| Plan Review Stops For Permit 09070792 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2009-08-10 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-08-10 |
Time |
10:25 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-08-10 |
Time |
10:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-08-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-08-05 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-08-05 |
Time |
09:47 |
Sent To |
PC |
|
| Notes |
| 2009-08-05 09:53:55 | RE-ROOF BUILDING REVIEW CHECKLIST. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- NOA 04-0723.01 SUBMITTED EXPIRED ON 04/16/09. NEED | | | TO PROVIDE CURRENT NOA. | | | | | | 2- CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO | | | BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN | | | PRESSURES OF SEC. 1609 FBC 2007. | | | | | | 3- CLEARLY IDENTIFY WHICH FASTENING OPTION IS GOING TO | | | BE USED. | | | | | | 4- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | | LIMITATION #7. | | | NOTE: IF SELECTED ASSEMBLY IS LIMITED BY GENERAL | | | LIMITATION #9, THEN IT MAY NOT BE USED IN THIS PROJECT. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
|