Plan Review Details - Permit 09080201
Plan Review Stops For Permit 09080201
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-09-16 Cont ID  
Sent By lmartine Date 2009-09-16 Time 11:27 Rev Time 0.00
Received By lmartine Date 2009-09-16 Time 11:27 Sent To  
Notes
2009-09-16 11:34:18PROVIDE SUBMITTAL FOR BLOCK INFILL ON SHEET E-1.
 CORRECT DESIGN WIND SPEED ON SHEET S1.1.
  
  
  
  
 L.MARTINEZ
 561-805-6710

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-10-14 Cont ID  
Sent By btrobaug Date 2009-10-14 Time 12:08 Rev Time 0.00
Received By btrobaug Date 2009-10-14 Time 10:55 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-08-24 Cont ID  
Sent By btrobaug Date 2009-08-24 Time 14:59 Rev Time 0.00
Received By btrobaug Date 2009-08-24 Time 14:25 Sent To  
Notes
2009-08-24 14:59:07 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 702.8 A SIGN SHALL BE PLACED AT THE SERVICE-ENTRANCE
 EQUIPMENT THAT INDICATES THE TYPE AND LOCATION OF
 ON-SITE OPTIONAL STANDBY POWER SOURCES.
  
 2} PROVIDE A LOAD CALCULATION FOR THE LOAD INTENDED TO
 BE SERVED. 215.5. 702.5, 2005NEC
  
 3} PROVIDE SPECIFICATIONS FOR THE TRANSFER SWITCH AND
 GENERATOR INTENDED TO BE INSTALLED, THE FAXED COPIES
 ARE GENERIC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2009-10-06 Cont ID  
Sent By mgonzale Date 2009-10-06 Time 08:22 Rev Time 1.50
Received By mgonzale Date 2009-10-06 Time 08:22 Sent To  
Notes
2009-10-06 08:26:31PASSED WITH PROVISO:
  
 #1 PRIVATE STORM MANHOLE IN THE VICINITY OF THE
 GENERATOR PAD MUST BE ACCESSIBLE
 #2 IF DECISION IS MADE TO RELOCATED YOU NEED PLUMBING
 PERMIT WITH CONSTRUCTION SERVICE
 #3 NO WORK IS ALLOWED IN THE ALLEYWAY
 #4 BLOCKING OF THE ALLEYWAY REQUIRES A ROW PERMIT
 PLEASE FIND LINK BELOW TO ACQUIRE A ROW PERMIT TO
 FACILITATE WORKING VEHICLES IN THE ALLEYWAY.
 HTTP://WWW.CITYOFWPB.COM/ENGINEERING/ENG_FORMS.PHP
  
 MANNY GONZALEZ
 CS ENGINEERING REVIEW
 401 CLEMATIS STREET, 1TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-10-05 Cont ID  
Sent By mcarsill Date 2009-10-05 Time 12:34 Rev Time 0.00
Received By mcarsill Date 2009-10-05 Time 12:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-08-28 Cont ID  
Sent By mcarsill Date 2009-08-28 Time 08:18 Rev Time 0.00
Received By mcarsill Date 2009-08-28 Time 08:13 Sent To  
Notes
2009-08-28 08:17:11307 EVERNIA STREET # 100
 PERMIT NUMBER 09080201
  
 1. GAS INSTALLATION TO COMPLY WITH NFPA STANDARDS FOR
 NATURAL GAS INSTALLATIONS. GAS SYSTEMS AND
 APPURTENANCES SHALL BE INSTALLED IN A SAFE AND
 WORKMANLIKE MANNER.
  
 2. WHAT EQUIPMENT DOES THE EMERGENCY GENERATOR SUPPLY
 POWER TO.
  
 3. NO SURVEY PROVIDED WITH DRAWINGS.
  
 4. PLEASE PROVIDE CUT-SHEETS ON SPECIFIC EMERGENCY
 GENERATOR AND TRANSFER SWITCH.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2009-10-06 Cont ID  
Sent By kstevens Date 2009-10-06 Time 14:00 Rev Time 0.00
Received By kstevens Date 2009-10-06 Time 14:00 Sent To  
Notes
2009-10-06 14:01:18ENGINEER SIGNED & SEALED PLANS AT FIRE STATION #1.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2009-09-30 Cont ID  
Sent By kstevens Date 2009-09-30 Time 11:22 Rev Time 0.00
Received By kstevens Date 2009-09-30 Time 11:22 Sent To  
Notes
2009-09-30 11:26:50DENIED
 FBC-2007 CHAPTER 1
 FLORIDA STATUTES
  
 1. SHT P-1 IF THE DESIGN PROFESSIONAL IS AN ENGINEER
 LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE
 REGULATING THE PRACTICE OF ENGINEERING AS PROVIDED FOR
 IN CHAPTER 471, FLORIDA STATUTES, THE HE OR SHE SHALL
 AFFIX HIS OR HER OFFICIAL SEAL, SIGNATURE AND DATE TO
 THE SAID DRAWINGS. SECTION 106.1. THE SHEETS SUBMITTED
 HAVE NOT BEEN SIGNED, SEALED OR DATED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2009-08-24 Cont ID  
Sent By kstevens Date 2009-08-24 Time 15:52 Rev Time 0.00
Received By kstevens Date 2009-08-24 Time 15:52 Sent To  
Notes
2009-08-24 15:53:49PASSED/PROVISO:
  
 MANUF. SPECIFICATIONS SHOWING BTU LOAD REQUIRED AT TIME
 OF GAS ROUGH.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-30 Cont ID  
Sent By jgomez Date 2009-09-30 Time 09:07 Rev Time 0.00
Received By jgomez Date 2009-09-30 Time 09:07 Sent To  
Notes
2009-09-30 09:07:51SENT TO COMMERCIAL BOX #35.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-09-16 Cont ID  
Sent By lmartine Date 2009-09-16 Time 11:27 Rev Time 0.00
Received By lmartine Date 2009-08-07 Time 14:59 Sent To  
Notes
2009-08-24 15:01:03TO C-2

Review Stop Z ZONING
Rev No 2 Status P Date 2009-10-07 Cont ID  
Sent By aaponte Date 2009-10-07 Time 12:40 Rev Time 0.00
Received By aaponte Date 2009-10-07 Time 12:40 Sent To  
Notes
2009-10-07 12:41:14PROVISO: CHAIN LINK AND WOOD GATE SHALL NOT EXCEED 6
 FEET IN MAXIMUM HEIGHT.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-08-14 Cont ID  
Sent By aaponte Date 2009-08-14 Time 14:40 Rev Time 0.00
Received By aaponte Date 2009-08-14 Time 14:40 Sent To  
Notes
2009-08-14 14:42:57SCREENING SHALL BE PROVIDED AROUND THE ENTIRE
 DUMPSTER/GENERATOR ENCLOSURE (OBSCURING GATES). CHAIN
 LINK DOES NOT PROVIDE THE SCREENING REQUIRED.