| Plan Review Stops For Permit 09070775 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2011-05-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2011-05-25 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2011-05-25 |
Time |
09:35 |
Sent To |
|
|
| Notes |
| 2011-05-25 09:36:02 | BAR JOIST CALCULATIONS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2010-07-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-07-28 |
Time |
15:03 |
Rev Time |
0.75 |
| Received By |
jwitmer |
Date |
2010-07-28 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2010-07-28 15:04:58 | BUILDING PLAN REVIEW | | | PERMIT: 09070775 | | | ADD: 4295 45TH ST | | | CONT: TO BE DETERMINED | | | TEL: (561)856-6655 NEYITA LEIVA | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | JULY 28/ 2010 | | | | | | | | | | | | 1 PROVISO: ADDITION IS LOCATED WITHIN A FLOODZONE A8 AT | | | WITH A REQUIRED ELEVATION OF 15.5 FT NGVD, FBC BUILDING | | | 3110.1.2 / CITY OF WPB CODE OF ORDINANCES SECTION | | | 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A | | | FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED ONCE THE | | | FLOOR SLAB HAS BEEN POURED. | | | | | | | | | BUILDING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISION, DOCUMENTS | | | THAT ARE BEING PROVISOED, WILL REQUIRE ADDITIONAL | | | REVIEWS WITH ASSOCIATED FEES. | | | | | | | | | 2) BUILDING PROVISO:FL BLD CODE 1609.6.2.2 COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT | | | INSPECTOR OF PRODUCT TESTING REPORTS, MISSING REPORTS | | | ARE AS FOLLOWS: | | | A-F) COMPLIED. | | | G) ROOFING ASSEMBLIES INCLUDING ROOF INSULATION- | | | SUBMITTED WAS CARLISLE ROOF DECK NOA 08-0108.09 | | | NO SUB-SYSTEM WAS HIGHLIGHTED, ALL SYSTEMSWILL REQUIRE | | | ENHANCED FASTENING. | | | | | | 9-16-2010 | | | PAGE 14 JOIST LIMITATION OF 6'-0" OK DISMISS COMMENT | | | BELOW | | | PAGE 17- STEEL DECK SYSTEM LIMITATION, NOTE# 2 INDICATE | | | BAR JOIST SPACING A MAXIMUM OF 5'-0". BAR JOIST J1 & J2 | | | ARE APPROXIMATELY 5'-10" C/C AND BAR JOIST J4 ARE | | | APPROXIMATELY 5'-6" C/C/. WILL REQUIRE A DIFFERENT | | | SYSTEM. | | | | | | H) ROOF TOP PENBARRY ALUMINUM FANS NOA: 09-1015.03 | | | +/-V50 PSF FANS ARE LOCATED IN ZONES 2 AAND ZONE 3 OF | | | ROOF WITH DRAMATICLLY HIGHER PRESSURES. | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | SURVEY: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2010-04-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-04-21 |
Time |
11:48 |
Rev Time |
1.55 |
| Received By |
jwitmer |
Date |
2010-04-21 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2010-04-21 11:59:55 | BUILDING PLAN REVIEW | | | PERMIT: 09070775 | | | ADD: 4295 45TH ST | | | CONT: TO BE DETERMINED | | | TEL: (561)856-6655 NEYITA LEIVA | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | APRIL 21/ 2010 | | | | | | ACTION: DENIED | | | | | | ONCE TTHE CONTRACTOR HAS SIGNED ON, LICENSURE CAN BE | | | VERIFIED AND PERMIT VALUATION IS VERIFIED THEN A PASS | | | CAN BE ENTERED. | | | | | | 1-4) COMPLIED. | | | | | | 5) PROVISO: ADDITION IS LOCATED WITHIN A FLOODZONE A8 | | | AT WITH A REQUIRED ELEVATION OF 15.5 FT NGVD, FBC | | | BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES | | | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD | | | ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED | | | ONCE THE FLOOR SLAB HAS BEEN POURED. | | | | | | | | | BUILDING APPROVED WITH EXCEPTION! | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISION, DOCUMENTS | | | THAT ARE BEING PROVISOED, WILL REQUIRE ADDITIONAL | | | REVIEWS WITH ASSOCIATED FEES. | | | | | | | | | 6) BUILDING PROVISO:FL BLD CODE 1609.6.2.2 COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT | | | INSPECTOR OF PRODUCT TESTING REPORTS, MISSING REPORTS | | | ARE AS FOLLOWS: | | | A-F) COMPLIED. | | | G) ROOFING ASSEMBLIES INCLUDING ROOF INSULATION- | | | SUBMITTED WAS CARLISLE ROOF DECK NOA 08-0108.09 | | | NO SUB-SYSTEM WAS HIGHLIGHTED, ALL SYSTEMSWILL REQUIRE | | | ENHANCED FASTENING. | | | PAGE 17- STEEL DECK SYSTEM LIMITATION, NOTE# 2 INDICATE | | | BAR JOIST SPACING A MAXIMUM OF 5'-0". BAR JOIST J1 & J2 | | | ARE APPROXIMATELY 5'-10" C/C AND BAR JOIST J4 ARE | | | APPROXIMATELY 5'-6" C/C/. WILL REQUIRE A DIFFERENT | | | SYSTEM. | | | | | | H) ROOF TOP PENBARRY ALUMINUM FANS NOA: 09-1015.03 | | | +/-V50 PSF FANS ARE LOCATED IN ZONES 2 AAND ZONE 3 OF | | | ROOF WITH DRAMATICLLY HIGHER PRESSURES. | | | | | | 7-9) COMPLIED. | | | | | | 10) IMPACT FEES PAID PR# 2010-0419-215 | | | 11) COMPLIED. | | | | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | SURVEY: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2010-03-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-03-23 |
Time |
11:24 |
Rev Time |
4.00 |
| Received By |
jwitmer |
Date |
2010-03-23 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2010-03-23 11:35:45 | BUILDING PLAN REVIEW | | | PERMIT: 09070775 | | | ADD: 4295 45TH ST | | | CONT: TO BE DETERMINED | | | TEL: (561)856-6655 NEYITA LEIVA | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | MARCH 23/ 2010 | | | 3RD REVIEW | | | ACTION: DENIED | | | | | | 1) COMPLIED. | | | | | | 2-4) COMPLIED. | | | | | | 5) PROVISO: ADDITION IS LOCATED WITHIN A FLOODZONE A8 | | | AT WITH A REQUIRED ELEVATION OF 15.5 FT NGVD, FBC | | | BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES | | | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD | | | ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED | | | ONCE THE FLOOR SLAB HAS BEEN POURED. | | | | | | 6) BUILDING PROVISO:FL BLD CODE 1609.6.2.2 COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT | | | INSPECTOR OF PRODUCT TESTING REPORTS, MISSING REPORTS | | | ARE AS FOLLOWS: | | | A-F) COMPLIED. | | | G) ROOFING ASSEMBLIES INCLUDING ROOF INSULATION- | | | SUBMITTED WAS CARLISLE ROOF DECK NOA 08-0108.09 | | | NO SUB-SYSTEM WAS HIGHLIGHTED, ALL SYSTEMSWOULD REQUIRE | | | ENHANCED FASTENING. | | | PAGE 17- STEEL DECK SYSTEM LIMITATION, NOTE# 2 INDICATE | | | BAR JOIST SPACING A MAXIMUM OF 5'-0". BAR JOIST J1 & J2 | | | ARE APPROXIMATELY 5'-10" C/C AND BAR JOIST J4 ARE | | | APPROXIMATELY 5'-6" C/C/. WILL REQUIRE A DIFFERENT | | | SYSTEM. | | | | | | H) ROOF TOP PENBARRY ALUMINUM FANS NOA: 09-1015.03 | | | +/-V50 PSF FANS ARE LOCATED IN ZONES 2 AAND ZONE 3 OF | | | ROOF WITH DRAMATICLLY HIGHER PRESSURES. | | | | | | 7-9) COMPLIED. | | | | | | 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 11) COMPLIED. | | | | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | SURVEY: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2009-12-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-12-28 |
Time |
11:25 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2009-12-28 |
Time |
11:24 |
Sent To |
|
|
| Notes |
| 2009-12-28 13:27:39 | BUILDING PLAN REVIEW | | | PERMIT: 09070775 | | | ADD: 4295 45TH ST | | | CONT: TO BE DETERMINED | | | TEL: (561)856-6655 NEYITA LEIVA | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | DEC. 28/ 2009 | | | 2ND REVIEW | | | ACTION: DENIED | | | | | | 1) COMPLIED. | | | | | | 2) SUBMITTED ENERGY CALCS FORM 400B-2008. THIS FORM | | | PLEASE SEE BOTH THE ELECTRICAL AND MECHANICAL COMMENTS | | | ON THE REQUIRED SIGNATURE AND SEAL REQUIREMENTS. | | | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS | | | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR | | | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE | | | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. | | | FL ADMIN CODE 61G15-23.002 ENGINEERS | | | FL ADMIN CODE 61G16.003 ARCHITECTS | | | | | | 3-4) COMPLIED. | | | | | | 5) PROVISO: ADDITION IS LOCATED WITHIN A FLOODZONE A8 | | | AT WITH A REQUIRED ELEVATION OF 15.5 FT NGVD, FBC | | | BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES | | | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD | | | ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. | | | | | | 6) PLEASE NOTE THAT PRODUCT APPROVALS WILL NOT BE | | | REQUIRED AT TIME OF PERMITTING BUT WILL BE REQUIRED FOR | | | FULL REVIEW. | | | | | | BUILDING PROVISO:FL BLD CODE 1609.6.2.2 COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT | | | INSPECTOR OF PRODUCT TESTING REPORTS, MISSING REPORTS | | | ARE AS FOLLOWS: | | | A) EXTERIOR GLAZED WINDOWS | | | B) MULLION | | | C) EXTERIOR GLAZED DOORS, AUTOMATIC SLIDDING GLASS | | | DOORS W/ TRANSOM | | | D) OVERHEAD DOORS | | | E) WALL LOUVERS | | | F) EFIS SYSTEMS | | | G) ROOFING ASSEMBLIES INCLUDING ROOF INSULATION | | | H) PERMANUFACTURED A/C STANDS | | | | | | 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE | | | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND | | | APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO | | | SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | 7) PARTIAL APPROVAL, ENGINEERING CALCULATIONS WERE | | | SUBMITTED FOR THE ATTACHMENT OF THE CURB TO ROOF | | | FRAMING MEMBERS WIWTH A CLIP SYSTEM, PRODUCED BY ICR | | | ENGINEERING, INC. THE CALCULATIONS ARE NOT SIGNED NOR | | | SEALED NOR DO THEY PROVIDE A SIGNED AND SEALED COVER | | | SHEET. | | | | | | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS | | | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR | | | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE | | | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. | | | FL ADMIN CODE 61G15-23.002 ENGINEERS | | | | | | 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX | | | SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND | | | THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE | | | PRODUCTION & PREPARATION OF EACH SECTION OF THE | | | ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION | | | ON THE COVER SHEET OR INDEX. | | | | | | A3.3 PLEASE NOTE THAT ROOF TOP MECHANICAL EQUIPMENT | | | MUST MEET THE WIND REQUIREMENTS IN CHAPTER 16 OF FBC. | | | 301.13 FBC MECHANICAL. WIND RESISTANCE. MECHANICAL | | | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO | | | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST WIND | | | PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS | | | DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING | | | CODE, BUILDING. NOTE THE STRUCTURAL SHEETS INDICATE THE | | | CURB ATTACHMENTS TO THE ROOF DECK BUT NOT THE UNIT TO | | | THE ROOF CURB. | | | | | | 2ND REQUEST, FOR ALL ROOFTOP EQUIPMENT PLEASE PROVIDE | | | EITHER BY TESTING, CALCULATIONS OR RATIONAL ANYLSIS THE | | | EXTERIOR ELEMENTS (CABINETS)OF THE ROOF TOP EQUIPMENT | | | ARE DESIGNED TO WITHSTAND THE WIND REQUIREMENTS OF | | | CHAPTER 16 OF THE FLORIDA BUILDING CODE BUILDING AS | | | REQUIRED BY SECTION 301.13 FBC MECHANICAL CODE. | | | | | | 8) COMPLIED. | | | | | | 9) 2ND REQUESST, PLANS INDICATE THE USE OF WALK IN | | | COOLERS ( AGA1) PLEASE PROVIDE DOCUMENTATION THAT THE | | | THERMA- STRUCTURE COOLERS COMPLIES WITH SECTION | | | 2603.4.1.2 (1-4). SUBMITTALS FOR FREZZER CASES WERE | | | FOUND BUT NOT FOR THE WALK IN COOLERS.2603.4.1.2 COOLER | | | AND FREEZER WALLS. FOAM PLASTIC INSTALLED IN A MAXIMUM | | | THICKNESS OF 10 INCHES (254 MM) IN COOLER AND FREEZER | | | WALLS SHALL: | | | | | | 1. HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A | | | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE | | | TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS. | | | | | | 2. HAVE FLASH IGNITION AND SELF-IGNITION TEMPERATURES | | | OF NOT LESS THAN 600??F AND 800??F (316??C AND 427??C), | | | RESPECTIVELY. | | | | | | 3. HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8 MM) | | | ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE | | | METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT | | | ANY POINT. | | | | | | 4. BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM. WHERE | | | THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH THE | | | COOLER OR FREEZER AND THAT PART OF THE BUILDING IN | | | WHICH IT IS LOCATED SHALL BE SPRINKLERED. | | | | | | | | | 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | 11) NEW COMMENT SHEET S6.3 PLEASE SEE FBC* 106.1 THE | | | NEW TYPE OF ENGINEER'S SEAL IS REQUIRED FOR ALL PLANS | | | SEALED AFTER 12/31/05. ENGINEER'S SEALS INCLUDING THE | | | WORD "CERTIFICATE" ARE NO LONGER VALID. ON 2/5/04 THE | | | FLORIDA BOARD OF PROFESSIONAL ENGINEERS AMENDED THE | | | 'SEALS' RULE AND REQUIRED THAT ALL MEMBERS OBTAIN SEALS | | | WITH THE WORD "LICENSE" INSTEAD OF "CERTIFICATE". THE | | | EXTENDED GRACE PERIOD FOR COMPLIANCE ENDED ON 12/31/05. | | | (REF: 471.025 F.S. AND RULE 61G15-23.001 F.A.C.) | | | | | | RULE 61G15-23.001(1) F.A.C. THE FLORIDA BOARD OF | | | PROFESSIONAL ENGINEERS HAS CLEANED UP THE APPEARANCE | | | OF THE SEAL BY ELIMINATING OBSOLETE CONTENT AND | | | CHANGING THE WORD "CERTIFICATE" TO "LICENSE". A GRACE | | | PERIOD RAN THROUGH DEC. 31,2005. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | SURVEY: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-08-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-08-11 |
Time |
16:32 |
Rev Time |
5.60 |
| Received By |
jwitmer |
Date |
2009-08-11 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2009-08-11 16:52:52 | BUILDING PLAN REVIEW | | | PERMIT: 09070775 | | | ADD: 4295 45TH ST | | | CONT: TO BE DETERMINED | | | TEL: (561)856-6655 NEYITA LEIVA | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | AUGUST 11/2009 | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1A) COVER SHEET/ CODES: PLANS SUBMITTED FOR PERMIT | | | (FIRST TIME REVIEW) AFTER MARCH 1ST, 2009 SHALL BE | | | REVIEWED TO THE 2007 FBC BUILDING WITH 2009 | | | SUPPLEMENTS. | | | PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING | | | BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO | | | WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS | | | PERMIT. | | | 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE | | | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 403, 404 AND 405 OF THIS CODE. | | | | | | 1B) COVER SHEET/ CODES: PLANS INDICATE THE HANDICAPPED | | | ACCESSIBILITY GUIDELINES AS AMERICANS WITH DISSIBILITY | | | GUIDELINES PLEASE SEE FLORIDA'S BUILDING CODE , CHAPTER | | | 11 WHICH NOT ONLY ADOPTED THE ADAG BUT IS MORE | | | RESTRICTIVE AND WERE ADOPTED BY THE DEPARTMENT OF | | | JUSTICE. | | | | | | 2) SUBMITTED WAS THE 2004 ENERGY CALCS FORM 400A-2004R. | | | THIS FORM IS NO LONGER IN EFFECT. WHEN THE 2007 FBC | | | CAME INTO EFFECT THIS FORM WAS NULL IN VOID. PLEASE | | | REVIEW AND USE FORM 400B-08, THIS IS FOR COMMERCIAL | | | RENOVASIONS. | | | | | | 3) SHEET S0: | | | | | | 3A) SECTION # 5 DEALS WITH FOUNDATIONS PLEASE PROVIDE | | | THE SOILS REPORT PREPARED BY ECS OF FLORIDA LLC, JULY | | | 9/ 2009. 1802.2.1 QUESTIONABLE SOIL. WHERE THE | | | SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE | | | A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS | | | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE | | | THAT THE NECESSARY INVESTIGATION BE MADE. SUCH | | | INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF | | | SECTIONS 1802.4 THROUGH 1802.6 . | | | | | | 3B) SECTION # 2 & 6 BOTH MAKE REFRENECE TO THE IBC | | | SPECIAL INSPECTION SECTION 1704, PLEASE REVIEW THIS | | | SECTION WAS NOT ADOPTED INTO THE FLORIDA BUILDING CODE, | | | BUILDING. | | | | | | 4) THE COVERSHEET INDICATES SQUARE FOOTAGE BY OCCUPANCY | | | BUT NOT BY EXISTING AND ADDITIONAL SQ. FOOTAGE BEING | | | ADDED AS AN ADDITION. 106.1.2. ADDITIONAL INFORMATION | | | REQUIRED. | | | | | | 5) ADDITION IS LOCATED WITHIN A FLOODZONE A8 AT WITH A | | | REQUIRED ELEVATION OF 15.5 FT NGVD, FBC BUILDING | | | 3110.1.2 / CITY OF WPB CODE OF ORDINANCES SECTION | | | 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A | | | FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. | | | | | | 6) PLEASE NOTE THAT PRODUCT APPROVALS WILL NOT BE | | | REQUIRED AT TIME OF PERMITTING BUT WILL BE REQUIRED FOR | | | FULL REVIEW. | | | | | | BUILDING PROVISO:FL BLD CODE 1609.6.2.2 COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT | | | INSPECTOR OF PRODUCT TESTING REPORTS, MISSING REPORTS | | | ARE AS FOLLOWS: | | | A) EXTERIOR GLAZED WINDOWS | | | B) MULLION | | | C) EXTERIOR GLAZED DOORS, AUTOMATIC SLIDDING GLASS | | | DOORS W/ TRANSOM | | | D) OVERHEAD DOORS | | | E) WALL LOUVERS | | | F) EFIS SYSTEMS | | | G) ROOFING ASSEMBLIES INCLUDING ROOF INSULATION | | | H) PERMANUFACTURED A/C STANDS | | | | | | 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE | | | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND | | | APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO | | | SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | 7) A3.3 PLEASE NOTE THAT ROOF TOP MECHANICAL EQUIPMENT | | | MUSST MEET THE WIND REQUIREMENTS IN CHAPTER 16 OF FBC. | | | 301.13 FBC MECHANICAL. WIND RESISTANCE. MECHANICAL | | | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO | | | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST WIND | | | PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS | | | DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING | | | CODE, BUILDING. NOTE THE STRUCTURAL SHEETS INDICATE THE | | | CURB ATTACHMENTS TO THE ROOF DECK BUT NOT THE UNIT TO | | | THE ROOF CURB. | | | | | | 8) A3.4 PLEASE SEE A3.4 EXTERIOR WALL SECTION INDICATE | | | 1/2 INCH CD PLYWOOD ON WALLS. PLEASE SEE SECTION | | | 603.1(1.1)AND (1.2) FOR WHERE FIRE RETARDANT TREATED | | | ELEMENTS CAN BE INSTALLED. | | | | | | 9) PLANS INDICATE THE USE OF WALK IN COOLERS PLEASE | | | PROVIDE DOCUMENTATION THAT THE THERMA- STRUCTURE | | | COOLERS COMPLIES WITH SECTION 2603.4.1.2 (1-4). | | | | | | 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | SURVEY: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2010-04-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2010-04-28 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2010-04-28 |
Time |
09:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2010-02-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2010-02-25 |
Time |
17:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2010-02-25 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2010-02-25 17:00:34 | ** DENIED ** | | | | | | | | | 1) NOTE: THERE ARE THREE NEW BOOKS SUBMITTED WITH TWO | | | SETS OF FLA COM CALCULATIONS IN EACH OF THE NEW BLUE | | | BINDER BOOKS. | | | ONE SET FOR METHOD A FOR WHOLE BUILDING COMPLIANCE AND | | | ONE SET OF METHOD B FOR RENOVATIONS/PRESCRIPTIVE | | | REQUIREMENTS. | | | PLEASE SEE PAGE TWO OF THE FLA COM CALCULATIONS. THIS | | | REQUIRES THE INPUT DATA REPORT TO BE SUBMITTED WITH | | | EACH OF THE FLA COM SUMMARY SHEETS COMPLIANCE REPORTS. | | | NO INPUT DATA REPORT SHEETS WERE SUBMITTED. THIS OFFICE | | | CAN NOT CONFIRM OR REVIEW FOR MINIMUM CODE COMPLIANCE. | | | | | | **METHOD B PRESCRIPTIVE FOR NEW BEING CHANGED OUT OR | | | INSTALLED MUST BE USED INSIDE THE EXISTING STORE AREAS. | | | 13-400.B.0.4. | | | PLEASE SEE 13-415.AB.5, 13-415.AB.5.1, 13-415.B.1 AND | | | APPENDIX B 4.1.1 FOR INTERIOR. | | | PLEASE SEE 13-415.AB.2.2 FOR EXTERIOR. | | | | | | **THE SUBMITTED METHOD *A* MAY BE USED FOR NEW | | | CONSTRUCTION OF WHOLE BUILDINGS, NEW ADDITIONS/AIR | | | CONDITIONED PORTIONS OF EXISTING BUILDINGS. | | | IN EITHER CASE WHEN USING METHOD *A* ALL PORTIONS AND | | | COMPONENTS OF THAT NEW AREA ARE REQUIRED TO BE ENTERED | | | INTO THE IDR FOR COMPLIANCE. | | | | | | ** I NOTICED IN ONE OF THE SUMMARY REPORTS THE USE OF * | | | LIGHTING DESIGNATED AS REQUIRED BY HEALTH OR LIFE | | | SAFETY STATUTE, ORDINANCE OR OTHER REGULATION. | | | THIS MAY NOT BE USED AS THERE ARE NO SUCH ADOPTED | | | ALLOWANCES FOR THE STORE LOCATION KNOWN TO THIS OFFICE. | | | | | | | | | 2) NOTE: SIDE NOTE, THIRD COPY IS A PHOTO-COPY OF | | | SIGNED AND SEALED COMPLIANCE REPORTS FOR METHOD *A*. | | | ONLY TWO COMPLETE SETS ARE NEEDED HOWEVER IF A THIRD | | | COPY IS NEEDED FOR YOUR RECORDS OR STAMPING THEN THE | | | SETS MUST BE ORIGINAL. | | | | | | 3) NOTE: NO LICENSED CONTRACTOR HAS APPLIED FOR PERMIT | | | AS OF YET. REVIEW TO REMAIN IN FAILED STATUS UNTIL | | | COMMENTS HAVE BEEN ADDRESSED AND LICENSED CONTRACTOR | | | CAN BE VERIFIED. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2009-12-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-12-16 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-12-15 |
Time |
14:22 |
Sent To |
|
|
| Notes |
| 2009-12-16 15:29:07 | | | | ** DENIED ** | | | | | | **** IMPORTANT** | | | 1) NOTE: AS NOTED PREVIOUSLY THE BREAKERS WHICH ARE IN | | | THE ELECTRICAL SERVICE EQUIPMENT WHICH ARE NOT RATED | | | FOR THE AVAILABLE FAULT CURRENT NEED TO BE CHANGED OUT. | | | THIS IS A FIRE AND LIFE SAFETY HAZARD. THIS OFFICE HAS | | | SEEN FAULTS ON ELECTRICAL SYSTEMS WHICH HAVE RESULTED | | | IN FIRE, INJURY AND LOSS OF LIFE. THESE CAN BE CHANGED | | | OUT UNDER A SEPARATE PERMIT BEFORE CONSTRUCTION BEGINS | | | FOR THE REMAINDER OF THE PROJECT. PLEASE SUBMIT PERMIT | | | APPLICATION AND SPECS/CUT SHEETS ON BREAKERS AND PERMIT | | | WILL BE DONE ON A TURN AROUND BASIS. NOTICE HAS BEEN | | | GIVEN IN PREVIOUS REVIEW AND NO PERMIT APPLICATION HAS | | | BEEN MADE TO RESOLVE SAFETY CONCERNS. THE NEXT STEP | | | WILL BE TO ISSUE CORRECTION NOTICE TO STORE LOCATION. | | | PLEASE OBTAIN PERMIT AND CHANGE OUT BREAKERS AS SOON AS | | | POSSIBLE. THE DISCONNECTION OF UTILITY SOURCE BASED ON | | | LIFE SAFETY CONCERNS IS POSSIBLE IF THIS IS NOT DONE IN | | | A TIMELY FASHION. PLEASE CALL TO GO OVER TO ALLEVIATE | | | ANY POSSIBLE DELAYS. NEC 110.9 | | | | | | 2) NOTE: AS GONE OVER WITH THE STRUCTURAL ENGINEER, | | | SHEET S6.3 CONTAINS THE OLD SEAL WITH THE WORDING | | | *CERTIFICATE* INSTEAD OF THE NEW SEAL. A NEW SHEET IS | | | TO BE REPLACED INTO SETS. | | | | | | 3) NOTE: THE SUBMITTED ENERGY CALCULATIONS ARE NOT ALL | | | ORIGINALS. IN FACT ONLY ONE SET SUBMITTED CONTAINS THE | | | ORIGINAL SIGNATURE AND SEAL OF DESIGN PROFESSIONALS. | | | THE OTHER TWO REQUIRED COPIES ARE ACTUALLY PHOTO-COPIES | | | OF THE SIGNED AND SEALED ORIGINALS. THE CERTIFICATION | | | SHEETS ARE ALL REQUIRED TO CONTAIN ORIGINAL SIGNATURE, | | | DATE AND SEAL. | | | FAC 61G15-23.002, FS471.025 | | | | | | 4) NOTE: THE SUBMITTED ENERGY PERFORMANCE CALCULATIONS | | | CONTAIN A SIGNATURE FROM THE PERSON WHO PREPARED | | | DOCUMENTS NOT AS ONE OF THE LICENSED DESIGN | | | PROFESSIONALS LISTED ON PROJECT. THE ONLY PERSON | | | PERMITTED TO PREPARE DOCUMENTS IS THAT LISTED AS THE | | | LICENSED DESIGN PROFESSIONAL AS REQUIRED UNDER FBC | | | 13-103.1, FS 471.005. FS 481.221, FAC 61G15-23.002. | | | | | | 5) NOTE: PREVIOUS REVIEW GAVE CODE SECTIONS FOR | | | REQUIRED LIGHTING CONTROLS. RESPONSE STATES THE CODE IS | | | MET HOWEVER BASED ON THE PLANS AND RESPONSE THERE IS | | | STILL SOME ITEMS WHICH NEED TO BE ADDRESSED. FBC | | | 13-415.AB1.1 FIRST REQUIRES *ALL* LIGHTING IN BUILDING | | | GREATER THAN 5K SQ FT TO BE AUTOMATICALLY CONTROLLED. | | | THE CODE DOES GIVE DIFFERENT WAYS IN DOING THIS AND | | | SOME EXCEPTIONS. HOWEVER THE INTENT OF THE ENERGY CODE | | | IS TO SAVE ENERGY BY TURNING OFF ALL LIGHTING. | | | | | | SECTION 13-415.AB.1.2 REQUIRES EACH SPACE TO HAVE ITS | | | OWN MANUAL CONTROL TO BE CAPABLE OF OVER RIDING ANY | | | TIME OF DAY SCHEDULING SYSTEM OR IT MAY BE A SEPARATE | | | CONTROL FOR SPACE SUCH AS TIMED OR OCCUPANCY SENSORS. | | | IN EITHER CASE THIS DOES NOT MEAN INDIVIDUAL MANUAL | | | CONTROL SUCH AS SINGLE POLE SWITCHES. | | | SUCH LOCATIONS WOULD BE THE JANITOR CLOSET, MEAT | | | COOLER, PRODUCE COOLER, MEAT PREP, UTILITY ROOM, | | | PHOTO-LAB AREA, ROTISSERIE PREP, AND BAKER FREEZER. | | | ** ALL SPACES. | | | | | | 6) NOTE: PREVIOUS REVIEW REQUESTED TO INDICATE WHETHER | | | OR NOT THE CONTINUOUS LOADS ARE ALREADY FIGURED AT | | | 125%. THE RESPONSE STATES SOME INFORMATION ABOUT THE | | | AIR CURTAIN FOR THE DOORS. THIS WAS NOT PART OF THE | | | ORIGINAL COMMENT. | | | PLEASE SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS LOADS | | | WHICH ARE REQUIRED TO BE SHOWN AND FIGURED AT 125%. | | | | | | 7) NOTE: COVER SHEET STATES A 2006 FLORIDA BUILDING | | | CODE. THIS COULD BE REDLINED ON PLANS. | | | | | | 8) NOTE: PLEASE SEE 13-415.AB.5, 13-415.AB.2.2 FOR | | | EXTERIOR PERFORMANCE CALCULATIONS FOR PRESCRIPTIVE | | | REQUIREMENTS. PLEASE EXPLAIN HOW THE INPUT DATA REPORT | | | CAN BE BLANK FOR EXTERIOR LIGHTING WHEN THERE IS NEW | | | LIGHTING BEING INSTALLED ON PLANS? | | | | | | ** COMMENTS: 1,2,3,4 AND 8 4 MUST BE ADDRESSED AT THIS | | | TIME. COMMENTS #5 AND 6 CAN BE DONE AS A PROVISO WHICH | | | WOULD ALLOW ISSUANCE OF PERMIT AND GIVE DESIGN TEAM | | | TIME TO REVISE PLANS WITHIN A SPECIFIED TIME FRAME. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-08-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-08-26 |
Time |
09:15 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-08-26 |
Time |
09:15 |
Sent To |
|
|
| Notes |
| 2009-08-26 09:15:45 | | | | ** DENIED REVIEW ** | | | | | | | | | | | | 1) NOTE: THE SEAL IN USE OF STRUCTURAL PLANS IS NO | | | LONGER VALID FOR USE IN THE STATE OF FLORIDA. PLEASE | | | SEE RULING UNDER FLORIDA ADMINISTRATIVE CODE | | | 61G15-23.001. THIS SECTION WAS REVISED IN FEBRUARY OF | | | 2004 THAT THE WORDING OF *CERTIFICATE* ON SAID SEAL IS | | | NO LONGER PERMITTED. THE NEW WORDING OF *LICENSE* WAS | | | REQUIRED. ALL SEALS WERE REQUIRED TO BE REVISED/NEW. AN | | | EXTENSION WAS GRANTED BY THE BOARD OF ENGINEERS TO THE | | | DATE OF DECEMBER 31ST 2005. HOWEVER AFTER THAT DATE THE | | | OLD SEALS COULD NOT LONGER BE USED. | | | THIS COMMENT IS REQUIRED WHETHER OR NOT COMMENT IS MADE | | | BY ANY OTHER TRADE. | | | | | | | | | 2) NOTE: THE SUBMITTED ENERGY CALCULATIONS ARE NOT CODE | | | COMPLIANT. | | | THE VERSION SUBMITTED IS FROM THE 2004 FLORIDA BUILDING | | | CODE. PLEASE KNOW THAT ALL PERMIT APPLICATIONS | | | SUBMITTED AFTER MARCH 1ST 2009 SHALL BE UNDER THE 2007 | | | FBC W/ 2009 REVISIONS. | | | PLEASE SEE 13-400.3.A, 13-400.3.B. | | | AS THIS IS NOT A WHOLE BUILDING PLEASE SEE | | | 13-400.0.B.4, 13-415.AB.5, 13-415.B.1 FOR LIGHTING | | | PERFORMANCE CALCULATIONS FOR PRESCRIPTIVE REQUIREMENTS. | | | | | | MAY NOT SUBMIT AND USE AND METHOD *A* WHOLE BUILDING | | | CALCULATION UNLESS IT IS A WHOLE BUILDING WITHIN THE | | | SCOPE. | | | PLEASE ALSO SEE THAT NO INPUT DATA REPORT WAS | | | SUBMITTED. IN ORDER TO VERIFY CODE COMPLIANCE FOR THE | | | INFORMATION ON PLANS COORDINATING WITH THE SUBMITTED | | | CALCULATIONS, THE INPUT DATA REPORT MUST ACCOMPANY THE | | | SUBMITTED SUMMARY SHEETS OF THE CALCULATIONS. | | | | | | ** IMPORTANT, PLEASE BE SURE ALL INFORMATION ON THE | | | IDR, IS COORDINATED WITH PLANS. | | | | | | ** IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | 3) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR STAIR EGRESS | | | AREAS. PLEASE SEE NFPA-101 7.8.1.3, 7.9.1.2 AND 7.9.2.2 | | | OF THE LIFE SAFETY CODE. REQUIRES A MINIMUM OF 10FT | | | CANDLES UNDER NORMAL AND IS PERMITTED TO GO DOWN TO 1FT | | | CANDLE UNDER EMERGENCY. THIS INCLUDES OUTSIDE EGRESS | | | STAIRS. | | | PLEASE SEE NFPA-70 700.12 FOR ACCEPTABLE BACK UP AND | | | CIRCUITING PER 700.12F. CHAPTER 10 OF THE FBC ALSO | | | GOVERNS EGRESS ILLUMINATION. | | | | | | 4) NOTE: ANY NEW LIGHTING CONTROLS ARE REQUIRED TO MEET | | | PRESCRIPTIVE REQUIREMENTS OF 13-415.AB.1.1,.1.2, .1.3 | | | AND .1.4. | | | EXAMPLE: INTERIOR JANITOR CLOSET INDICATING ONLY A | | | STANDARD WALL SWITCH. | | | EXAMPLE: OUTSIDE LIGHTS NEEDING TO MEET ONE OF TWO | | | MINIMUM REQUIRED METHODS. | | | EXAMPLE: RECEIVING AREA. WHERE ARE THE EXISTING | | | LIGHTING CONTROLS FOR SEPARATE SPACES? IF NEW, THEN | | | MUST MEET REQUIREMENTS FOR SEPARATE SPACES. IF NOT NEW | | | THEN PLEASE SHOW THE EXISTING. | | | EXAMPLE: MEAT COOLER, PRODUCE COOLER ETC. | | | | | | ** ALL LOCATIONS AND SEPARATE SPACES ARE REQUIRED TO | | | MEET MINIMUM PRESCRIPTIVE REQUIREMENTS FOR AUTOMATED | | | LIGHTING CONTROLS. | | | | | | 5) NOTE: SHEET E-2 STATES A NOTE #9 FOR A ROOM LOCATED | | | ON THE EAST SIDE OF THE BUILDING WHICH STATES * | | | REMODELED ELECTRICAL*. HOWEVER NO INFORMATION COULD BE | | | LOCATED. | | | ALL OF THE OTHER AREAS ARE NOTED TO OTHER SHEETS AND | | | ENLARGED DETAILS HOWEVER THIS ROOM/LOCATION COULD NOT | | | BE FOUND. | | | PLEASE EXPLAIN. | | | AS THE SCOPE IS NOT CLEAR IT IS NOT POSSIBLE TO REVIEW. | | | | | | 6) NOTE: PLEASE SEE 210.8B2 FOR THE 2005 NEC. ALL | | | 15/20AMP RECEPTACLES LOCATED IN KITCHEN AREAS SHALL BE | | | GFI/GFI PROTECTED. THIS IS REQUIRED WHETHER OR NOT | | | THESE ARE FEEDING COUNTER SPACES. | | | | | | 8) NOTE: PLEASE SHOW ALL CLASS AND DIVISION LOCATIONS | | | PER NEC 500. | | | | | | 9) NOTE: PLEASE INDICATE IF THE CONTINUOUS LOADS ARE | | | ALREADY FIGURED AT 125% ALONG WITH LARGEST MOTORS LOADS | | | OR CONTINUOUS MOTOR LOADS. | | | EXAMPLE: LIGHTING, STORAGE TYPE WATER HEATERS, ETC. | | | PLEASE ALSO PROVIDE INFORMATION ON AIR CURTAIN MOTORS. | | | ARE THESE CONTROLLED FOR OPERATION DURING THE DOOR | | | OPENING OR CONTINUOUS DURING THE HOURS OF STORE | | | OPERATION/OPEN HOURS? | | | 215.3, 230.42 | | | | | | 10) NOTE: THE NOTE ON RISER SHEET 16.R64 INDICATES | | | THERE IS AN ISSUE WITH THE RATING OF THE BREAKERS BEING | | | EXCEEDED BY THE AVAILABLE FAULT CURRENT. PLEASE VERIFY | | | THIS AT THIS TIME. PLEASE KNOW THAT IF THIS IS INDEED | | | THE CASE A SEPARATE ELECTRICAL PERMIT SHOULD BE APPLIED | | | FOR AS SOON AS POSSIBLE TO ADDRESS THIS ISSUE. MINIMUM | | | CODE COMPLIANCE FOR SAFETY OF THESE ISSUES INCLUDING | | | ANY FIRE HAZARDS NEEDS TO BE ADDRESSED. | | | 110.9. | | | | | | ** PERMIT HAS BEEN APPLIED FOR HOWEVER NOT BY ANY | | | LICENSED CONTRACTOR. PERMIT MAY NOT BE ISSUED UNTIL | | | LICENSED CONTRACTOR HAS APPLIED UNDER THIS PERMIT | | | NUMBER. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
5 |
Status |
F |
Date |
2010-08-30 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2010-08-30 |
Time |
14:24 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2010-08-30 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2010-08-30 14:37:10 | PLANS SUBMITTED DO NOT MATCH ENGINEERING SERVICES | | | SUBMITTAL. | | | SUBMIT MODIFICATION REVIEW WITH ENGINEERING SERVICES | | | WITH LATEST CHANGES. | | | | | | #1 DRAINAGE HAS CHANGED. | | | #2 ADDITIONAL SHEETS SUCH AS 6032 HAVE BEEN ADDED. | | | #3 REVISIONS ON SHEETS (FOR EXAMPLE 6030, 6050) ARE NOT | | | REFLECTED IN ENGINEERING APPROVED SET. | | | | | | PLEASE SUPPLY UPDATED SET TO ENGINEERING SERVICES | | | DEPARTMENT FOR REVIEW: | | | | | | MANUEL JULIAN GONZALEZ | | | CSD ENGINEERING REVIEW | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 1ST FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 644-7301 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
4 |
Status |
P |
Date |
2010-05-06 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2010-05-06 |
Time |
15:33 |
Rev Time |
0.50 |
| Received By |
mgonzale |
Date |
2010-05-06 |
Time |
15:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2010-03-25 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2010-03-25 |
Time |
11:03 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2010-03-25 |
Time |
11:03 |
Sent To |
|
|
| Notes |
| 2010-03-25 11:07:48 | PASSED WITH PROVISOS: | | | | | | #1 ENGINEERING SERVICES APPROVED PLANS DATED FEB 17, | | | 2010, ANY DEVIATION FROM THIS PLAN MUST BE SENT INTO | | | ENGINEERING SERVICES DEPARTMENT AS A REVISION. | | | #2 ALL REVISIONS MUST BE SENT TO ENGINEERING SERVICES | | | DEPARTMENT FOR APPROVAL PRIOR TO CONSTRUCTION. A | | | PRE-CONSTRUCTION CONFERENCE IS REQUIRED. | | | #3 NO LARGE ROOT BEARING TREES IN CITY OF WEST PALM | | | BEACH UTILITY EASEMENTS. ANY LANDSCAPOE IMPACT ON | | | UTILITY EASEMENT MUST BE SUBMITTED AS A REVISION. | | | | | | MANUEL JULIAN GONZALEZ | | | CSD ENGINEERING REVIEW | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 644-7301 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2010-01-05 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2010-01-05 |
Time |
13:53 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2010-01-05 |
Time |
13:49 |
Sent To |
|
|
| Notes |
| 2010-01-05 13:53:07 | *** ENGINEERING REVIEW FAILED *** | | | | | | PREVIOUS COMMENTS HAVE BEEN ADDRESSED THRU ESD. | | | | | | ITEM PENDING: MUST PROCESS A MINOR AMENDMENT PRIOR TO | | | FINAL REVIEW OF PERMIT. | | | | | | MANUEL JULIAN GONZALEZ | | | ENGINEERING REVIEW AT CSD | | | 401 CLEMATIS STREET | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2009-09-22 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2009-09-22 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2009-09-22 |
Time |
|
Sent To |
|
|
| Notes |
| 2009-09-22 12:29:21 | PLAN COMMENTS FROM ENGINEERING 09-08-09 - STATUS IS | | | FAILED | | | SOME OF THE ISSUES HAVE BEEN DISCUSSED VIA PHONE | | | CONVERSATIONS. | | | | | | #1 PROVIDE FFE EL OF SAM'S STORE AND MC DONALDS | | | #2 REMOVE DOOR CHART SCHEDULE ON TOPOGRAPHIC SHEET (NOT | | | NEEDED) | | | #3 PROVIDE WRITTEN EXPLANATION FOR DRAINAGE PORTION | | | (EXISTING DRAINAGE) WHICH DOES NOT FALL WITHIN | | | PROPERTY. | | | (IS THERE A DRAINAGE EASEMENT OR CROSS ACCESS EASEMENT? | | | ETC..) | | | #4 RETENTION POND NEXT TO SAM'S BUILDING IS FOR SAM'S | | | USE ONLY? | | | #5 SODDING NOTES NEED TO BE ON SHEET 6030, ITS PART OF | | | EROSION CONTROL. | | | #6 CHECK NEW SWALE IN THE BACK, IT MAY NEED A HAND RAIL | | | DUE TO THE SLOPES. | | | #7 FIRE SERVICE WILL STILL BE SUFFICIENT TO SERVE NEW | | | ADDITIONAL S.F. | | | #8 DOMESTICS SERVICE AND FIRE SERVICE BACKFLOWS MUST BE | | | TO UNIVERSITY OF SOUTHERN CALIFORNIA APPROVED LIST. | | | #9 PROVIDE DETAIL FOR A TYPE F DITCH BOTTOM INLET. | | | #10 SEWER CLEAN-OUT NEEDED EVERY 75' , SEE PLAN | | | #11 PROVIDE INVERT AT EXISTING SEWER LATERAL | | | #12 HYDRANT SHOWN ON-SITE OFF CITY'S WM NEEDS A DCDA | | | (SHT. 6060) | | | #13 SEWER FLOWS SOUTH TO LIFT STATION (SHT. 6060) | | | #14 S2 IS CALLING OUT MANHOLE WHEN IT SHOULD BE GREASE | | | INTERCEPTOR | | | #15 OUR STANDARD GREASE INTERCEPTOR IS NOT UP TO CODE. | | | PROVIDE SHOP DRAWING. | | | #16 S1 AND S2 CALL OUT SHEET XXXX, STATE SHEET NUMBER. | | | #17 WATER SERVICE MUST HAVE THE REQUIRED DEPT. PLEASE | | | CHECK GRADES AND DEPTH. 30" MIN DEPTH. | | | #18 LARGE TREES ALONG CITY'S UTILITY EASEMENT ARE NOT | | | ALLOWED. THERE IS WATER AND SEWER ALONG THESE | | | EASEMENTS. ROOT BARRIER WILL BE REQUIRED FOR ANY | | | VEGETATION ON THIS EASEMENT. | | | #19 ALL ACCESS OFF 45TH STREET MUST MEET ADA. | | | #20 SUPPLY COMMENTS FROM SFWMD AS ADVISED. | | | | | | COMMENTS SPECIFIC TO ENGINEERING HAVE BEEN REMOVED FROM | | | LIST. | | | | | | MANUEL JULIAN GONZALEZ | | | ENGINEERING PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 644-7301 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2010-03-25 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2010-03-25 |
Time |
17:13 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2010-03-25 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2010-03-25 18:28:43 | *****FIRE-STAMPING NEEDED***** | | | | | | THE APPROPIATE PLAN SHEETS ARE TO BE FIRE-STAMPED WHEN | | | A GENERAL CONTRACTOR HAS BEEN SIGNED/CONTRACTOR FOR THE | | | SCOPE OF WORK. | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2009-12-29 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-12-29 |
Time |
12:43 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-12-29 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2009-12-29 12:43:00 | *****FIRE-STAMPING NEEDED***** | | | | | | THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN | | | ADDRESSED OR ACKNOWLEDGED. HOWEVER, THE APPROPIATE PLAN | | | SHEETS ARE TO BE FIRE-STAMPED WHEN THE OTHER TRADES' | | | PLAN EXAMINERS COMMENTS AS WELL AS THE FOLLOWING | | | COMMENT HAS BEEN ADDRESSED: | | | | | | 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK | | | OF EACH SUBMITTED PLAN SHEET. | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2009-08-19 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2009-08-19 |
Time |
12:24 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2009-08-19 |
Time |
11:56 |
Sent To |
|
|
| Notes |
| 2009-08-19 12:23:54 | 1. MEZZANINE FLOOR AREA TOTAL ON PAGE CS DOES NOT | | | APPEAR CORRECT. THE TOTAL FLOOR AREA TOTAL AMOUNT MAY | | | ALSO BE INCORRECT. | | | | | | 2. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. | | | | | | 3. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS | | | FOR HANDRAILS AND GUARDRAILS. | | | | | | 4. DUST WALLS SHOWN ON PAGE D1 SHALL NOT CONSIST OF | | | NON-RATED VISQUEEN OT OTHER MATERIALS. PLEASE SEE NOTES | | | ON DUCT WALLS AND DRAPES ON PAGE D1.3. | | | | | | 5. IF GASOLINE POWERED SAWS ARE USED, PROPER | | | CONSIDERATION TO THE PRODUCTION AND ACCUMULATION OF | | | CARBON MONOXIDE (CO) . PROPER VENTILATION CONTROLS ARE | | | TO BE UTILIZED TO PREVENT THE PRODUCTION OF CARBON | | | MONOXIDE WHICH IS A COLORLESS, ODORLESS, AND IN THE | | | PROPER CONCENTRATION FLAMMABLE. | | | | | | 6. IF ANY REQUIRED FIRE PROTECTION SYSTEMS ARE OUT OF | | | SERVICE MORE THAN FOUR HOURS IN A TWENTY FOUR HOUR | | | PERIOD A FIRE WATCH WILL BE REQUIRED. ALL FIRE WATCHES | | | MUST BE APPROVED BY THE BATTALION CHIEF OR HIS DESIGNEE | | | AND ALL FIRE WATCHES REQUESTS MUST BE IN WRITING. | | | | | | 7. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE | | | SPRINKLER OR FIRE ALARM SYSTEM REMODELING. | | | | | | 8. NEW AUTOMATIC SLIDING DOORS ON PAGE A3 SHALL MEET | | | THE REQUIREMENTS FOR POWERED OPERATED DOORS. | | | | | | 9. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY NEW | | | HOOD, DUCT, AND FIRE SUPPRESSION SYSTEMS. | | | | | | 10. ALL FREEZERS AND COOLER SHALL BE PROTECTED WITH | | | FIRE SPRINKLER PROTECTION AS SHOWN ON THE SPRINKLER | | | PLANS. | | | | | | 11. NOTES ON PAGE 6025 MENTIONS THE JURISDICTION OF | | | PORT CHARLOTTE, FLORIDA. WRONG LOCATION. | | | | | | 12. PLEASE PROVIDE FLAME SPREAD REQUIREMENTS FOR NEW | | | CEILING TILES PLANNED FOR THE LOCATION. | | | | | | 13. ALL WORK IS SUBJECT TO FIELD INSPECTION AND | | | APPROVAL. | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2010-03-25 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2010-03-25 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2010-03-25 |
Time |
08:59 |
Sent To |
|
|
| Notes |
| 2010-03-25 10:40:25 | NOTE: | | | VALVE REQUIRED BEFORE ANY REGULATOR | | | FBC GAS 2007 409.4 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2009-12-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-12-16 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-12-15 |
Time |
17:53 |
Sent To |
|
|
| Notes |
| 2009-12-16 12:05:04 | DENIED | | | REFERENCE: FBC-2007 FUEL GAS | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | A. SHEETS M2 & M3.1 SHOW A GAS PIPING RISER DIAGRAM & A | | | GAS EQUIPMENT DETAIL. ALL NATURAL OR LP GAS INFIRMATION | | | SHALL BE SUBMITTED ON THE PLUMBING SHEETS AS IT IS IN | | | THE SCOPE OF WORK OF THE PLUMBING CONTRACTOR. A | | | SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING | | | INFORMATION IS REQUIRED FOR THE GAS PERMIT: | | | | | | 1. OK | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | ****RESPONSE NOTED, BUT THE PIPING MATERIAL WAS NOT | | | FOUND IN THE SPECIFICATION BOOK. NO SECTION 15190 WAS | | | INDICATED. | | | | | | 3. OK | | | 4. OK | | | 5. OK | | | 6. OK | | | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. -- IF 2 PSI SUBMIT | | | THE MANUF. SPECIFICATION SHEETS FOR THE REGULATORS. | | | ****RESPONSE NOTED, BUT SINCE THIS IS A 2 PSI SYSTEM, | | | THE REGULATORS SHALL BE INDICATED ON THE GAS ISOMETRIC | | | RISER DIAGRAM. ALSO THE LOCATION FOR EACH MANUFACTURE & | | | MODEL NUMBER SHALL BE INDICATED FOR EACH REGULATOR ON | | | THE ISOMETRIC TO VERIFY COMPLIANCE OF USAGE AT EACH | | | REGULATOR. THE MANUF SHEETS SHALL SHOW APPROVAL | | | LISTING. THIS IS NOT SHOWN OR INDICATED ON THE | | | REGULATOR SPEC SHEET. (P4, NOT M4 AS INDICATED IN THE | | | RESPONSE). | | | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2007 FUEL GAS CODE | | | SECS. 502 THRU 505 & RESIDENTIAL CODE SECS. G2426 THRU | | | G2429. | | | ****RESPONSE NOTED, BUT 4-M3.1DOES NOT INDICATE THE | | | INFORMATION REQUESTED IN COMMENT. PLEASE SHOW | | | INFORMATION REQUESTED. | | | | | | 9. OK | | | 10. N/A | | | 11. N/A | | | | | | 12. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. -- UNION NOT INDICATED. | | | ****RESPONSE NOTED, BUT UNION NOT SHOWN IN DETAIL | | | 3-MP1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2009-08-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-08-13 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-08-13 |
Time |
10:32 |
Sent To |
|
|
| Notes |
| 2009-08-13 10:41:45 | DENIED | | | REFERENCE: FBC-2007 FUEL GAS | | | | | | A. SHEETS M2 & M3.1 SHOW A GAS PIPING RISER DIAGRAM & A | | | GAS EQUIPMENT DETAIL. ALL NATURAL OR LP GAS INFIRMATION | | | SHALL BE SUBMITTED ON THE PLUMBING SHEETS AS IT IS IN | | | THE SCOPE OF WORK OF THE PLUMBING CONTRACTOR. A | | | SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING | | | INFORMATION IS REQUIRED FOR THE GAS PERMIT: | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR | | | 2007 FUEL GAS CODE. | | | | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE IF BEING USED. | | | | | | 3. TYPE OF GAS, (LP OR NATURAL). | | | | | | 4. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2007 FUEL GAS CODE SECS. 401.8 | | | THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(33) OR RESIDENTIAL CODE SECTIONS G2412.8 THRU | | | G2413.6.1 AND TABLES G2413.4(1) THRU 2413.4(8). | | | | | | 5. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2007 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | 6. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2007 FUEL | | | GAS CODE SECTION 304 & RESIDENTIAL CODE SECTION G2407. | | | | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. -- IF 2 PSI SUBMIT | | | THE MANUF. SPECIFICATION SHEETS FOR THE REGULATORS. | | | | | | 8. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2007 FUEL GAS CODE | | | SECS. 502 THRU 505 & RESIDENTIAL CODE SECS. G2426 THRU | | | G2429. | | | | | | 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE | | | SEC. G2413.2. | | | | | | 10. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | 11. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND | | | APPURTENANCES PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | 12. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. -- UNION NOT INDICATED. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2011-09-21 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2011-09-21 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2011-05-20 |
Time |
10:44 |
Sent To |
|
|
| Notes |
| 2011-05-20 10:44:33 | TO JW DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2010-04-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-04-21 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2010-04-21 |
Time |
11:45 |
Sent To |
|
|
| Notes |
| 2010-04-21 11:47:05 | 1 SET OF PLANS RESUBMITTED FROM IMPACT FEE ASSESSMENT | | | ROUTED TO C-31 BOX WITH OTHER PLAN. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2010-02-17 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2010-02-16 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2010-02-16 |
Time |
08:37 |
Sent To |
|
|
| Notes |
| 2010-02-17 08:49:20 | C--33,34 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-11-25 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2009-11-23 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2009-11-23 |
Time |
12:17 |
Sent To |
|
|
| Notes |
| 2009-11-25 12:17:52 | C--41 & 42 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2009-08-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-08-03 |
Time |
13:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2010-03-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2010-03-23 |
Time |
11:49 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2010-03-23 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2010-03-23 11:50:50 | | | | 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT | | | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL | | | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND | | | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE | | | INFORMATION. | | | | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
4 |
Status |
P |
Date |
2010-04-16 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2010-04-16 |
Time |
16:57 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2010-04-16 |
Time |
16:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
3 |
Status |
F |
Date |
2010-03-09 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2010-03-09 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2010-03-09 |
Time |
12:49 |
Sent To |
|
|
| Notes |
| 2010-03-09 13:20:19 | ***LANDSCAPE REVIEW FAILED*** | | | | | | PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT. | | | | | | 1. THERE ARE CONFLICTS BETWEEN VARIOUS UTILITIES AND | | | PROPOSED LANDSCAPING. A WATER MAIN RUNS DIRECTLY UNDER | | | PROPOSED TREES IN THE TERMINAL ISLANDS SOUTH OF THE | | | EXISTING WET POND. A CLEAN-OUT, 3" VENT AND OTHER ITEMS | | | ARE SHOWN IN THE FIRE LANE. THERE IS ALSO A WATER LINE | | | ALONG THE NORTH PERIMETER OF THE SITE IN CONFLICT WITH | | | SOME EXISTING AND PROPOSED TREES. | | | | | | 2. PURSUANT TO SECTION 94-442 (D), PRIVATE LAND AND | | | PUBLIC RIGHTS-OF-WAY BETWEEN STREET OR SIDEWALK | | | SURFACES AND REQUIRED BUFFER STRIPS AND LANDSCAPED OPEN | | | SPACE AREAS SHALL BE PLANTED WITH GRASS. GRASS AREAS | | | SHALL BE SODDED. MULCH HAS BEEN PROPOSED ALONG THE | | | SOUTH END OF THE PARKING LOT AND IN THE 5 X 5 FOOT | | | AREAS ALONG THE LANDSCAPE STRIPS THAT SEPARATE THE | | | PARKING ROWS. MULCH CANNOT BE A SUBSTITUTE FOR SOD. | | | GROUND COVER SHALL BE PLANTED IN THE 5 X 5 FOOT | | | LANDSCAPE AREAS (JUST OUTSIDE OF THE ROOTBALL OF THE | | | TREE) AND THE AREA ALONG THE SOUTH END OF THE PARKING | | | LOT SHALL BE SODDED. | | | | | | 3. STAFF STRONGLY RECOMMENDS THAT THE PALM GROUPINGS BE | | | UNDERPLANTED WITH SHRUBS AND GROUND COVER. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT | | | KUSSNER @ (561) 822-1462., |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
F |
Date |
2010-01-15 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2010-01-15 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2010-01-15 |
Time |
17:03 |
Sent To |
|
|
| Notes |
| 2010-01-15 17:04:59 | ***LANDSCAPE REVIEW FAILED*** | | | | | | MUST PROCESS A MINOR AMENDMENT PRIOR TO REVIEW OF | | | PERMIT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT | | | KUSSNER @ (561) 822-1462. |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
2009-08-13 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2009-08-13 |
Time |
17:27 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2009-08-13 |
Time |
17:27 |
Sent To |
|
|
| Notes |
| 2009-08-13 17:28:47 | ***LANDSCAPE REVIEW FAILED*** | | | | | | MUST PROCESS A MINOR AMENDMENT PRIOR TO REVIEW OF | | | PERMIT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT | | | KUSSNER @ (561) 822-1462. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2011-09-21 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2011-09-21 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2011-09-21 |
Time |
11:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2010-05-04 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2010-05-04 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2010-05-04 |
Time |
10:50 |
Sent To |
|
|
| Notes |
| 2010-05-04 10:51:46 | **PROVISO** | | | | | | PROVIDE MANUFACTURER'S WIND RESISTANCE DATA FOR ALL | | | OUTDOOR APPLIANCES AND EQUIPMENT WHICH IS EXPOSED TO | | | WIND IN ACCORDANCE WITH FBC-M 301.12. | | | | | | SEPARATE PLANS AND PERMIT APPLICATIONS REQUIRED FOR | | | KITCHEN HOODS, HOOD SUPPRESSION AND WALK-IN COOLERS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2010-03-26 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2010-03-26 |
Time |
12:02 |
Rev Time |
0.00 |
| Received By |
hmoser |
Date |
2010-03-26 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2010-03-26 12:37:19 | PLAN DENIED | | | COMMENTS # 3, FROM LAST REVIEW WAS NOT ADDRESSED , | | | COMMENT # 4 THE PRODUCT APPROVALS ARE FOR GREENHECK | | | FANS NOT PENNBARRY FANS ,COULD NOT FIND THE WIND | | | CALCULATIONS FOR THE RTU UNITS OR EXHAUST FANS . | | | COMMENT # 5 NOT ADDRESSED , | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2009-12-19 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-12-19 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-12-19 |
Time |
14:02 |
Sent To |
|
|
| Notes |
| 2009-12-19 14:43:01 | REVIEW #: 2ND | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS REVIEW COMMENTS FOR CONTINUITY: | | | | | | 1. OK | | | | | | 2. OK | | | | | | 3. **NOT ADDRESSED** NOTE 15.710 ON PG M2 CALLS FOR FAN | | | TO RUN CONTINUOUSLY DURING OPERATION, BUT THERE IS NO | | | INDICATION ON PLANS AS TO HOW THIS WILL BE | | | ACCOMPLISHED. ALSO, NOTE H ON PAGE M4 EF SCHEDULE CALLS | | | FOR INTERLOCK WITH MUA FANS. THIS IS A DIFFERENT | | | REQUIREMENT FROM THE INTERLOCK WITH COOKING APPLIANCES | | | AS REQUIRED PER FNC-M 507.2.1.1. KITHCEN HOOD EXHAUST | | | SYSTEM IS NO LONGER PART OF THIS REVIEW. PROVIDE | | | SEPARATE PLANS AND PERMIT APPLICATIONS FOR COMMERCIAL | | | KITCHEN HOOD EXHAUST SYSTEMS AND HOOD SUPPRESSION | | | SYSTEMS. | | | | | | 4. **NOT ADDRESSED** THE CUT SHEETS PROVIDED DO NOT | | | CONTAIN ANY INFORMATION FROM THE APPLIANCE | | | MANUFACTURERS REGARDING THE WIND RESISTANCE | | | CAPABILITIES OF THE APPLIANCES. PROVIDE MANUFACTURER'S | | | DATA SHOWING ALL OUTDOOR APPLIANCES (RTU, EF, | | | CONDESNER, ETC.) ARE DESIGNED FOR WIND RESISTANCE IN | | | ACCORDANCE WITH FBC-M 301.12. | | | | | | 5. ENERGY CALCULATIONS: UPDATED FORM 400B-08 WAS | | | PROVIDED, HOWEVER, THE CERTIFICATION PAGE IN THE CODE | | | COMPLIANCE FORM IS A PHOTOCOPY. PROVIDE ORIGINAL SIGNED | | | AND SEALED CODE COMPLIANCE FORMS IN ACCORDANCE WITH | | | FBC-B 13-103.2. ALSO, ENERGY CALCULATIONS DO NOT | | | INCLUDE THE NEW RTU 25. PLANS AND ENERGY CALCULATIONS | | | SHALL MATCH IN ACCORDANCE WITH 13-103.2. | | | | | | 6. **NOT ADDRESSED** NO COOLING LOAD CALCULATIONS COULD | | | BE FOUND IN THE SUBMITTED PACKAGE. COOLING LOAD | | | CALCULATIONS SHALL BE APENDED TO THE ENERGY CODE | | | COMPLIANCE FORM IN ACCORDANCE WITH FBC-B 13-407.AB.1. | | | | | | NOTE: SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | COMMERCIAL KITCHEN HOOD EXHAUSTSYSTEMS, HOOD | | | SUPPRESSION SYSTEMS, AND REMOTE REFRIGERATION SYSTEMS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2009-08-06 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-08-06 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-08-05 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2009-08-06 09:43:15 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. RETURN AIR TRANSFER GRILLS IN SOME AREAS ARE NOT | | | SIZED TO MEET THE EXCEPTIONS UNDER FBC-M 601.4. | | | EXAMPLES: DETAIL 1 (COMPUTER/COUNTDOWN/CASH ROOM AREAS) | | | AND DETAIL 9 (DEMO ROOM) ON PAGE M2. PLEASE CHECK ALL | | | RETURN AIR TRANFER GRILL SIZES FOR COMPLIANCE. | | | | | | 2. PAGE M2: DETAIL 1 SHOWS THE MANUAL PULL STATION FOR | | | THE HOOD SUPPRESSION SYSTEM IN EXCESS OF 20 FEET FROM | | | THE KITCHEN EXHAUST SYSTEM. ALSO, DETAIL 2 SHOWS A | | | MANUAL PULL STATION LESS THAN 10 FEET FROM THE KITCHEN | | | EXHAUST SYSTEM. THESE MANUAL ACTUATION DEVICES SHALL BE | | | LOCATED AT OR NEAR A MEANS OF EGRESS FROM THE COOKING | | | AREA A MINIMUM OF 10 FEET AND A MAXIMUM OF 20 FEET FROM | | | THE KITCHEN EXHAUST SYSTEM IN ACCORDANCE WITH FBC-B | | | 904.11.1. | | | | | | 3. PAGE M2: MECHANICAL KEYNOTE 15.722 CALLS FOR EXHAUST | | | FAN INTERLOCK WITH PIZZA OVEN OPERATION. INTERLOCK OF | | | EXHAUST FAN WITH ROTISSERIE OPERATION IS ALSO REQUIRED | | | IN ACCORDANCE WITH FBC-M 507.2.1.1. THE ACTIVATION OF | | | THE EXHAUST FAN SHALL OCCUR THROUGH AN INTERLOCK WITH | | | THE COOKING APPLIANCES, BY MEANS OF HEAT SENSORS OR BY | | | MEANS OF OTHER APPROVED METHODS. | | | | | | 4. PROVIDE MANUFACTURER'S DATA FOR THE WIND RESISTANT | | | CONSTRUCTION AND INSTALLATION OF ALL APPLIANCES EXPOSED | | | TO WIND SUCH AS: NEW RTUS, EXHAUST FANS, MUA FANS, | | | REMOTE CONDENSERS IN ACCORDANCE WITH FBC-M 301.12. | | | | | | 5. ENERGY CALCULATIONS: THIS JOB CONSTITUTES A | | | RENOVATION AS DEFINED IN FBC-B SECTION 13-202. AS SUCH, | | | THIS BUILDING SHALL COMPLY WITH METHOD B OF SUBCHAPTER | | | 13-4 FOR INSULATION, HVAC SYSTEMS, LIGHTING, WATER | | | HEATING SYSTEMS AND EXTERIOR ENVELOPE COMPONENTS BEING | | | RETROFITTED OR REPLACED IN ACCORDANCE WITH FBC-B | | | 13-101.1.3. SUBMIT A COMPLETED ENERGY CODE COMPLIANCE | | | FORM 400B-08 TO DEMONSTRATE COMPLIANCE WITH THIS | | | SECTION. THE FORM 400A-04R WHICH WAS SUBMITTED IS OUT | | | OF DATE AND NO LONGER VALID AS OF MARCH 1, 2009, THE | | | EFFECTIVE DATE OF THE 2007 FLORIDA BUILDING CODE. | | | | | | 6. A COOLING LOAD CALCULATION FOR ALL NEW AIR | | | CONDITIONING APPLIANCES BEING INSTALLED SHALL BE | | | ATTACHED TO THE ENERGY CODE COMPLIANCE FORM IN | | | ACCORDANCE WITH FBC-B SECTION 13-407.AB.1. | | | | | | NOTE: SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN | | | HOOD EXHAUST AND HOOD SUPPRESSION SYSTEMS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2009-12-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-12-15 |
Time |
17:45 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-12-15 |
Time |
17:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2009-08-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-08-13 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-08-13 |
Time |
10:32 |
Sent To |
|
|
| Notes |
| 2009-08-13 10:54:07 | DENIED | | | REFERENCE: | | | FBC-2007 PLUMBING | | | FBC-2007 CHAPTER 1 | | | | | | 1. INFORMATIONAL: SEPARATE PERMITS ARE REQUIRED FOR THE | | | TEMP. TOILET ROOM TRAILER & THE GREASE INTERCEPTORS. | | | SECTION 105.1. | | | | | | 2. SHTS SP2.1, P1 & P3.1 DETAIL #2 A 2-WAY CLEANOUT IS | | | REQUIRED ON THE INLET PIPING TO THE GREASE | | | INTERCEPTORS. (UTILITY STANDARD) | | | | | | 3. SHTS SP2 COMPACTOR PAN PLAN INDICATES A DRAIN & | | | SP2.1 DETAILS 2 & 3. PLEASE INDICATE IF THE COMPACTOR | | | WILL BE COVERED AS TO NOT ALLOW STORM WATER TO ENTER | | | THE DRAIN. THE DRAIN SHALL CONNECT TO THE GREASE | | | INTERCEPTOR. IF THE STORM WATER WILL DRAIN AT THE | | | COMPACTOR DRAIN, THEN THE DRAIN WILL HAVE TO BE | | | DELETED. PLEASE CLARIFY. SECTION 106.1.2 (MORE INFO | | | REQD). | | | | | | 4. SHT P2.1 DETAIL #1. SUBMIT CALCULATIONS FOR THE | | | STORM DRAINAGE. SHOW THE SQUARE FOOT AREA OF THE ROOF | | | PLUS 1/2 AREA OF ALL VERTICAL WALLS INCLUDING PARAPETS | | | ADDED TO THE SQUARE FOOTAGE OF THE ROOF & TOTAL SQUARE | | | FOOTAGE BEING DRAINED BY THE ROOF TABLE. TABLE 1106.3 & | | | SECTIONS 1106.3 & 1106.4. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2010-04-21 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2010-04-21 |
Time |
17:01 |
Rev Time |
1.50 |
| Received By |
lfranco |
Date |
2010-04-21 |
Time |
17:01 |
Sent To |
E |
|
| Notes |
| 2010-04-26 12:03:15 | PLANNING AND ZONING: PASSED WITH PROVISO - SHEET LS1, | | | PROPOSED MECHANICAL EQUIPMENT ON ROOFTOP SHALL BE | | | SCREENED FROM ALL SIDES. SHEET A3.1 DEPICTS A VERY LOW | | | PARAPET W/ NO DIMENSION OF THE TOP OF ROOF OR CROSS | | | SECTION OF HOW HIGH THE MECHANICAL EQUIPMENT WILL BE. | | | REVISE PLANS ACCORDINGLY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2010-03-10 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2010-03-10 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2010-03-10 |
Time |
14:22 |
Sent To |
B |
|
| Notes |
| 2010-03-10 14:34:42 | PLANNING AND ZONING **** FAILED **** | | | | | | 1. RESPOND TO COMMENTS IN WRITING. | | | | | | 2. LANDSCAPE COMMENTS ARE OUTSTANDING. SEE LANDSCAPE | | | COMMENTS FOR DETAILS. | | | | | | IF YOU HAVE ANY QUESTIONS, CONTACT ME. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2009-12-21 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2009-12-21 |
Time |
12:06 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2009-12-21 |
Time |
12:06 |
Sent To |
|
|
| Notes |
| 2009-12-21 12:07:15 | PLANNING AND ZONING: ***** FAILED**** | | | | | | 1. RESPOND TO COMMENTS IN WRITING. | | | | | | 2. REPEAT COMMENT: THE PROPOSED WORK IS WITHIN THE | | | SAM'S CLUB PROJECT THAT IS PART OF THE NORTH TRAIL | | | COMMERCIAL PLANNED DEVELOPMENT ("CPD") . THE PROPOSED | | | AMENDMENTS ARE CURRENTLY BEING REVIEWED FOR A MINOR PD | | | AMENDMENT WITH THE PLANNING AND ZONING DEPARTMENT. | | | THEREFORE, THIS PERMIT CANNOT BE APPROVED UNTIL FINAL | | | APPROVAL OF THE MINOR AMENDMENT HAS BEEN MADE BY THE | | | PLANNING AND ZONING DEPARTMENT, DUE TO PERTINENT | | | CHANGES/REVISIONS THAT MAY BE REQUIRED, WHICH WILL NEED | | | TO BE REFLECTED ON THIS PERMIT. | | | | | | ANY WORK PERFORMED WITHOUT FIRST OBTAINING THE MINOR | | | AMENDMENT AND BUILDING PERMIT APPROVAL SHALL BE THE | | | FULL RESPONSIBILITY OF THE OWNER TO RECTIFY AND | | | CORRECT, SHOULD IT BE REQUIRED THROUGH OUR REVIEW | | | PROCESS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2009-08-13 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2009-08-13 |
Time |
17:15 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2009-08-13 |
Time |
17:15 |
Sent To |
|
|
| Notes |
| 2009-08-13 17:21:51 | PLANNING AND ZONING: ***** FAILED**** | | | | | | 1. RESPOND TO COMMENTS IN WRITING. | | | | | | 2. THE PROPOSED WORK IS WITHIN THE SAM'S CLUB PROJECT | | | THAT IS PART OF THE NORTH TRAIL COMMERCIAL PLANNED | | | DEVELOPMENT ("CPD") . THE PROPOSED AMENDMENTS ARE | | | CURRENTLY BEING REVIEWED FOR A MINOR PD AMENDMENT WITH | | | THE PLANNING AND ZONING DEPARTMENT. THEREFORE, THIS | | | PERMIT CANNOT BE APPROVED UNTIL FINAL APPROVAL OF THE | | | MINOR AMENDMENT HAS BEEN MADE BY THE PLANNING AND | | | ZONING DEPARTMENT, DUE TO PERTINENT CHANGES/REVISIONS | | | THAT MAY BE REQUIRED, WHICH WILL NEED TO BE REFLECTED | | | ON THIS PERMIT. | | | | | | ANY WORK PERFORMED WITHOUT FIRST OBTAINING THE MINOR | | | AMENDMENT AND BUILDING PERMIT APPROVAL SHALL BE THE | | | FULL RESPONSIBILITY OF THE OWNER TO RECTIFY AND | | | CORRECT, SHOULD IT BE REQUIRED THROUGH OUR REVIEW | | | PROCESS. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | EMAIL: [email protected] | | | | | | | | | |
|
|