| Plan Review Stops For Permit 09080201 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2009-09-16 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2009-09-16 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2009-09-16 |
Time |
11:27 |
Sent To |
|
|
| Notes |
| 2009-09-16 11:34:18 | PROVIDE SUBMITTAL FOR BLOCK INFILL ON SHEET E-1. | | | CORRECT DESIGN WIND SPEED ON SHEET S1.1. | | | | | | | | | | | | | | | L.MARTINEZ | | | 561-805-6710 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2009-10-14 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-10-14 |
Time |
12:08 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-10-14 |
Time |
10:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-08-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-08-24 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-08-24 |
Time |
14:25 |
Sent To |
|
|
| Notes |
| 2009-08-24 14:59:07 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005 | | | NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} 702.8 A SIGN SHALL BE PLACED AT THE SERVICE-ENTRANCE | | | EQUIPMENT THAT INDICATES THE TYPE AND LOCATION OF | | | ON-SITE OPTIONAL STANDBY POWER SOURCES. | | | | | | 2} PROVIDE A LOAD CALCULATION FOR THE LOAD INTENDED TO | | | BE SERVED. 215.5. 702.5, 2005NEC | | | | | | 3} PROVIDE SPECIFICATIONS FOR THE TRANSFER SWITCH AND | | | GENERATOR INTENDED TO BE INSTALLED, THE FAXED COPIES | | | ARE GENERIC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2009-10-06 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2009-10-06 |
Time |
08:22 |
Rev Time |
1.50 |
| Received By |
mgonzale |
Date |
2009-10-06 |
Time |
08:22 |
Sent To |
|
|
| Notes |
| 2009-10-06 08:26:31 | PASSED WITH PROVISO: | | | | | | #1 PRIVATE STORM MANHOLE IN THE VICINITY OF THE | | | GENERATOR PAD MUST BE ACCESSIBLE | | | #2 IF DECISION IS MADE TO RELOCATED YOU NEED PLUMBING | | | PERMIT WITH CONSTRUCTION SERVICE | | | #3 NO WORK IS ALLOWED IN THE ALLEYWAY | | | #4 BLOCKING OF THE ALLEYWAY REQUIRES A ROW PERMIT | | | PLEASE FIND LINK BELOW TO ACQUIRE A ROW PERMIT TO | | | FACILITATE WORKING VEHICLES IN THE ALLEYWAY. | | | HTTP://WWW.CITYOFWPB.COM/ENGINEERING/ENG_FORMS.PHP | | | | | | MANNY GONZALEZ | | | CS ENGINEERING REVIEW | | | 401 CLEMATIS STREET, 1TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 644-7301 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2009-10-05 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2009-10-05 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2009-10-05 |
Time |
12:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2009-08-28 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2009-08-28 |
Time |
08:18 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2009-08-28 |
Time |
08:13 |
Sent To |
|
|
| Notes |
| 2009-08-28 08:17:11 | 307 EVERNIA STREET # 100 | | | PERMIT NUMBER 09080201 | | | | | | 1. GAS INSTALLATION TO COMPLY WITH NFPA STANDARDS FOR | | | NATURAL GAS INSTALLATIONS. GAS SYSTEMS AND | | | APPURTENANCES SHALL BE INSTALLED IN A SAFE AND | | | WORKMANLIKE MANNER. | | | | | | 2. WHAT EQUIPMENT DOES THE EMERGENCY GENERATOR SUPPLY | | | POWER TO. | | | | | | 3. NO SURVEY PROVIDED WITH DRAWINGS. | | | | | | 4. PLEASE PROVIDE CUT-SHEETS ON SPECIFIC EMERGENCY | | | GENERATOR AND TRANSFER SWITCH. | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | 804-4709 PHONE | | | 804-4774 FAX | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2009-10-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-10-06 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-10-06 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2009-10-06 14:01:18 | ENGINEER SIGNED & SEALED PLANS AT FIRE STATION #1. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2009-09-30 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-09-30 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-09-30 |
Time |
11:22 |
Sent To |
|
|
| Notes |
| 2009-09-30 11:26:50 | DENIED | | | FBC-2007 CHAPTER 1 | | | FLORIDA STATUTES | | | | | | 1. SHT P-1 IF THE DESIGN PROFESSIONAL IS AN ENGINEER | | | LEGALLY REGISTERED UNDER THE LAWS OF THIS STATE | | | REGULATING THE PRACTICE OF ENGINEERING AS PROVIDED FOR | | | IN CHAPTER 471, FLORIDA STATUTES, THE HE OR SHE SHALL | | | AFFIX HIS OR HER OFFICIAL SEAL, SIGNATURE AND DATE TO | | | THE SAID DRAWINGS. SECTION 106.1. THE SHEETS SUBMITTED | | | HAVE NOT BEEN SIGNED, SEALED OR DATED. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2009-08-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-08-24 |
Time |
15:52 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-08-24 |
Time |
15:52 |
Sent To |
|
|
| Notes |
| 2009-08-24 15:53:49 | PASSED/PROVISO: | | | | | | MANUF. SPECIFICATIONS SHOWING BTU LOAD REQUIRED AT TIME | | | OF GAS ROUGH. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-09-30 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-09-30 |
Time |
09:07 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-09-30 |
Time |
09:07 |
Sent To |
|
|
| Notes |
| 2009-09-30 09:07:51 | SENT TO COMMERCIAL BOX #35. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2009-09-16 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2009-09-16 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2009-08-07 |
Time |
14:59 |
Sent To |
|
|
| Notes |
| 2009-08-24 15:01:03 | TO C-2 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2009-10-07 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2009-10-07 |
Time |
12:40 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2009-10-07 |
Time |
12:40 |
Sent To |
|
|
| Notes |
| 2009-10-07 12:41:14 | PROVISO: CHAIN LINK AND WOOD GATE SHALL NOT EXCEED 6 | | | FEET IN MAXIMUM HEIGHT. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2009-08-14 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2009-08-14 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2009-08-14 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2009-08-14 14:42:57 | SCREENING SHALL BE PROVIDED AROUND THE ENTIRE | | | DUMPSTER/GENERATOR ENCLOSURE (OBSCURING GATES). CHAIN | | | LINK DOES NOT PROVIDE THE SCREENING REQUIRED. |
|
|