| Plan Review Stops For Permit 09070777 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2009-09-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-09-21 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2009-09-21 |
Time |
13:00 |
Sent To |
|
|
| Notes |
| 2009-09-21 13:41:24 | NEW A-1, A-3, & A-5 AND LETTER FOR MEZZANINE STATING | | | RESIDENTIAL OCCUPANCY. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2009-09-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-09-09 |
Time |
12:54 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
2009-09-09 |
Time |
12:30 |
Sent To |
|
|
| Notes |
| 2009-09-09 13:05:01 | BUILDING PLAN REVIEW | | | PERMIT: 09070777 | | | ADD: 701 S OLIVE AVE SUITES: 115-116 | | | CONT: KAST | | | TEL: (561)281-3390 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2ND REVIEW | | | ACTION: DENIED | | | 09-09-09 | | | | | | 1) SECOND REQUEST, WHEN COMBINING TWO UNITS (115 & 116) | | | A UNITY OF TITLE WILL BE REQUIRED. CROSSING PROPERTY | | | LINES TABLE 602. | | | | | | 2)SECOND REQUEST, SHEET A-3 TOILET ROOM 107 INDICATES | | | THIS ROOM WAS ALTERED. 11-4.1.6(1)(A) NO ALTERATION | | | SHALL BE TRAKEN WHICH DECREASES OR HAS THE EFFECT OF | | | DECRESSING ACCESSIBILTY OR USABILITY OF A BUILDING OF | | | FACILITY BELOW THE REQUIREMENTS FOR NEW CONSTRUCTION AT | | | THE TIME OF ALTERATION.11-4.1.3(11) IF TOILET ROOMS ARE | | | PROVIDED, THEN EACH PUBLIC AND COMMON USE TOILET ROOM | | | SHALL COMPLY WITH SECTION 11-4.22. RESPONCE INDICATED | | | TO SEE FIGURE 28 WHICH DOES COMPLY WITH CHAPTER 11, THE | | | PLANS FAIL TO COMPLY WITH: 1-4.22.3 CLEAR FLOOR SPACE. | | | THE ACCESSIBLE FIXTURES AND CONTROLS REQUIRED IN | | | SECTIONS 11-4.22.4, 11-4.22.5, 11-4.22.6 AND 11-4.22.7 | | | SHALL BE ON AN ACCESSIBLE ROUTE. AN UNOBSTRUCTED | | | TURNING SPACE COMPLYING WITH SECTION 11-4.2.3 SHALL BE | | | PROVIDED WITHIN AN ACCESSIBLE TOILET ROOM. | | | | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | SURVEY: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | | | | | | | RECORDED UNITY OF TITLE- SUBMITTED 9-16-09 JW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-07-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-07-31 |
Time |
07:42 |
Rev Time |
1.10 |
| Received By |
jwitmer |
Date |
2009-07-30 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2009-07-31 07:53:48 | BUILDING PLAN REVIEW | | | PERMIT: 09070777 | | | ADD: 701 S OLIVE AVE SUITES: 115-116 | | | CONT: KAST | | | TEL: (561)281-3390 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) WHEN COMBINING TWO UNITS (115 & 116) A UNITY OF | | | TITLE WILL BE REQUIRED. CROSSING PROPERTY LINES TABLE | | | 602. | | | | | | 2) SHEET A-3 TOILET ROOM 107 INDICATES THIS ROOM WAS | | | ALTERED. 11-4.1.6(1)(A) NO ALTERATION SHALL BE TRAKEN | | | WHICH DECREASES OR HAS THE EFFECT OF DECRESSING | | | ACCESSIBILTY OR USABILITY OF A BUILDING OF FACILITY | | | BELOW THE REQUIREMENTS FOR NEW CONSTRUCTION AT THE TIME | | | OF ALTERATION.11-4.1.3(11) IF TOILET ROOMS ARE | | | PROVIDED, THEN EACH PUBLIC AND COMMON USE TOILET ROOM | | | SHALL COMPLY WITH SECTION 11-4.22. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | SURVEY: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2009-09-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-09-16 |
Time |
18:05 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-09-16 |
Time |
18:05 |
Sent To |
|
|
| Notes |
| 2009-09-16 18:05:48 | LOW VOLTAGE AND FIRE ALARM UNDER SEPARATE PERMITS. | | | NO ACCESS CONTROL SYSTEMS PRESENT ON PLANS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-07-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-07-31 |
Time |
19:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-07-31 |
Time |
19:27 |
Sent To |
|
|
| Notes |
| 2009-07-31 19:27:20 | ** DENIED REVIEW ** | | | | | | ** PLANS ARE COMING BACK FOR COMMENTS WITH RESPECT TO | | | UNITY OF TITLE. | | | | | | | | | | | | 1) NOTE: PANEL SCHEDULE WILL BE REQUIRED TO BE REVISED | | | TO ALL ROOMS/AREAS AND LOCATIONS TO BE SPECIFIC. ** THE | | | USE OF GENERAL LIGHTING* MAY NOT BE USED. | | | SEE UPDATED 408.4 OF THE 2005 NEC. | | | ** PLANS INDICATES CIRCUIT SUCH AS WASHER #9 ON PANEL | | | SCHEDULE T15 TO REMAIN * AS IS* HOWEVER THE PLANS MAKE | | | NOTES TO REMOVE BOTH THE WASHER AND DRYER CIRCUITS? | | | ** PLANS INDICATES CIRCUIT T15 -28 AS A LIGHTING | | | CIRCUIT YET THE T15 PANEL SCHEDULE INDICATES THIS AS A | | | WATER FOUNTAIN DEDICATED CIRCUIT? IT APPEARS 26 AND 28 | | | ARE SWITCHED. | | | ** SEE BATH ROOMS T15, 11, 13, 21, FIRST FLOOR, SECOND | | | FLOOR. | | | | | | 2) NOTE: PLEASE INDICATE ALLOWANCE/LIGHTING FOR J-BOX | | | IN CORRIDOR 105 DIRECTLY IN FRONT OF T15 PANEL. | | | PLEASE KNOW THAT THE SPECIFIC FIXTURES WHICH ARE NOW | | | SHOWN AS A 200WATT ALLOWANCE WILL BE REQUIRED TO BE | | | SHOWN ON FIXTURE LEGEND BEFORE THE END OF PROJECT. | | | KITCHEN AREA IS NOT FOOD SERVICE DESIGNATION AS WOULD | | | BE IN RESTAURANT OCCUPANCY. THIS WILL NOT AFFECT | | | CALCULATIONS. | | | | | | 3) NOTE: PLEASE SHOW THE REQUIRED SIGN CIRCUIT PER | | | 600.5 AND ADD LOADS ACCORDINGLY. | | | | | | 4) NOTE: PLEASE INDICATE NORMAL AND EMERGENCY EGRESS | | | LIGHTING LEVELS FOR STAIRS PER NFPA-101 7.8.1.3, | | | 7.9.2.1, .2.2. | | | FBC 1006.1 | | | | | | ** PER BUILDING OFFICIAL, REJECTED PLANS/PERMIT | | | APPLICATION ARE NO LONGER GIVEN BACK TO CONTRACTOR. | | | | | | ** PLEASE ALSO BE AWARE THE WEEK STARTING AUGUST 17TH, | | | THE CONSTRUCTION SERVICES DEPARTMENT WILL BE CLOSING ON | | | FRIDAY OF EACH WEEK UNTIL FURTHER NOTICE. THE 21ST OF | | | AUGUST WILL BE THE FIRST FRIDAY OF CLOSING. THERE WILL | | | NO LONGER BE THE ROTATING SCHEDULE CURRENTLY IN EFFECT. | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2009-09-21 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-09-21 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-09-21 |
Time |
13:45 |
Sent To |
|
|
| Notes |
| 2009-09-21 13:48:33 | ******RE-STAMP***** | | | | | | | | | PLAN SHEET A-5, PREVIOUSLY STAMPED, INITIALED, AND | | | DATED ON 9/17/2009, WAS RE-STAMPED AS PER JIM WIRMER. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2009-09-17 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-09-17 |
Time |
11:15 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-09-17 |
Time |
10:41 |
Sent To |
|
|
| Notes |
| 2009-09-17 11:03:25 | ****APPROVED***** | | | | | | PLAN SHEETS A-5, E-1, AND E-2 WERE STAMPED, INITIALED, | | | AND DATED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2009-08-14 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-08-14 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-08-14 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2009-08-14 14:50:35 | *****FIRE-STAMPING NEEDED***** | | | | | | | | | THE APPROPIATE PLAN SHEETS TO BE FIRE STAMPED WHEN THE | | | OTHER PLAN REVIEWERS' COMMENTS AS WELL AS THE BELOW | | | COMMENT HAS BEEN ADDRESSED: | | | | | | 1. ON SHEET E-2 - ELECTRICAL NOTE 2, AMEND FROM THE | | | 2003 EDITION OF NFPA-101 TO THE 2006 EDITION AS | | | PROPERLY STATED ON THE SHEET T IN THE REFERENCE | | | STANDARDS. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-09-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-09-01 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-09-01 |
Time |
13:50 |
Sent To |
|
|
| Notes |
| 2009-09-16 15:53:36 | RECEIVED EXPEDITED FORM 9/16/09 LM | | 2009-09-01 14:00:54 | SENT TO C-17. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2009-08-14 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-08-14 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-07-30 |
Time |
15:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2009-09-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-09-16 |
Time |
17:49 |
Rev Time |
|
| Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2009-09-09 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-09-09 |
Time |
15:11 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-09-09 |
Time |
14:27 |
Sent To |
|
|
| Notes |
| 2009-09-09 14:38:14 | PASSED WITH THE FOLLOWING CONDITIONS: | | | | | | 1. PROVIDE PRODUCT APPROVALS FOR BUILDING PLAN REVIEW | | | PER FAC-RULE 9B-72. PAGE M-2 SHOWS TWO NEW WALL | | | LOUVERS. | | | | | | 2. PROVIDE TEST AND BALANCE REPORT AT TIME OF FINAL | | | INSPECTION TO VERIFY VENTILATION AIRFLOW RATES IN | | | ACCORDANCE WITH ASHRAE 62.1-2004 SECTION 7.2.2. | | | | | | 3. HP-1 REQUIRES A DUCT MOUNTED SMOKE DETECTOR | | | INSTALLED AND CONNECTED TO BUILDING FIRE ALARM SYSTEM | | | IN ACCORDANCE WITH FBC-M 606.2.1 AND 606.4. | | | | | | 4. ENERGY CALCULATIONS NOT REVIEWED AS PART OF THIS | | | PERMIT FOR COMPLIANCE WITH THE MECHANICAL PROVIDIONS OF | | | THE FLORIDA ENERGY CODE. COOLING LOAD CALCULATIONS HAVE | | | BEEN DETATCHED FROM ENERGY CALCULATIONS AND RETAINED AS | | | PART OF THIS PERMIT RECORD DUE TO INCREASED COOLING | | | LOADS ASSOCIATED WITH ADDED OUTSIDE AIR. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2009-08-05 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-08-05 |
Time |
19:40 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-08-05 |
Time |
18:44 |
Sent To |
|
|
| Notes |
| 2009-08-05 19:40:33 | PASSED WITH THE FOLLOWING CONDITIONS: | | | | | | 1. PROVIDE PRODUCT APPROVALS FOR BUILDING PLAN REVIEW | | | PER FAC-RULE 9B-72. PAGE M-2 SHOWS TWO NEW WALL | | | LOUVERS. | | | | | | 2. PROVIDE TEST AND BALANCE REPORT AT TIME OF FINAL | | | INSPECTION TO VERIFY VENTILATION AIRFLOW RATES IN | | | ACCORDANCE WITH ASHRAE 62.1-2004 SECTION 7.2.2. | | | | | | 3. HP-1 REQUIRES A DUCT MOUNTED SMOKE DETECTOR | | | INSTALLED AND CONNECTED TO BUILDING FIRE ALARM SYSTEM | | | IN ACCORDANCE WITH FBC-M 606.2.1 AND 606.4. | | | | | | 4. ENERGY CALCULATIONS NOT REVIEWED AS PART OF THIS | | | PERMIT FOR COMPLIANCE WITH THE MECHANICAL PROVIDIONS OF | | | THE FLORIDA ENERGY CODE. COOLING LOAD CALCULATIONS HAVE | | | BEEN DETATCHED FROM ENERGY CALCULATIONS AND RETAINED AS | | | PART OF THIS PERMIT RECORD DUE TO INCREASED COOLING | | | LOADS ASSOCIATED WITH ADDED OUTSIDE AIR. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2009-08-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-08-06 |
Time |
07:24 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-08-05 |
Time |
17:17 |
Sent To |
|
|
| Notes |
| 2009-08-06 07:27:00 | | | | | | | | | | PASSED/PROVISO: | | | | | | TOILET ROOM 107 SHALL BE ACCESSIBLE. A REVISION IS | | | REQUIRED SHOWING ALL REQUIREMENTS PER SECTIONS 11-4.16, | | | 11-4.19 & 11-4.22. SECTION 11-4.1.3(11). |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2009-08-07 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2009-08-07 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
aaponte |
Date |
2009-08-07 |
Time |
14:59 |
Sent To |
|
|
| Notes |
|
|