Plan Review Details - Permit 09080203
Plan Review Stops For Permit 09080203
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-09-17 Cont ID  
Sent By shill Date 2009-09-17 Time 17:08 Rev Time 0.00
Received By shill Date 2009-09-17 Time 17:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-08-19 Cont ID  
Sent By shill Date 2009-08-19 Time 17:10 Rev Time 0.00
Received By shill Date 2009-08-19 Time 17:10 Sent To B
Notes
2009-08-19 17:19:03***PROVISO***
  
 ***REVISION REQUIRED***
 PROVIDE WINDOW PRODUCT APPROVAL FAC9B72 (ITEM 7 ON DEMO
 PLAN), SUBMIT AS REVISION PRIOR TO INSTALLATION, REVISE
 OCCUPANT LOAD PER FBC TABLE 1004
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-08-07 Cont ID  
Sent By shill Date 2009-08-07 Time 18:10 Rev Time 0.00
Received By shill Date 2009-08-07 Time 18:10 Sent To  
Notes
2009-08-07 18:32:57***PROVISOS***
 PER OWNER, GRAB BARS TO BE INSTALLED IN ACCESSIBLE
 BATH, HANDRAILS TO BE INSTALLED AT STAIRS, ALL EXITING
 TO BE IN COMPLIANCE WITH FBC CH 10
  
  
 ***REVISION REQUIRED***
 PROVIDE WINDOW PRODUCT APPROVAL FAC9B72 (ITEM 7 ON DEMO
 PLAN), SUBMIT AS REVISION PRIOR TO INSTALLATION, REVISE
 OCCUPANT LOAD PER FBC TABLE 1004
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-10-28 Cont ID  
Sent By btrobaug Date 2009-10-28 Time 17:30 Rev Time 0.00
Received By btrobaug Date 2009-10-28 Time 17:00 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-09-16 Cont ID  
Sent By dpalmer Date 2009-09-16 Time 19:07 Rev Time 0.00
Received By dpalmer Date 2009-09-16 Time 19:07 Sent To M
Notes
2009-09-16 19:07:56** PROVISO/REDLINED PLANS**
  
 1) NOTE: PLANS CONTAIN A NEW A/C SYSTEM PER MECHANICAL
 COMMENTS WHICH WAS NOT ON EITHER OF THE TWO PREVIOUS
 REVIEWED PLANS.
 NEW ELECTRICAL PLANS DO NOT INDICATE THE REQUIRED
 ELECTRICAL TO AHU. NEEDS DISCONNECT MEETING 440.11,12,
 110.26.
  
 2) NOTE: THE OVER CURRENT PROTECTION INDICATED FOR
 EXISTING AIR HANDLER UNITS WITH 5KW HEAT IS SHOWN TOO
 HIGH. HEAT STRIPS ARE SHOWN AT 5KW> PLEASE SEE 424.3B
 AS MINIMUM OCP IS 125%, HOWEVER PLEASE SEE 422.11E3 AS
 THE MAXIMUM OCP IS 150% OR MANUFACTURES NAMEPLATE. THE
 60AMP AS SHOWN APPEARS TOO HIGH AND IS A POSSIBLE
 FIRE/LIFE SAFETY HAZARD. THIS WAS IN PREVIOUS NOTES.
 PLEASE VIF AND ADJUST BREAKERS AS NEEDED.
  
 3) NOTE: PLEASE SHOW ALL CIRCUITING ON PLANS AND
 CORRELATE WITH PANEL SCHEDULES. PLEASE SUBMIT BEFORE
 FINAL ELECTRICAL INSPECTION. ANY OTHER CHANGES ARE
 REQUIRED BEFORE ROUGH.
 AS CIRCUITING IS NOT SHOWN, PLANS ARE REDLINED FOR
 EMERGENCY AND EXIT LIGHTS TO MEET 700.12F AS TYPICAL.
 ALL MUST BE CIRCUITED TO LOCAL LIGHTING BRANCH CIRCUIT
 IN ANY ONE AREA.
  
 4) NOTED *** ONLY THE FIXTURE OUTSIDE SOUTH DOOR NEEDS
 TO BE ADDED AS BATTERY BACK UP OF SOME KIND TO MEET
 NFPA-101 7.8.1.3,7.9.1.2,.2.2.
  
 5) NOTED *** ANY REVISIONS BY OTHER TRADES SUCH AS THE
 SIZING OF THE A/C SYSTEM MAY AFFECT ELECTRICAL PLANS.
 ELECTRICAL REVIEW IS BASED ON SYSTEM SHOWN ON PLANS AT
 THIS TIME. IT IS KNOWN THERE MAY BE CODE COMMENTS WITH
 RESPECT TO THE SIZE OF THE A/C SYSTEM AS SUBMITTED AND
 SHOWN.
  
 6) NOTED *** SERVICE RISER/METER IS SHOWN AS IT EXISTS
 ON PLANS AND AT LOCATION. ONLY MOVING MAIN OUTSIDE TO
 GROUP MAINS FOR SERVICES TO MEET 230.72. ADDITIONAL
 SERVICE IS NOT GRANTED PER 230.2. HOWEVER AS IT IS
 EXISTING SIGNAGE FOR ALL SERVICES AND MAIN LOCATIONS
 SHALL BE INSTALLED AT THIS SERVICE.
 ** ALL OTHER MAINS AND SERVICES ON BUILDING SHALL BE
 LABELED PER 230.2E. VERIFY IN FIELD. ALL SERVICES
 INCLUDING HOUSE SERVICE IS THE RESPONSIBILITY OF
 BUILDING OWNER.
  
 ** AS STATED ON ALL REVIEWS PREVIOUSLY, PLEASE CALL TO
 GO OVER ANY QUESTIONS.
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-08-21 Cont ID  
Sent By dpalmer Date 2009-08-21 Time 15:32 Rev Time 0.00
Received By dpalmer Date 2009-08-21 Time 15:32 Sent To  
Notes
2009-08-21 15:32:14 
  
  
 ** DENIED 2ND REVIEW **
  
 ** SOME NOTES FROM PREVIOUS REVIEW ARE STILL IN NEED OF
 ADDRESSING. SOME NEW NOTES BASED ON REVISED PLANS NOW
 SHOWING INFORMATION NOT ON PREVIOUS PLANS.
  
 1) NOTE: PLEASE SHOW ALL CIRCUITING ON PLANS AND
 COORDINATE WITH THE NOW SUBMITTED PANEL SCHEDULES.
 PLEASE BE SURE TO SEE 700.12F FOR CIRCUITING OF EXIT
 AND EMERGENCY LIGHTS AS NOTED ON PREVIOUS REVIEW.
 408.4
 240.4,310.16 ETC SEE NOTES BELOW.
  
 2) NOTE: PANEL SCHEDULES NOW SUBMITTED ALONG WITH LOAD
 CALCULATIONS INDICATE 2-POLE 60AMP BREAKERS ON AHU*S
 HOWEVER THE HEAT LOADS ON HAU ARE SHOWN AS 5KW EACH.
 PLEASE SEE 424.3B AND 422.11E AS MINIMUM OVER CURRENT
 PROTECTION WOULD BE 125% HOWEVER MAXIMUM OCP WOULD BE
 150%/ MANUFACTURES NAMEPLATE.
 IT IS NOT POSSIBLE TO HAVE 60AMP OCP ON 5KW AIR HANDLER
 UNITS. IF THE UNITS ARE ACTUALLY 10KW, PLEASE ADJUST
 LOAD CALCULATIONS.
 220,220.56 ETC
  
 3) NOTE: PLEASE WHO NEW OR EXISTING SIGN CIRCUIT AND
 MINIMUM LOAD OF 1200 VA PER 600.5 AS NOTED ON PREVIOUS
 REVIEW. PLANS NOW CONTAIN A NOTE WHICH MENTIONS * NO
 ELECTRICAL SIGNAGE* HOWEVER THE MINIMUM REQUIRED BY THE
 NEC IS THAT A SIGN CIRCUIT BE PROVIDED EVEN IF THE
 TENANT DOES NOT INSTALL AN ELECTRICAL SIGN. PLEASE SEE
 THE FOLLOWING COMMENTARY FROM THE NEC FROM SECTION
 600.5. THIS IS PASTED DIRECTLY FROM THE NEC HANDBOOK.
  
 **ELECTRIC SIGNS AND OUTLINE LIGHTING TO ATTRACT THE
 ATTENTION OF CONSUMERS ARE USED EXTENSIVELY BY
 COMMERCIAL ENTERPRISES. THE NEED FOR AN ACCESSIBLE
 PROVISION TO FACILITATE THE CONNECTION OF AN ELECTRIC
 SIGN AT A COMMERCIAL BUILDING IS COVERED BY 600.5(A). A
 20-AMPERE OUTLET ON A CIRCUIT DEDICATED TO THE PURPOSE
 OF SUPPLYING AN ELECTRIC SIGN(S) IS REQUIRED TO BE
 INSTALLED AT THE ENTRANCE TO SINGLE-OCCUPANT COMMERCIAL
 BUILDINGS AND AT THE ENTRANCE TO EACH OCCUPANCY OF
 MULTIPLE-OCCUPANT COMMERCIAL BUILDINGS (E.G., SHOPPING
 MALLS). THIS REQUIREMENT IS NOT CONTINGENT ON WHETHER
 AN ELECTRIC SIGN WILL BE INSTALLED AT THE TIME AN
 OCCUPANT MOVES INTO A COMMERCIAL SPACE, SINCE IT IS NOT
 UNCOMMON FOR AN ELECTRIC SIGN TO BE INSTALLED AFTER THE
 SPACE IS OCCUPIED OR WHEN A NEW OCCUPANT MOVES INTO AN
 EXISTING SPACE. FOR BRANCH CIRCUIT, FEEDER AND SERVICE
 CALCULATIONS, A MINIMUM LOAD OF 1200 VA PER 20-AMPERE
 SIGN BRANCH CIRCUIT IS REQUIRED TO BE ADDED. DUE TO THE
 NATURE OF THEIR USE, ELECTRIC SIGNS ARE CONSIDERED TO
 BE CONTINUOUS LOADS, AND AS SUCH THE CONDUCTORS AND
 OVERCURRENT DEVICES SUPPLYING SIGN LOADS HAVE TO BE
 ADJUSTED IN SIZE ACCORDINGLY.
  
 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS AS PREVIOUS REVIEW NOTES PER 13-415.AB.5,
 13-415.400.B.0.4, 13-415.B, 13-415.B.1.
 NO INFORMATION SUBMITTED. PLEASE KEEP IN MIND THIS IS
 PRESCRIPTIVE ONLY. IF USING FLA COM FOR CALCULATIONS,
 PLEASE KNOW THAT ONLY THE LIGHTING NEED BE PLACED INTO
 CALCULATION UNLESS OTHER PRESCRIPTIVE ITEMS ARE BEING
 CHANGED OR INSTALLED. IE: A/C EQUIPMENT. SEE MECHANICAL
 NOTES.
 *** AS STATED ON PREVIOUS REVIEW PLEASE CALL TO GO
 OVER.
  
 5) NOTE: OCCUPANT LOAD ON ELECTRICAL PLANS STILL STATE
 60, PLEASE BE SURE TO REVISE FOR FIRE MARSHAL REVIEW
 NOTES ALONG WITH BUILDING REVIEW NOTES.
  
 6) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 LIGHTING CONTROLS IN SPACE. 13-415.AB.1.1,.1.2 AND
 .1.3.
 PLEASE SEE PLANS WHICH DO INDICATE SOME OCCUPANCY
 SENSORS HOWEVER IT IS NOT CLEAR WHAT THE SYMBOL AND
 DEVICE IS FOR * S MT*.
  
  
 7) NOTE: PLANS NOW NOTE A * OPEN/CLOSE DOOR CARD*
 HOWEVER NO INFORMATION WAS PROVIDED ON PLANS FOR
 CHAPTER 7 OF THE LIFE SAFETY CODE NFPA-101. PLEASE SEE
 SECTIONS. 7.2.1.5, 7.2.1.6.2 FOR ACCESS CONTROLS. ALL
 ACCESS CONTROLS SHALL BE UNDER SEPARATE LOW VOLTAGE
 PERMITS AND PLANS.
  
  
 8) NOTE: PLEASE SHOW LOAD CALCULATIONS PER NEC 220.
 PLEASE BE SURE ALL CONTINUOUS LOADS ARE SHOWN AT 125%.
 SEE NOTES ABOVE FOR ITEMS SUCH AS SIGN CIRCUIT, A/C
 UNITS, ETC
 SEE 220.12,220.14,220.42,220.44, 220.56 ETC.
 215.3,.230.42 FOR CONTINUOUS LOADS.
  
 9) NOTE: PLEASE SEE 210.63, 210.8B, AS NEW OR EXISTING
 GFI IS REQUIRED FOR CONDENSING UNITS OUTSIDE. IF THIS
 WAS THE ONLY ITEM PLANS WOULD HAVE BEEN REDLINED.
  
 10) NOTE: PLEASE EXPLAIN CONDUCTORS ON RISER FROM METER
 TO MAIN AND MAIN TO PANEL. SHOWS 3-3/0 AND 1-#1. THIS
 IS A SINGLE PHASE SERVICE. ONLY THE PHASE CONDUCTORS
 AND NEUTRAL IS PERMITTED BEFORE THE FIRST MEANS OF
 DISCONNECT. 250.24,250.6. AS THE NEC REQUIRES THE
 NEUTRAL (GROUNDED CONDUCTOR) TO BE BONDED AT THE FIRST
 MEANS OF DISCONNECT IF AN EQUIPMENT GROUNDING CONDUCTOR
 IS INSTALLED THEN THIS WOULD PARALLEL THE NEUTRAL AND
 CREATE OBJECTIONABLE CURRENTS.
 ONLY AFTER THE FIRST MEANS OF DISCONNECT IS THE
 EQUIPMENT GROUNDING CONDUCTOR REQUIRED. PLEASE SEE
 250.122 FOR SIZING. RISER SHOWS #1, HOWEVER SEE
 SECTION.
 ** PLEASE SEE 250.66 FOR ANY NEW GROUNDING ELECTRODE
 CONDUCTOR.
 ** PLANS DO NOT SHOW MAIN DISCONNECT OUTSIDE. SIGNAGE
 WILL BE REQUIRED PER 230.2E.
  
 ** CALLED ELECTRICAL CONTRACTOR FOR MEETING SOME TIME
 THE FOLLOWING WEEK TO GO OVER PLANS/COMMENTS.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-08-09 Cont ID  
Sent By dpalmer Date 2009-08-09 Time 09:26 Rev Time 0.00
Received By dpalmer Date 2009-08-09 Time 07:56 Sent To  
Notes
2009-08-09 09:26:48 
  
 ** DENIED REVIEW **
  
 1) NOTE: PLANS SPECIFICALLY STATE WORK TO BE DONE TO A
 2006 FLORIDA BUILDING AS WELL AS STATING THE 2007
 FLORIDA BUILDING CODE WITH 2009 SUPPLEMENTS. SEE NOTE
 #4 ON PLANS.
 AS OF MARCH 1ST, 2009 THE STATE OF FLORIDA ADOPTED THE
 2007 FBC WITH THE 2009 SUPPLEMENTS. THE PREVIOUS
 FLORIDA BUILDING CODE WAS THE 2004 EDITION. THERE HAS
 NOT BEEN A 20096 EDITION. THE PLANS ALSO STATE * THE
 LATEST EDITIONS OF OTHER CODES*. PLEASE UNDERSTAND
 THERE ARE NUMEROUS CODES WHICH ARE CURRENTLY THE LATEST
 EDITIONS HOWEVER THE STATE OF FLORIDA HAS NOT YET
 ADOPTED MANY OF THE LATEST EDITIONS.
 THE PLANS SHOULD HAVE THE FOLLOWING AT A MINIMUM UNDER
 THE DESIGN:
 2007 FBC W/2009 SUPPLEMENTS
 2006 NFPA-101
 2005 NFPA-70 ( NATIONAL ELECTRICAL CODE)
  
 PER: FS 553.73, FBC 2007 EDITION WITH 2009 REVISIONS,
 FLORIDA ADMINISTRATIVE CODE 69A-3.012, 69A-60.004.
  
 ** IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 2) NOTE: THE SUBMITTED ELECTRICAL PLANS DO NOT CONTAIN
 ANY DESIGN PROFESSIONAL SIGNED, DATED OR SEALED ON SAID
 ELECTRICAL PLANS. PLEASE SEE FS 481.229, 471.003. WHEN
 MEETING EXCEPTIONS TO THE REQUIRED DESIGN PROFESSIONAL
 AS NOTED THEN PLANS WOULD BE THEN UNDER THE EXCEPTIONS
 TO A DESIGN PROFESSIONAL PER FS 489.
 ** IF CASTILLO ELECTRIC IS THE DESIGN PROFESSIONAL
 PLEASE BE SURE THE PRINTED NAME AND SIGNATURE IS STATED
 ON PLANS.
  
 3) NOTE: PLEASE SHOW WHERE THE DECLARED LEVEL OF
 ALTERATION PER EXISTING BUILDING CODE CHAPTER 4 IS
 STATED ON PLANS. THIS IS ALSO A CHANGE IN OCCUPANCY TO
 A HIGHER LEVEL OF HAZARD FROM THE PREVIOUS USE. SEE
 TABLES IN CHAPTER 8.
  
  
 4) NOTE: PLEASE COMPLETE ELECTRICAL PLANS WITH ALL
 CIRCUITING AND COORDINATE WITH A PANEL SCHEDULE(S) TO
 BE SUBMITTED. PLEASE BE SURE TO SEE 700.12F FOR
 CIRCUITING OF EMERGENCY AND EXIT LIGHTS TO LOCAL
 LIGHTING BRANCH CIRCUIT. SIZE OF CIRCUIT, PANEL, OVER
 CURRENT PROTECTION DEVICE ETC NEEDS TO BE SHOWN.
 PLEASE ALSO INDICATE LOADS IMPOSED ON EXISTING PANELS
 AND THE RATINGS OF EXISTING EQUIPMENT.
  
 408.4, 310.16, 240.4, 220.14, 220.12, 220.42, 220.43,
 220.44. THESE ARE ONLY A FEW SECTIONS NOTED.
 FBC 106.1.1, 106.3.5.1.2 FOR CLARITY AND ADDITIONAL
 INFORMATION NOT YET ON PLANS FOR MINIMUM CODE REVIEW.
  
 5) NOTE: PLEASE INDICATE THE NEW OR EXISTING SIGN
 CIRCUIT PER 600.5. PLEASE BE SURE TO INCLUDE LOAD. (
 1200VA MINIMUM)
  
 6) NOTE: PLEASE SEE 13-415.AB.1.1, .1.2, .1.3. THIS IS
 A TENANT SPACE LOCATED IN BUILDING GREATER THAN 5K SQ
 FT. SEE DEFINITIONS OF *BUILDING*, A RATED TENANT
 SEPARATION WALL DOES NOT CREATE A SEPARATE BUILDING.
 ADJACENT TENANT SPACES ARE ALSO TENANTS LOCATED IN A
 BUILDING GREATER THAN 5K SQ FT.
 AUTOMATED LIGHTING CONTROLS ARE REQUIRED FOR NEW BEING
 INSTALLED. PLEASE ALSO BE AWARE THAT CHANGE IN
 OCCUPANCY PER 13-101.3.2 STATES TO COMPLY WITH 13-4 OF
 THE FBC.
  
 7) NOTE: PLEASE SEE 13-415.AB.1.4 FOR CONTROLS OF
 EXTERIOR LIGHTING. THIS MAY BE ONE OF TWO METHODS AS
 STATED IN SECTION.
  
 8) NOTE: PLEASE SEE FBC 13-415.AB.5, 13-415.B,
 13-415.B.1 AND SUBMIT LIGHTING PERFORMANCE CALCULATIONS
 FOR LIGHTING. PLEASE SEE 13-415.AB.2.2 FOR EXTERIOR
 LIGHTING.
 ** IMPORTANT** LIGHTING FIXTURES WOULD NEED TO BE
 SPECIFIC AT THIS TIME. STATING 2FT BY 8FT CEILING
 MOUNTED FLUORESCENT IS NOT SPECIFIC. THESE FIXTURE COLD
 CONTAIN AS LITTLE AS 4-32W BULBS WITH A MUCH LOWER VA
 RATING OR IT COULD BE MUCH HIGHER.
 PLEASE SEE SECTIONS NOTED ABOVE AS THE VA/ WATTAGE USED
 IN PERFORMANCE CALCULATIONS ARE BASED ON
 FIXTURE/BALLAST RATINGS NOT LIGHT BULB WATTAGE.
 THE EXTERIOR FIXTURES WHICH ARE ON ARCHITECTURAL PLANS
 ARE NOT ON ELECTRICAL PLANS.
  
 9) NOTE: PLEASE SEE FBC 1006.1.1, .1.2, NFPA-101
 7.8.1.3, 7.9.1.2, .2.2. AS REQUIRED EGRESS LIGHTING IS
 REQUIRED UNDER NORMAL AND EMERGENCY CONDITIONS. PLEASE
 SEE SECTIONS ABOVE SPECIFIC TO STAIR AREAS AT THE REAR
 AND SIDE OF THE BUILDING. THE LIGHTING LEVELS REQUIRED
 UNDER NORMAL CONDITIONS ARE 10 FC AND IS PERMITTED TO
 GO DOWN TO 1FC UNDER EMERGENCY CONDITIONS. PLANS DO NOT
 SHOW ANY LIGHTING AT THESE LOCATIONS FOR NORMAL OR
 EMERGENCY ILLUMINATION.
 SEE POSSIBLE COMMENTS FROM FIRE MARSHAL REVIEW.
  
 10) NOTE: ARCHITECTURAL PLANS INDICATE AN ELECTRICAL
 PANEL LOCATED IN *OFFICE #1* HOWEVER ELECTRICAL PLANS
 DO NOT INDICATE ANY PANEL?
 PLEASE SHOW LOCATIONS OF ALL SERVICE EQUIPMENT AND
 PANELS.
 110.26, 240.24, ETC.
  
 11) NOTE: IN LONGUE AREA RECEPTACLE LOCATED AT THE SIDE
 OF SINK WOULD HAVE AN OCCUPANT CROSSING OVER THE NEW
 SINK TO PLUG IN ANY APPLIANCES LEAVING CORD IN SINK
 AREA. THIS IS NOT A SAFE LOCATION FOR RECEPTACLE
 SERVING THE COUNTER SPACE AS SHOWN.
 PLEASE SEE 210.8B.
 PLEASE ALSO INDICATE IF THE EXISTING DEVICES LOCATED IN
 BATH ROOMS ARE GFCI PROTECTED. IF THESE ARE NOT PER THE
 CHANGE IN OCCUPANCY IN THE EBC, ALL ELECTRICAL SHALL BE
 MADE SAFE TO CURRENT CODE REQUIREMENTS.
  
 ** PLEASE KNOW THAT PLANS ARE NO LONGER RELEASED BACK
 TO CONTRACTOR PER NEW DIRECTOR.
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-09-17 Cont ID  
Sent By mawillia Date 2009-09-17 Time 15:11 Rev Time 0.00
Received By mawillia Date 2009-09-17 Time 14:54 Sent To  
Notes
2009-09-17 15:01:29*****PROVISO*****
  
 AS PREVIOUSLY DONE ON 8/25/2009, PLAN SHEETS A-2 AND
 E-1 WERE STAMPED, INITIALED, AND DATED. INCLUDED ON
 SHEET A-2 IS THE FOLLOWING PROVISO:
  
 PROVISO: PER WEST PALM BEACH FIRE PREVENTION BUREAU,
 THE OCCUPANT LOAD SHALL NOT EXCEED 60 PERSONS. IF THE
 OCCUPANT LOAD EVER EXCEEDS 100 PERSONS, AS PER 12.3.5.1
 OF NFPA 101, THE ASSEMBLY OCCUPANCY SHALL BE PROTECTED
 THROUGHOUT BY AN APPROVED SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-08-25 Cont ID  
Sent By mawillia Date 2009-08-25 Time 11:19 Rev Time 0.00
Received By mawillia Date 2009-08-25 Time 10:26 Sent To  
Notes
2009-08-25 10:45:48*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEETS A-2 AND E-1 WERE STAMPED,
 INITIALED, AND DATED. INCLUDED ON SHEET A-2 IS THE
 FOLLOWING PROVISO:
  
 PROVISO: PER WEST PALM BEACH FIRE PREVENTION BUREAU,
 THE OCCUPANT LOAD SHALL NOT EXCEED 60 PERSONS. IF THE
 OCCUPANT LOAD EVER EXCEEDS 100 PERSONS, AS PER 12.3.5.1
 OF NFPA 101, THE ASSEMBLY OCCUPANCY SHALL BE PROTECTED
 THROUGHOUT BY AN APPROVED SUPERVISED AUTOMATIC
 SPRINKLER SYSTEM.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-08-13 Cont ID  
Sent By mawillia Date 2009-08-13 Time 14:21 Rev Time 0.00
Received By mawillia Date 2009-08-12 Time 13:12 Sent To B1
Notes
2009-08-12 14:40:35*****DENIED*****
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. NFPA 101, LIFE SAFETY CODE, 2006 EDITION SHALL BE
 REFERENCED.
  
 3. ON SHEET A-1, IT IS STATED THAT THE OCCUPANCY SPACE
 IS AN EXISTING ASSEMBLY; BE ADVISED THAT SINCE THIS A
 CHANGE OF OCCUPANCY FROM THAT OF MERCANTILE, THIS
 TENANT SPACE SHALL BE A NEW ASSEMBLY AS PER NFPA 101.
  
 4. PLEASE EXPLAIN THE OCCUPANT LOAD FACTOR OF 50 GROSS
 USED TO DERIVE AN OCCUPANT LOAD OF 60 PERSONS. BE
 ADVISED, AS PER 12.3.5.1 OF NFPA 101, WHERE THE
 OCCUPANT LOAD EXCEEDS 100, THE ASSEMBLY OCCUPANCY SHALL
 BE PROTECTED THROUGHOUT BY AN APPROVED SUPEWRVISED
 AUTOMATIC SPRINKLER SYSTEM.
  
 5. PROVIDE OCCUPANT LOAD FOR THE WAITING AREA.
  
 6. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE NEW
 WALL IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICIATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-10-28 Cont ID  
Sent By jwitmer Date 2009-10-28 Time 14:00 Rev Time 0.00
Received By jwitmer Date 2009-10-28 Time 14:00 Sent To  
Notes
2009-10-28 14:01:20INCOMING, REVISION: ELEC TO D. PALMER

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-09-14 Cont ID  
Sent By lmartine Date 2009-09-14 Time 16:14 Rev Time 0.00
Received By lmartine Date 2009-09-14 Time 16:13 Sent To  
Notes
2009-09-14 16:18:33**********EXPEDITED*************GAVE TO DEWEY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-08-21 Cont ID  
Sent By dpalmer Date 2009-08-21 Time 14:45 Rev Time 0.00
Received By dpalmer Date 2009-08-21 Time 14:45 Sent To  
Notes
2009-08-21 14:45:44TO B-24

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-09-14 Cont ID  
Sent By shill Date 2009-08-13 Time 17:33 Rev Time 0.00
Received By lmartine Date 2009-08-07 Time 16:19 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2009-08-19 Cont ID  
Sent By shill Date 2009-08-19 Time 17:33 Rev Time 0.00
Received By shill Date 2009-08-19 Time 17:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-09-17 Cont ID  
Sent By rregueir Date 2009-09-17 Time 13:34 Rev Time 0.00
Received By rregueir Date 2009-09-17 Time 13:33 Sent To B
Notes
2009-09-17 13:34:44PROVIDE FIELD INSPECTIOR WITH TEST AND BALANCE REPORT
 TO VERIFY THAT REQUIRED VENTILATION RATES ARE PROVIDED
 PER FBC-M 403.3.1.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-08-25 Cont ID  
Sent By rregueir Date 2009-08-25 Time 18:09 Rev Time 0.00
Received By rregueir Date 2009-08-25 Time 17:28 Sent To  
Notes
2009-08-25 18:09:55REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. WHERE THE OCCUPANCY OF AN EXISTING BUILDING OR PART
 OF AN EXISTING BUILDING IS CHANGED SUCH THAT THE NEW
 OCCUPANCY IS SUBJECT TO INCREASED MECHANICAL
 VENTILATION REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, MECHANICAL , THE INTENT OF THE
 RESPECTIVE FLORIDA BUILDING CODE, MECHANICAL PROVISIONS
 SHALL BE COMPLIED WITH FOR THE NEW OCCUPANCY IN
 ACCORDANCE WITH FBC-EB 909.1. NO INFORMATION WAS
 PROVIDED REGARDING THE EXISTING AIR CONDITIONING SYSTEM
 OR THE VENTILATION RATES WHICH ARE BEING PROVIDED.
 DEMONSTRATE COMPLIANCE WITH THE REQUIREMENTS OF FBC-M
 403.3 OR 403.4 FOR THE NEW OCCUPANCY.
  
 NOTE: A TEST AND BALANCE REPORT WILL BE REQUIRED AT
 TIME OF INSPECTION (PRIOR TO C.O.) TO VERIFY
 VENTILATION RATES IN ACCORDANCE WITH FBC-M 403.3.4.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2009-08-13 Cont ID  
Sent By mcruz Date 2009-08-13 Time 16:25 Rev Time 0.00
Received By mcruz Date 2009-08-13 Time 16:24 Sent To B
Notes
2009-08-13 16:25:06*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  