Plan Review Details - Permit 09070801
Plan Review Stops For Permit 09070801
Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-11-04 Cont ID  
Sent By btrobaug Date 2009-11-04 Time 12:58 Rev Time 0.00
Received By btrobaug Date 2009-10-29 Time 14:54 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-10-07 Cont ID  
Sent By jleahy Date 2009-10-07 Time 16:34 Rev Time 0.00
Received By jleahy Date 2009-10-07 Time 16:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-08-27 Cont ID  
Sent By btrobaug Date 2009-08-27 Time 11:59 Rev Time 0.00
Received By btrobaug Date 2009-08-27 Time 11:48 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-08-05 Cont ID  
Sent By btrobaug Date 2009-08-05 Time 09:47 Rev Time 0.00
Received By btrobaug Date 2009-08-05 Time 09:10 Sent To I
Notes
2009-08-05 09:47:14 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET, UNLESS OTHERWISE NOTED.
 ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} THE RISER DIAGRAM SUBMITTED IS NOT CLEAR ENOUGH TO
 REVIEW. TWO ARE SUBMITTED ON OPPOSITE SIDES AND THE
 SAME PLAN, WHICH IS TO BE USED.
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 3} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN
 IS NEW OR EXISTING. IF NEW PROVIDE AN AIC RATING, AND
 LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, METER
 ENCLOSURE, DISCONNECTS AND PANELS, SO THAT COMPLIANCE
 WITH ARTICLES 225 AND 230 CAN BE REVIEWED. PROVIDE A
 RISER DIAGRAM WITH CONDUCTOR AND CONDUIT SIZE AND
 TYPE.
  
 4} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.2
 RESIDENTIAL FLORIDA BUILDING CODE.
  
 5} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN.
 ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER
 440.14, RECEPTACLE PER 210.63, LIGHT PER 210.70(A) (3)
 IF APPLICABLE.
  
 6} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE
 PLANS FOR RECORD RETENTION.106.1.3.FBC AS AMENDED.
  
 7} 106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION DOCUMENTS,
 SPECIAL INSPECTION AND STRUCTURAL OBSERVATION PROGRAMS,
 AND OTHER DATA SHALL BE SUBMITTED IN TWO OR MORE SETS
 WITH EACH APPLICATION FOR A PERMIT.
  
 8} LABEL ALL ROOMS FOR CLARITY, RECORD RETENTION AND SO
 OUTLET REQUIREMENTS OF 210.52 CAN BE REVIEWED.
  
 9} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT THE PLANS
 MUST BE DRAWN IN INK OR ON A CAD MACHINE TO PREVENT
 THEM FROM BEING ALTERED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-09-29 Cont ID  
Sent By shill Date 2009-09-29 Time 10:39 Rev Time 0.00
Received By shill Date 2009-09-29 Time 10:39 Sent To  
Notes
2009-09-29 10:39:58REVISION TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-08-25 Cont ID  
Sent By lmartine Date 2009-08-25 Time 15:52 Rev Time 0.00
Received By lmartine Date 2009-08-25 Time 15:52 Sent To  
Notes
2009-08-25 15:53:22GAVE TO BILL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-08-05 Cont ID  
Sent By btrobaug Date 2009-08-05 Time 09:47 Rev Time 0.00
Received By btrobaug Date 2009-08-05 Time 09:10 Sent To PC
Notes
***NONE***