIONAL INFORMATION REQUIRED. 1203.2/ 106.1.2
 & 1609.6.
  
 10) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 10A) TRUSS ANCHORS
  
 11) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 12) STORM SHUTTERS PLEASE PROVIDE THE FOLLOWING
 INFORMATION ; PROVIDE STORM PANEL INFORMATION WITH
 INSTALLATION SCHEDULE AND KEY PLAN WITH SPECIFIC
 ANCHORS AND MOUNTING TO BE USED FOR ALL NON-IMPACT
 GLAZING. FBC 1609.1.4.
  
 FL BLD CODE 2004 SECTION 106.3.3,
 1609.1.4, 1714.5.1 & EXIST BUILD CODE 507.3.
 PROCEDURES: 1(B) A COMPLETE INSTALLATION SCHEDULE
 SUMMARIZING & IDENTIFYING OPENING SIZES, STORY HEIGHTS,
 UNIT MARK NUMBERS, UNIT SPANS/WIDTHS, UNIT STORM BAR
 REINFORCING REQUIREMENTS, WALL PRESSURE ZONES, SLAT
 TYPES, ETC., SHALL BE SUBMITTED AT TIME OF PERMIT
 APPLICATION TO FACILITATE PLAN REVIEW AND PERMIT
 ISSUANCE.
 SEE EXAMPLE ATTACHED.
  
 12) DISCREPANCIES SEE A2 VERSES A3 11/12 VERSES 12/12?
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-08-20 Cont ID  
Sent By kdfreema Date 2009-08-25 Time 08:32 Rev Time 0.00
Received By btrobaug Date 2009-08-20 Time 14:12 Sent To  
Notes
2009-08-20 14:35:34 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 REFERENCE SHEET E1:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 2} 13-415.AB.2.2 EXTERIOR BUILDING LIGHTING POWER. THE
 TOTAL EXTERIOR LIGHTING POWER ALLOWANCE FOR ALL
 EXTERIOR BUILDING APPLICATIONS IS THE SUM OF THE
 INDIVIDUAL LIGHTING POWER DENSITIES PERMITTED IN TABLE
 13-415.AB.2.2 FOR THESE APPLICATIONS PLUS AN ADDITIONAL
 UNRESTRICTED ALLOWANCE OF 5% OF THAT SUM. TRADE-OFFS
 ARE ALLOWED ONLY AMONG EXTERIOR LIGHTING APPLICATIONS
 LISTED IN THE TABLE 13-415.AB.2.2, "TRADABLE SURFACES"
 SECTION. EXTERIOR LIGHTING FOR ALL APPLICATIONS (EXCEPT
 THOSE INCLUDED IN THE EXCEPTIONS TO SECTION 13-415.0
 AND THIS SECTION) SHALL COMPLY WITH THE REQUIREMENTS OF
 SECTION 13-415.AB.2.1.*** COMPLY WITH SAME.THIS CAN BE
 DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF
 THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE
 DENSITY REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE
 SCHEDULE TO CORRELATE WITH THE ONES IN THE
 CALCULATIONS. SUBMIT A LEGEND OF FIXTURE TYPES AND
 WATTAGES ON THE PLAN TO CORRELATE WITH THE ONES IN THE
 CALCULATIONS.
  
 NOTE: LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR
  
 3} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 THE LUMINAIRES BEING INSTALLED.106.3.5.2 FBC AS
 AMENDED.
  
 4} NOTE: SEE NFPA-101 FOR EGRESS LIGHTING REQUIREMENTS,
 DEMONSRARE COMPLIANCE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  
  
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2009-10-05 Cont ID  
Sent By efabian Date 2009-10-05 Time 15:40 Rev Time 0.50
Received By efabian Date 2009-10-05 Time 15:40 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-10-05 Cont ID  
Sent By lmartine Date 2009-10-05 Time 16:54 Rev Time 0.00
Received By lmartine Date 2009-08-11 Time 16:08 Sent To  
Notes
2009-08-20 16:09:25C6
2009-08-11 11:00:56IN ZONING

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2009-08-25 Cont ID  
Sent By mcruz Date 2009-08-25 Time 12:34 Rev Time 0.00
Received By kdfreema Date 2009-08-25 Time 08:32 Sent To E
Notes
***NONE***