Plan Review Details - Permit 09070785
Plan Review Stops For Permit 09070785
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-08-14 Cont ID  
Sent By shill Date 2009-08-14 Time 17:52 Rev Time 0.00
Received By shill Date 2009-08-14 Time 17:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-08-21 Cont ID  
Sent By dpalmer Date 2009-08-21 Time 10:54 Rev Time 0.00
Received By dpalmer Date 2009-08-21 Time 10:54 Sent To  
Notes
2009-08-21 10:54:21*** REDLINED/ PROVISO ***
  
 THE FOLLOWING ITEMS NEED TO BE REVISED, SUBMITTED,
 REVIEW AND ON SITE BEFORE FINAL INSPECTION.
  
 ** ALL OTHER REVISIONS TO SCOPE OF WORK SHOWN SHALL BE
 SUBMITTED BEFORE ROUGH ELECTRICAL INSPECTIONS.
  
  
 1) NOTE: PANEL SCHEDULES FOR ALL PANELS IN THIS TENANT
 SPACE SHALL BE UPDATED FOR EXISTING AS WELL AS NEW. ALL
 LOCATIONS, ROOMS AND AREAS SHALL BE SPECIFIC. THE USE
 OF * RECEPTACLES/LIGHTING IS NOT PERMITTED. PLEASE SEE
 408.4 COMMENTARY UNDER THE 2005 NEC>
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-08-18 Cont ID  
Sent By dpalmer Date 2009-08-18 Time 18:12 Rev Time 0.00
Received By dpalmer Date 2009-08-18 Time 18:12 Sent To  
Notes
2009-08-18 18:13:34 
 ** DENIED REVIEW **
  
 1) NOTE: THE FOLLOWING CODES ARE NOT STATED ON
 ELECTRICAL PLANS FOR EDITIONS CURRENTLY ADOPTED AND
 UNDER PERMIT APPLICATION DATE.
  
 2007 FBC W/ 2009 REVISIONS
 2006 NFPA-101
 2005 NFPA-70
 2002 NFPA-72
  
 2) NOTE: PLEASE UPDATE CIRCUITS TO ROOMS AND AREAS IN
 WHICH THEY FEED FOR NEW AS NOTED ON PLANS. THIS MAY BE
 DONE BY ALPHA OR NUMERIC DESIGNATIONS.
 THE USE OF *RECEPTACLES* OR LIGHTING* IS NOT ACCEPTABLE
 FOR NEW.
 ** PLEASE KNOW THAT THIS ITEM ALONE BEING BASED ON A
 REMODEL COULD BE DONE AS A PROVISO HOWEVER PLANS ARE
 NEEDING CORRECTIONS FOR OTHER ITEMS.
 ALL OTHER CIRCUITING IN PANELS SPECIFIC TO THIS
 FLOOR/WORK LOCATION WILL BE REQUIRED TO HAVE PANEL
 SCHEDULES UPDATED TO SPECIFIC AREAS AND ROOMS BEFORE
 FINAL INSPECTIONS. RECORD SETS OF PLANS WILL ALSO NEED
 TO BE ACCURATE FOR THIS RECORD.
 408.4. THE FOLLOWING IS TAKEN DIRECTLY FROM THE UPDATED
 2005 NEC HANDBOOK COMMENTARY.
  
 SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANELBOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS SECTION.
  
 2) NOTE: PLEASE REVISE AND CORRECT THE FOLLOWING ITEMS
 ON RISER DIAGRAM SUBMITTED. THERE WILL BE SEVERAL
 EXAMPLES GIVEN BELOW.
  
 A) MAIN SHOWN ON RISER WHICH FEEDS THE 1600AMP MSB IS
 SHOWN AS 200AMPS? IF THIS WAS A MISPRINT FOR 2000AMPS,
 THEN THE OCP SHOWN WOULD BE TOO HIGH FOR 1600AMP MSB.
 310.16,240.4B 230.70 ,,,
  
 B) PLEASE COORDINATE RISER AND SCHEDULES. THE RISER
 INDICATES A *DFL* PANEL HOWEVER NO *DFL* SCHEDULE WAS
 SUBMITTED OR SHOWN ON SHEET.
  
 C) PLEASE SEE THE RISER WHICH INDICATES A PANEL *4L*
 FED FROM *DFL* YET THERE IS A *DPL* SCHEDULE FEEDING A
 *L4* PANEL? THIS SAME *DPL* PANEL IS SHOWN FEEDING 2L,
 3L, ETC.
  
 D) THE RISER INDICATES A PANEL *4L* WHICH IS SHOWN
 FEEDING THE TRANSFORMER AND THEN ON TO FEED PANEL *TA*.
 HOWEVER NO PANEL SCHEDULE WAS SUBMITTED FOR ANY *4L* OR
 *L4*??
 THERE IS A PANEL *L* SCHEDULE HOWEVER THIS DOES NOT
 INCLUDE ANY FEEDS TO TRANSFORMER AND IT IS SHOWN AS
 ANOTHER PANEL ON RISER.??
  
 E) COMPLIANCE FOR THE OVER CURRENT PROTECTION TO
 TRANSFORMER CAN NOT BE VERIFIED. COMPLIANCE FOR
 FEEDERS, EQUIPMENT GROUNDING, TAPPED CONDUCTORS ETC
 ALSO CAN NOT BE VERIFIED AS NO INFORMATION IS SHOWN ON
 RISER OR ON ANY PANEL SCHEDULES FOR THIS PARTICULAR
 EQUIPMENT/SPACE.
 PLEASE BE SURE TO SEE 450.3 FOR MAXIMUM OCP. PLEASE SEE
 310.16, 408.36 AND 240.21 FOR TAPPED CONDUCTORS ON THE
 LOAD SIDE OF TRANSFORMER.
 PLEASE SEE 250.20,250.30,250.66 ETC FOR THE EQUIPMENT
 GROUNDING AND GROUNDING ELECTRODE OF TRANSFORMER. THIS
 ALL MAY BE EXISTING HOWEVER INFORMATION IS NOT SHOWN.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2009-08-18 Time   Rev Time 0.00
Received By mcarsill Date 2009-08-13 Time 14:41 Sent To  
Notes
2009-08-21 10:35:04*****FIRE-STAMPED*****
  
 BASED UPON FIRE MARSHAL CARSILLO'S REVIEW/APPROVAL OF
 THE PLANS ON 8/13/2009, SHEETS LS1-0, A-1.0, A-4,
 FS0.1, FS2.1, E2.1, FA0.1, AND FA2.1 WERE STAMPED,
 INITIALED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
2009-08-13 14:46:3509070785
 1601 BELVEDERE ROAD, EAST TOWER, 4TH FLOOR, 400
 "TENANT IMPROVEMENT; RENOVATION OF EXISTING OFFICE
 SPACE, NEW CEILING, SOME WALLS, ELECTRICAL AND
 PLUMBING"
  
 1. CONSTRUCTION, DEMOLITION AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. ALL NEW FIRE DAMPERS SHALL BE DROP TESTED AFTER
 INSTALLATION TO ENSURE PROPER OPERATION.
  
 3. PLEASE EXPLAIN DOOR 100 LOCATED IN NEW ONE HOUR
 WALL. PLANS INDICATE EXISTING DOORS BUT ARE ABSENT OF A
 FIRE PROTECTION RATING. DOOR 100 IS CURRENTLY SHOWN IN
 A ONE HOUR WALL.
  
 APPROVED PROVISO;
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-12-02 Cont ID  
Sent By lmartine Date 2009-12-02 Time 14:15 Rev Time 0.00
Received By lmartine Date 2009-12-02 Time 14:15 Sent To  
Notes
2009-12-02 14:18:41GAVE TO RON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-08-20 Cont ID  
Sent By lmartine Date 2009-08-20 Time 17:01 Rev Time 0.00
Received By lmartine Date 2009-08-20 Time 17:01 Sent To  
Notes
2009-08-20 17:02:15GAVE TO DEWEY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-08-18 Cont ID  
Sent By dpalmer Date 2009-08-18 Time 18:12 Rev Time 0.00
Received By dpalmer Date 2009-08-18 Time 18:11 Sent To  
Notes
2009-08-04 09:46:26TO C14

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2009-08-18 Cont ID  
Sent By dpalmer Date 2009-08-18 Time 18:12 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-08-06 Cont ID  
Sent By rregueir Date 2009-08-06 Time 14:00 Rev Time 0.00
Received By rregueir Date 2009-08-06 Time 13:22 Sent To  
Notes
2009-08-06 14:00:41PASSED WITH THE FOLLOWING CONDITIONS:
 1. NEED ENGINEERED INSTALLATION DETAIL FOR WALL MOUNTED
 CONDENSER PER FBC-M 301.12.
  
 2. FIRE DAMPER INSTALLATION INSTRUCTIONS TO BE ON SITE
 AT TIME OF INSPECTION PER FBC-M 607.2 AND FBC-M 304.1.
  
 3. ANY CONFLICTSS BETWEEN FIRE DAMPER MANUFACTURER'S
 INSTRUCTIONS AND DETAILS ON PLANS, MANUFACTURER'S
 INSTRUCTIONS SHALL GOVERN.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-08-14 Cont ID  
Sent By kstevens Date 2009-08-14 Time 18:23 Rev Time 0.00
Received By kstevens Date 2009-08-14 Time 18:23 Sent To  
Notes
2009-08-14 18:24:16PASSED/PROVISO:
 WATER HAMMER ARRESTORS SHALL BE INSTALLED NEAR THE
 FIXTURES, NOT IN THE CEILING.

Review Stop Z ZONING
Rev No 1 Status N Date 2009-08-11 Cont ID  
Sent By eschneid Date 2009-08-11 Time 18:33 Rev Time 0.15
Received By eschneid Date 2009-08-11 Time 18:33 Sent To  
Notes
2009-08-11 18:34:15PERMIT VALUE LESS THAN 50% OF BUILDING.