Plan Review Details - Permit 09080087
Plan Review Stops For Permit 09080087
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-08-06 Cont ID  
Sent By shill Date 2009-08-06 Time 10:53 Rev Time 0.00
Received By shill Date 2009-08-06 Time 10:53 Sent To  
Notes
2009-08-06 10:57:54****PROVISO****
 ****REVISION REQUIRED****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 CONTRACTOR TO SUBMIT A REVISED INSTALLATION SCHEDULE
 (REVISION) OR PROVIDE SIGNED, SEALED ORIGINAL
 ENGINEERING TO JUSTIFY PROPOSED DESIGN PRESSURES
  
 FBC1003.6, MEANS OF EGRESS CONTINUITY, CANNOT BLOCK
 MAIN ENTRANCE WITH PANELS. (OPENINGS 4 & 5 HAVE BEEN
 REMOVED)
  
 THE INSTALLATION SCHEDULE SUBMITTED WAS BASED ON DESIGN
 PRESSURE OF -33PSF. DESIGN PRESSURES RUN BY COMPOUTER
 PROGRAM RANGED FROM -29.4 TO -33.6.
  
 THE DESIGN PRESSURES GENERATED BY THE COMPUTER SOFTWARE
 YOU ARE USING DO NOT COMPLY WITH FBC R301, FBC1609,
 FAC61G15. ENGINEERING SOFTWARE IS TO INCLUDE THE
 COMPANY NAME AND VERSION NUMBER. THE DESIGN PRESSURES
 GENERATED ARE TOO LOW, SEE ASCE7-05.
  
 REVISION MUST BE REVIEWED PRIOR TO FIRST INSPECTION
  
 ISSUED AT CONTRACTOR'S RISK
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-08-07 Cont ID  
Sent By shill Date 2009-08-07 Time 10:07 Rev Time 0.00
Received By shill Date 2009-08-06 Time 08:54 Sent To  
Notes
2009-08-06 08:54:48UNDER $5000