Plan Review Details - Permit 09070777
Plan Review Stops For Permit 09070777
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-09-21 Cont ID  
Sent By jwitmer Date 2009-09-21 Time 13:45 Rev Time 0.00
Received By jwitmer Date 2009-09-21 Time 13:00 Sent To  
Notes
2009-09-21 13:41:24NEW A-1, A-3, & A-5 AND LETTER FOR MEZZANINE STATING
 RESIDENTIAL OCCUPANCY.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-09-09 Cont ID  
Sent By jwitmer Date 2009-09-09 Time 12:54 Rev Time 0.75
Received By jwitmer Date 2009-09-09 Time 12:30 Sent To  
Notes
2009-09-09 13:05:01BUILDING PLAN REVIEW
 PERMIT: 09070777
 ADD: 701 S OLIVE AVE SUITES: 115-116
 CONT: KAST
 TEL: (561)281-3390
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
 09-09-09
  
 1) SECOND REQUEST, WHEN COMBINING TWO UNITS (115 & 116)
 A UNITY OF TITLE WILL BE REQUIRED. CROSSING PROPERTY
 LINES TABLE 602.
  
 2)SECOND REQUEST, SHEET A-3 TOILET ROOM 107 INDICATES
 THIS ROOM WAS ALTERED. 11-4.1.6(1)(A) NO ALTERATION
 SHALL BE TRAKEN WHICH DECREASES OR HAS THE EFFECT OF
 DECRESSING ACCESSIBILTY OR USABILITY OF A BUILDING OF
 FACILITY BELOW THE REQUIREMENTS FOR NEW CONSTRUCTION AT
 THE TIME OF ALTERATION.11-4.1.3(11) IF TOILET ROOMS ARE
 PROVIDED, THEN EACH PUBLIC AND COMMON USE TOILET ROOM
 SHALL COMPLY WITH SECTION 11-4.22. RESPONCE INDICATED
 TO SEE FIGURE 28 WHICH DOES COMPLY WITH CHAPTER 11, THE
 PLANS FAIL TO COMPLY WITH: 1-4.22.3 CLEAR FLOOR SPACE.
 THE ACCESSIBLE FIXTURES AND CONTROLS REQUIRED IN
 SECTIONS 11-4.22.4, 11-4.22.5, 11-4.22.6 AND 11-4.22.7
 SHALL BE ON AN ACCESSIBLE ROUTE. AN UNOBSTRUCTED
 TURNING SPACE COMPLYING WITH SECTION 11-4.2.3 SHALL BE
 PROVIDED WITHIN AN ACCESSIBLE TOILET ROOM.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
 RECORDED UNITY OF TITLE- SUBMITTED 9-16-09 JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-07-31 Cont ID  
Sent By jwitmer Date 2009-07-31 Time 07:42 Rev Time 1.10
Received By jwitmer Date 2009-07-30 Time 17:00 Sent To  
Notes
2009-07-31 07:53:48BUILDING PLAN REVIEW
 PERMIT: 09070777
 ADD: 701 S OLIVE AVE SUITES: 115-116
 CONT: KAST
 TEL: (561)281-3390
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) WHEN COMBINING TWO UNITS (115 & 116) A UNITY OF
 TITLE WILL BE REQUIRED. CROSSING PROPERTY LINES TABLE
 602.
  
 2) SHEET A-3 TOILET ROOM 107 INDICATES THIS ROOM WAS
 ALTERED. 11-4.1.6(1)(A) NO ALTERATION SHALL BE TRAKEN
 WHICH DECREASES OR HAS THE EFFECT OF DECRESSING
 ACCESSIBILTY OR USABILITY OF A BUILDING OF FACILITY
 BELOW THE REQUIREMENTS FOR NEW CONSTRUCTION AT THE TIME
 OF ALTERATION.11-4.1.3(11) IF TOILET ROOMS ARE
 PROVIDED, THEN EACH PUBLIC AND COMMON USE TOILET ROOM
 SHALL COMPLY WITH SECTION 11-4.22.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-09-16 Cont ID  
Sent By dpalmer Date 2009-09-16 Time 18:05 Rev Time 0.00
Received By dpalmer Date 2009-09-16 Time 18:05 Sent To  
Notes
2009-09-16 18:05:48LOW VOLTAGE AND FIRE ALARM UNDER SEPARATE PERMITS.
 NO ACCESS CONTROL SYSTEMS PRESENT ON PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-07-31 Cont ID  
Sent By dpalmer Date 2009-07-31 Time 19:27 Rev Time 0.00
Received By dpalmer Date 2009-07-31 Time 19:27 Sent To  
Notes
2009-07-31 19:27:20** DENIED REVIEW **
  
 ** PLANS ARE COMING BACK FOR COMMENTS WITH RESPECT TO
 UNITY OF TITLE.
  
  
  
 1) NOTE: PANEL SCHEDULE WILL BE REQUIRED TO BE REVISED
 TO ALL ROOMS/AREAS AND LOCATIONS TO BE SPECIFIC. ** THE
 USE OF GENERAL LIGHTING* MAY NOT BE USED.
 SEE UPDATED 408.4 OF THE 2005 NEC.
 ** PLANS INDICATES CIRCUIT SUCH AS WASHER #9 ON PANEL
 SCHEDULE T15 TO REMAIN * AS IS* HOWEVER THE PLANS MAKE
 NOTES TO REMOVE BOTH THE WASHER AND DRYER CIRCUITS?
 ** PLANS INDICATES CIRCUIT T15 -28 AS A LIGHTING
 CIRCUIT YET THE T15 PANEL SCHEDULE INDICATES THIS AS A
 WATER FOUNTAIN DEDICATED CIRCUIT? IT APPEARS 26 AND 28
 ARE SWITCHED.
 ** SEE BATH ROOMS T15, 11, 13, 21, FIRST FLOOR, SECOND
 FLOOR.
  
 2) NOTE: PLEASE INDICATE ALLOWANCE/LIGHTING FOR J-BOX
 IN CORRIDOR 105 DIRECTLY IN FRONT OF T15 PANEL.
 PLEASE KNOW THAT THE SPECIFIC FIXTURES WHICH ARE NOW
 SHOWN AS A 200WATT ALLOWANCE WILL BE REQUIRED TO BE
 SHOWN ON FIXTURE LEGEND BEFORE THE END OF PROJECT.
 KITCHEN AREA IS NOT FOOD SERVICE DESIGNATION AS WOULD
 BE IN RESTAURANT OCCUPANCY. THIS WILL NOT AFFECT
 CALCULATIONS.
  
 3) NOTE: PLEASE SHOW THE REQUIRED SIGN CIRCUIT PER
 600.5 AND ADD LOADS ACCORDINGLY.
  
 4) NOTE: PLEASE INDICATE NORMAL AND EMERGENCY EGRESS
 LIGHTING LEVELS FOR STAIRS PER NFPA-101 7.8.1.3,
 7.9.2.1, .2.2.
 FBC 1006.1
  
 ** PER BUILDING OFFICIAL, REJECTED PLANS/PERMIT
 APPLICATION ARE NO LONGER GIVEN BACK TO CONTRACTOR.
  
 ** PLEASE ALSO BE AWARE THE WEEK STARTING AUGUST 17TH,
 THE CONSTRUCTION SERVICES DEPARTMENT WILL BE CLOSING ON
 FRIDAY OF EACH WEEK UNTIL FURTHER NOTICE. THE 21ST OF
 AUGUST WILL BE THE FIRST FRIDAY OF CLOSING. THERE WILL
 NO LONGER BE THE ROTATING SCHEDULE CURRENTLY IN EFFECT.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-09-21 Cont ID  
Sent By mawillia Date 2009-09-21 Time 13:48 Rev Time 0.00
Received By mawillia Date 2009-09-21 Time 13:45 Sent To  
Notes
2009-09-21 13:48:33******RE-STAMP*****
  
  
 PLAN SHEET A-5, PREVIOUSLY STAMPED, INITIALED, AND
 DATED ON 9/17/2009, WAS RE-STAMPED AS PER JIM WIRMER.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-09-17 Cont ID  
Sent By mawillia Date 2009-09-17 Time 11:15 Rev Time 0.00
Received By mawillia Date 2009-09-17 Time 10:41 Sent To  
Notes
2009-09-17 11:03:25****APPROVED*****
  
 PLAN SHEETS A-5, E-1, AND E-2 WERE STAMPED, INITIALED,
 AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-08-14 Cont ID  
Sent By mawillia Date 2009-08-14 Time 14:51 Rev Time 0.00
Received By mawillia Date 2009-08-14 Time 14:02 Sent To  
Notes
2009-08-14 14:50:35*****FIRE-STAMPING NEEDED*****
  
  
 THE APPROPIATE PLAN SHEETS TO BE FIRE STAMPED WHEN THE
 OTHER PLAN REVIEWERS' COMMENTS AS WELL AS THE BELOW
 COMMENT HAS BEEN ADDRESSED:
  
 1. ON SHEET E-2 - ELECTRICAL NOTE 2, AMEND FROM THE
 2003 EDITION OF NFPA-101 TO THE 2006 EDITION AS
 PROPERLY STATED ON THE SHEET T IN THE REFERENCE
 STANDARDS.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-01 Cont ID  
Sent By kstevens Date 2009-09-01 Time 13:50 Rev Time 0.00
Received By kstevens Date 2009-09-01 Time 13:50 Sent To  
Notes
2009-09-16 15:53:36RECEIVED EXPEDITED FORM 9/16/09 LM
2009-09-01 14:00:54SENT TO C-17.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-08-14 Cont ID  
Sent By mawillia Date 2009-08-14 Time 14:02 Rev Time 0.00
Received By mawillia Date 2009-07-30 Time 15:14 Sent To  
Notes
2009-07-30 15:14:55B-5

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2009-09-16 Cont ID  
Sent By dpalmer Date 2009-09-16 Time 17:49 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-09-09 Cont ID  
Sent By rregueir Date 2009-09-09 Time 15:11 Rev Time 0.00
Received By rregueir Date 2009-09-09 Time 14:27 Sent To  
Notes
2009-09-09 14:38:14PASSED WITH THE FOLLOWING CONDITIONS:
  
 1. PROVIDE PRODUCT APPROVALS FOR BUILDING PLAN REVIEW
 PER FAC-RULE 9B-72. PAGE M-2 SHOWS TWO NEW WALL
 LOUVERS.
  
 2. PROVIDE TEST AND BALANCE REPORT AT TIME OF FINAL
 INSPECTION TO VERIFY VENTILATION AIRFLOW RATES IN
 ACCORDANCE WITH ASHRAE 62.1-2004 SECTION 7.2.2.
  
 3. HP-1 REQUIRES A DUCT MOUNTED SMOKE DETECTOR
 INSTALLED AND CONNECTED TO BUILDING FIRE ALARM SYSTEM
 IN ACCORDANCE WITH FBC-M 606.2.1 AND 606.4.
  
 4. ENERGY CALCULATIONS NOT REVIEWED AS PART OF THIS
 PERMIT FOR COMPLIANCE WITH THE MECHANICAL PROVIDIONS OF
 THE FLORIDA ENERGY CODE. COOLING LOAD CALCULATIONS HAVE
 BEEN DETATCHED FROM ENERGY CALCULATIONS AND RETAINED AS
 PART OF THIS PERMIT RECORD DUE TO INCREASED COOLING
 LOADS ASSOCIATED WITH ADDED OUTSIDE AIR.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-08-05 Cont ID  
Sent By rregueir Date 2009-08-05 Time 19:40 Rev Time 0.00
Received By rregueir Date 2009-08-05 Time 18:44 Sent To  
Notes
2009-08-05 19:40:33PASSED WITH THE FOLLOWING CONDITIONS:
  
 1. PROVIDE PRODUCT APPROVALS FOR BUILDING PLAN REVIEW
 PER FAC-RULE 9B-72. PAGE M-2 SHOWS TWO NEW WALL
 LOUVERS.
  
 2. PROVIDE TEST AND BALANCE REPORT AT TIME OF FINAL
 INSPECTION TO VERIFY VENTILATION AIRFLOW RATES IN
 ACCORDANCE WITH ASHRAE 62.1-2004 SECTION 7.2.2.
  
 3. HP-1 REQUIRES A DUCT MOUNTED SMOKE DETECTOR
 INSTALLED AND CONNECTED TO BUILDING FIRE ALARM SYSTEM
 IN ACCORDANCE WITH FBC-M 606.2.1 AND 606.4.
  
 4. ENERGY CALCULATIONS NOT REVIEWED AS PART OF THIS
 PERMIT FOR COMPLIANCE WITH THE MECHANICAL PROVIDIONS OF
 THE FLORIDA ENERGY CODE. COOLING LOAD CALCULATIONS HAVE
 BEEN DETATCHED FROM ENERGY CALCULATIONS AND RETAINED AS
 PART OF THIS PERMIT RECORD DUE TO INCREASED COOLING
 LOADS ASSOCIATED WITH ADDED OUTSIDE AIR.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-08-06 Cont ID  
Sent By kstevens Date 2009-08-06 Time 07:24 Rev Time 0.00
Received By kstevens Date 2009-08-05 Time 17:17 Sent To  
Notes
2009-08-06 07:27:00 
  
  
 PASSED/PROVISO:
  
 TOILET ROOM 107 SHALL BE ACCESSIBLE. A REVISION IS
 REQUIRED SHOWING ALL REQUIREMENTS PER SECTIONS 11-4.16,
 11-4.19 & 11-4.22. SECTION 11-4.1.3(11).

Review Stop Z ZONING
Rev No 1 Status N Date 2009-08-07 Cont ID  
Sent By aaponte Date 2009-08-07 Time 14:59 Rev Time 0.00
Received By aaponte Date 2009-08-07 Time 14:59 Sent To  
Notes
***NONE***