Plan Review Details - Permit 09070775
Plan Review Stops For Permit 09070775
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2011-05-25 Cont ID  
Sent By jwitmer Date 2011-05-25 Time 09:35 Rev Time 0.00
Received By jwitmer Date 2011-05-25 Time 09:35 Sent To  
Notes
2011-05-25 09:36:02BAR JOIST CALCULATIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2010-07-28 Cont ID  
Sent By jwitmer Date 2010-07-28 Time 15:03 Rev Time 0.75
Received By jwitmer Date 2010-07-28 Time 15:03 Sent To  
Notes
2010-07-28 15:04:58BUILDING PLAN REVIEW
 PERMIT: 09070775
 ADD: 4295 45TH ST
 CONT: TO BE DETERMINED
 TEL: (561)856-6655 NEYITA LEIVA
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 JULY 28/ 2010
  
  
  
 1 PROVISO: ADDITION IS LOCATED WITHIN A FLOODZONE A8 AT
 WITH A REQUIRED ELEVATION OF 15.5 FT NGVD, FBC BUILDING
 3110.1.2 / CITY OF WPB CODE OF ORDINANCES SECTION
 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A
 FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED ONCE THE
 FLOOR SLAB HAS BEEN POURED.
  
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISION, DOCUMENTS
 THAT ARE BEING PROVISOED, WILL REQUIRE ADDITIONAL
 REVIEWS WITH ASSOCIATED FEES.
  
  
 2) BUILDING PROVISO:FL BLD CODE 1609.6.2.2 COMPONENTS &
 CLADDING, PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT
 INSPECTOR OF PRODUCT TESTING REPORTS, MISSING REPORTS
 ARE AS FOLLOWS:
 A-F) COMPLIED.
 G) ROOFING ASSEMBLIES INCLUDING ROOF INSULATION-
 SUBMITTED WAS CARLISLE ROOF DECK NOA 08-0108.09
 NO SUB-SYSTEM WAS HIGHLIGHTED, ALL SYSTEMSWILL REQUIRE
 ENHANCED FASTENING.
  
 9-16-2010
 PAGE 14 JOIST LIMITATION OF 6'-0" OK DISMISS COMMENT
 BELOW
 PAGE 17- STEEL DECK SYSTEM LIMITATION, NOTE# 2 INDICATE
 BAR JOIST SPACING A MAXIMUM OF 5'-0". BAR JOIST J1 & J2
 ARE APPROXIMATELY 5'-10" C/C AND BAR JOIST J4 ARE
 APPROXIMATELY 5'-6" C/C/. WILL REQUIRE A DIFFERENT
 SYSTEM.
  
 H) ROOF TOP PENBARRY ALUMINUM FANS NOA: 09-1015.03
 +/-V50 PSF FANS ARE LOCATED IN ZONES 2 AAND ZONE 3 OF
 ROOF WITH DRAMATICLLY HIGHER PRESSURES.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2010-04-21 Cont ID  
Sent By jwitmer Date 2010-04-21 Time 11:48 Rev Time 1.55
Received By jwitmer Date 2010-04-21 Time 11:48 Sent To  
Notes
2010-04-21 11:59:55BUILDING PLAN REVIEW
 PERMIT: 09070775
 ADD: 4295 45TH ST
 CONT: TO BE DETERMINED
 TEL: (561)856-6655 NEYITA LEIVA
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 APRIL 21/ 2010
  
 ACTION: DENIED
  
 ONCE TTHE CONTRACTOR HAS SIGNED ON, LICENSURE CAN BE
 VERIFIED AND PERMIT VALUATION IS VERIFIED THEN A PASS
 CAN BE ENTERED.
  
 1-4) COMPLIED.
  
 5) PROVISO: ADDITION IS LOCATED WITHIN A FLOODZONE A8
 AT WITH A REQUIRED ELEVATION OF 15.5 FT NGVD, FBC
 BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED
 ONCE THE FLOOR SLAB HAS BEEN POURED.
  
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISION, DOCUMENTS
 THAT ARE BEING PROVISOED, WILL REQUIRE ADDITIONAL
 REVIEWS WITH ASSOCIATED FEES.
  
  
 6) BUILDING PROVISO:FL BLD CODE 1609.6.2.2 COMPONENTS &
 CLADDING, PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT
 INSPECTOR OF PRODUCT TESTING REPORTS, MISSING REPORTS
 ARE AS FOLLOWS:
 A-F) COMPLIED.
 G) ROOFING ASSEMBLIES INCLUDING ROOF INSULATION-
 SUBMITTED WAS CARLISLE ROOF DECK NOA 08-0108.09
 NO SUB-SYSTEM WAS HIGHLIGHTED, ALL SYSTEMSWILL REQUIRE
 ENHANCED FASTENING.
 PAGE 17- STEEL DECK SYSTEM LIMITATION, NOTE# 2 INDICATE
 BAR JOIST SPACING A MAXIMUM OF 5'-0". BAR JOIST J1 & J2
 ARE APPROXIMATELY 5'-10" C/C AND BAR JOIST J4 ARE
 APPROXIMATELY 5'-6" C/C/. WILL REQUIRE A DIFFERENT
 SYSTEM.
  
 H) ROOF TOP PENBARRY ALUMINUM FANS NOA: 09-1015.03
 +/-V50 PSF FANS ARE LOCATED IN ZONES 2 AAND ZONE 3 OF
 ROOF WITH DRAMATICLLY HIGHER PRESSURES.
  
 7-9) COMPLIED.
  
 10) IMPACT FEES PAID PR# 2010-0419-215
 11) COMPLIED.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2010-03-23 Cont ID  
Sent By jwitmer Date 2010-03-23 Time 11:24 Rev Time 4.00
Received By jwitmer Date 2010-03-23 Time 11:24 Sent To  
Notes
2010-03-23 11:35:45BUILDING PLAN REVIEW
 PERMIT: 09070775
 ADD: 4295 45TH ST
 CONT: TO BE DETERMINED
 TEL: (561)856-6655 NEYITA LEIVA
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 MARCH 23/ 2010
 3RD REVIEW
 ACTION: DENIED
  
 1) COMPLIED.
  
 2-4) COMPLIED.
  
 5) PROVISO: ADDITION IS LOCATED WITHIN A FLOODZONE A8
 AT WITH A REQUIRED ELEVATION OF 15.5 FT NGVD, FBC
 BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED
 ONCE THE FLOOR SLAB HAS BEEN POURED.
  
 6) BUILDING PROVISO:FL BLD CODE 1609.6.2.2 COMPONENTS &
 CLADDING, PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT
 INSPECTOR OF PRODUCT TESTING REPORTS, MISSING REPORTS
 ARE AS FOLLOWS:
 A-F) COMPLIED.
 G) ROOFING ASSEMBLIES INCLUDING ROOF INSULATION-
 SUBMITTED WAS CARLISLE ROOF DECK NOA 08-0108.09
 NO SUB-SYSTEM WAS HIGHLIGHTED, ALL SYSTEMSWOULD REQUIRE
 ENHANCED FASTENING.
 PAGE 17- STEEL DECK SYSTEM LIMITATION, NOTE# 2 INDICATE
 BAR JOIST SPACING A MAXIMUM OF 5'-0". BAR JOIST J1 & J2
 ARE APPROXIMATELY 5'-10" C/C AND BAR JOIST J4 ARE
 APPROXIMATELY 5'-6" C/C/. WILL REQUIRE A DIFFERENT
 SYSTEM.
  
 H) ROOF TOP PENBARRY ALUMINUM FANS NOA: 09-1015.03
 +/-V50 PSF FANS ARE LOCATED IN ZONES 2 AAND ZONE 3 OF
 ROOF WITH DRAMATICLLY HIGHER PRESSURES.
  
 7-9) COMPLIED.
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 11) COMPLIED.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-12-28 Cont ID  
Sent By jwitmer Date 2009-12-28 Time 11:25 Rev Time 2.22
Received By jwitmer Date 2009-12-28 Time 11:24 Sent To  
Notes
2009-12-28 13:27:39BUILDING PLAN REVIEW
 PERMIT: 09070775
 ADD: 4295 45TH ST
 CONT: TO BE DETERMINED
 TEL: (561)856-6655 NEYITA LEIVA
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 DEC. 28/ 2009
 2ND REVIEW
 ACTION: DENIED
  
 1) COMPLIED.
  
 2) SUBMITTED ENERGY CALCS FORM 400B-2008. THIS FORM
 PLEASE SEE BOTH THE ELECTRICAL AND MECHANICAL COMMENTS
 ON THE REQUIRED SIGNATURE AND SEAL REQUIREMENTS.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 3-4) COMPLIED.
  
 5) PROVISO: ADDITION IS LOCATED WITHIN A FLOODZONE A8
 AT WITH A REQUIRED ELEVATION OF 15.5 FT NGVD, FBC
 BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
  
 6) PLEASE NOTE THAT PRODUCT APPROVALS WILL NOT BE
 REQUIRED AT TIME OF PERMITTING BUT WILL BE REQUIRED FOR
 FULL REVIEW.
  
 BUILDING PROVISO:FL BLD CODE 1609.6.2.2 COMPONENTS &
 CLADDING, PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT
 INSPECTOR OF PRODUCT TESTING REPORTS, MISSING REPORTS
 ARE AS FOLLOWS:
 A) EXTERIOR GLAZED WINDOWS
 B) MULLION
 C) EXTERIOR GLAZED DOORS, AUTOMATIC SLIDDING GLASS
 DOORS W/ TRANSOM
 D) OVERHEAD DOORS
 E) WALL LOUVERS
 F) EFIS SYSTEMS
 G) ROOFING ASSEMBLIES INCLUDING ROOF INSULATION
 H) PERMANUFACTURED A/C STANDS
  
 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) PARTIAL APPROVAL, ENGINEERING CALCULATIONS WERE
 SUBMITTED FOR THE ATTACHMENT OF THE CURB TO ROOF
 FRAMING MEMBERS WIWTH A CLIP SYSTEM, PRODUCED BY ICR
 ENGINEERING, INC. THE CALCULATIONS ARE NOT SIGNED NOR
 SEALED NOR DO THEY PROVIDE A SIGNED AND SEALED COVER
 SHEET.
  
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 61G15-23.002(2) FL. ADMIN. CODE. A COVER SHEET OR INDEX
 SHEET FOR ENGINEERING SPECIFICATIONS MAY BE USED AND
 THAT SHEET MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE
 PRODUCTION & PREPARATION OF EACH SECTION OF THE
 ENGINEERING SPECIFICATION WITH SUFFICIENT INFORMATION
 ON THE COVER SHEET OR INDEX.
  
 A3.3 PLEASE NOTE THAT ROOF TOP MECHANICAL EQUIPMENT
 MUST MEET THE WIND REQUIREMENTS IN CHAPTER 16 OF FBC.
 301.13 FBC MECHANICAL. WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST WIND
 PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING. NOTE THE STRUCTURAL SHEETS INDICATE THE
 CURB ATTACHMENTS TO THE ROOF DECK BUT NOT THE UNIT TO
 THE ROOF CURB.
  
 2ND REQUEST, FOR ALL ROOFTOP EQUIPMENT PLEASE PROVIDE
 EITHER BY TESTING, CALCULATIONS OR RATIONAL ANYLSIS THE
 EXTERIOR ELEMENTS (CABINETS)OF THE ROOF TOP EQUIPMENT
 ARE DESIGNED TO WITHSTAND THE WIND REQUIREMENTS OF
 CHAPTER 16 OF THE FLORIDA BUILDING CODE BUILDING AS
 REQUIRED BY SECTION 301.13 FBC MECHANICAL CODE.
  
 8) COMPLIED.
  
 9) 2ND REQUESST, PLANS INDICATE THE USE OF WALK IN
 COOLERS ( AGA1) PLEASE PROVIDE DOCUMENTATION THAT THE
 THERMA- STRUCTURE COOLERS COMPLIES WITH SECTION
 2603.4.1.2 (1-4). SUBMITTALS FOR FREZZER CASES WERE
 FOUND BUT NOT FOR THE WALK IN COOLERS.2603.4.1.2 COOLER
 AND FREEZER WALLS. FOAM PLASTIC INSTALLED IN A MAXIMUM
 THICKNESS OF 10 INCHES (254 MM) IN COOLER AND FREEZER
 WALLS SHALL:
  
 1. HAVE A FLAME SPREAD INDEX OF 25 OR LESS AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450, WHERE
 TESTED IN A MINIMUM 4 INCH (102 MM) THICKNESS.
  
 2. HAVE FLASH IGNITION AND SELF-IGNITION TEMPERATURES
 OF NOT LESS THAN 600??F AND 800??F (316??C AND 427??C),
 RESPECTIVELY.
  
 3. HAVE A COVERING OF NOT LESS THAN 0.032-INCH (0.8 MM)
 ALUMINUM OR CORROSION-RESISTANT STEEL HAVING A BASE
 METAL THICKNESS NOT LESS THAN 0.0160 INCH (0.4 MM) AT
 ANY POINT.
  
 4. BE PROTECTED BY AN AUTOMATIC SPRINKLER SYSTEM. WHERE
 THE COOLER OR FREEZER IS WITHIN A BUILDING, BOTH THE
 COOLER OR FREEZER AND THAT PART OF THE BUILDING IN
 WHICH IT IS LOCATED SHALL BE SPRINKLERED.
  
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 11) NEW COMMENT SHEET S6.3 PLEASE SEE FBC* 106.1 THE
 NEW TYPE OF ENGINEER'S SEAL IS REQUIRED FOR ALL PLANS
 SEALED AFTER 12/31/05. ENGINEER'S SEALS INCLUDING THE
 WORD "CERTIFICATE" ARE NO LONGER VALID. ON 2/5/04 THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS AMENDED THE
 'SEALS' RULE AND REQUIRED THAT ALL MEMBERS OBTAIN SEALS
 WITH THE WORD "LICENSE" INSTEAD OF "CERTIFICATE". THE
 EXTENDED GRACE PERIOD FOR COMPLIANCE ENDED ON 12/31/05.
 (REF: 471.025 F.S. AND RULE 61G15-23.001 F.A.C.)
  
 RULE 61G15-23.001(1) F.A.C. THE FLORIDA BOARD OF
 PROFESSIONAL ENGINEERS HAS CLEANED UP THE APPEARANCE
 OF THE SEAL BY ELIMINATING OBSOLETE CONTENT AND
 CHANGING THE WORD "CERTIFICATE" TO "LICENSE". A GRACE
 PERIOD RAN THROUGH DEC. 31,2005.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-08-11 Cont ID  
Sent By jwitmer Date 2009-08-11 Time 16:32 Rev Time 5.60
Received By jwitmer Date 2009-08-11 Time 14:00 Sent To  
Notes
2009-08-11 16:52:52BUILDING PLAN REVIEW
 PERMIT: 09070775
 ADD: 4295 45TH ST
 CONT: TO BE DETERMINED
 TEL: (561)856-6655 NEYITA LEIVA
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 AUGUST 11/2009
 1ST REVIEW
 ACTION: DENIED
  
 1A) COVER SHEET/ CODES: PLANS SUBMITTED FOR PERMIT
 (FIRST TIME REVIEW) AFTER MARCH 1ST, 2009 SHALL BE
 REVIEWED TO THE 2007 FBC BUILDING WITH 2009
 SUPPLEMENTS.
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 1B) COVER SHEET/ CODES: PLANS INDICATE THE HANDICAPPED
 ACCESSIBILITY GUIDELINES AS AMERICANS WITH DISSIBILITY
 GUIDELINES PLEASE SEE FLORIDA'S BUILDING CODE , CHAPTER
 11 WHICH NOT ONLY ADOPTED THE ADAG BUT IS MORE
 RESTRICTIVE AND WERE ADOPTED BY THE DEPARTMENT OF
 JUSTICE.
  
 2) SUBMITTED WAS THE 2004 ENERGY CALCS FORM 400A-2004R.
 THIS FORM IS NO LONGER IN EFFECT. WHEN THE 2007 FBC
 CAME INTO EFFECT THIS FORM WAS NULL IN VOID. PLEASE
 REVIEW AND USE FORM 400B-08, THIS IS FOR COMMERCIAL
 RENOVASIONS.
  
 3) SHEET S0:
  
 3A) SECTION # 5 DEALS WITH FOUNDATIONS PLEASE PROVIDE
 THE SOILS REPORT PREPARED BY ECS OF FLORIDA LLC, JULY
 9/ 2009. 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 3B) SECTION # 2 & 6 BOTH MAKE REFRENECE TO THE IBC
 SPECIAL INSPECTION SECTION 1704, PLEASE REVIEW THIS
 SECTION WAS NOT ADOPTED INTO THE FLORIDA BUILDING CODE,
 BUILDING.
  
 4) THE COVERSHEET INDICATES SQUARE FOOTAGE BY OCCUPANCY
 BUT NOT BY EXISTING AND ADDITIONAL SQ. FOOTAGE BEING
 ADDED AS AN ADDITION. 106.1.2. ADDITIONAL INFORMATION
 REQUIRED.
  
 5) ADDITION IS LOCATED WITHIN A FLOODZONE A8 AT WITH A
 REQUIRED ELEVATION OF 15.5 FT NGVD, FBC BUILDING
 3110.1.2 / CITY OF WPB CODE OF ORDINANCES SECTION
 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A
 FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
  
 6) PLEASE NOTE THAT PRODUCT APPROVALS WILL NOT BE
 REQUIRED AT TIME OF PERMITTING BUT WILL BE REQUIRED FOR
 FULL REVIEW.
  
 BUILDING PROVISO:FL BLD CODE 1609.6.2.2 COMPONENTS &
 CLADDING, PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT
 INSPECTOR OF PRODUCT TESTING REPORTS, MISSING REPORTS
 ARE AS FOLLOWS:
 A) EXTERIOR GLAZED WINDOWS
 B) MULLION
 C) EXTERIOR GLAZED DOORS, AUTOMATIC SLIDDING GLASS
 DOORS W/ TRANSOM
 D) OVERHEAD DOORS
 E) WALL LOUVERS
 F) EFIS SYSTEMS
 G) ROOFING ASSEMBLIES INCLUDING ROOF INSULATION
 H) PERMANUFACTURED A/C STANDS
  
 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) A3.3 PLEASE NOTE THAT ROOF TOP MECHANICAL EQUIPMENT
 MUSST MEET THE WIND REQUIREMENTS IN CHAPTER 16 OF FBC.
 301.13 FBC MECHANICAL. WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST WIND
 PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING. NOTE THE STRUCTURAL SHEETS INDICATE THE
 CURB ATTACHMENTS TO THE ROOF DECK BUT NOT THE UNIT TO
 THE ROOF CURB.
  
 8) A3.4 PLEASE SEE A3.4 EXTERIOR WALL SECTION INDICATE
 1/2 INCH CD PLYWOOD ON WALLS. PLEASE SEE SECTION
 603.1(1.1)AND (1.2) FOR WHERE FIRE RETARDANT TREATED
 ELEMENTS CAN BE INSTALLED.
  
 9) PLANS INDICATE THE USE OF WALK IN COOLERS PLEASE
 PROVIDE DOCUMENTATION THAT THE THERMA- STRUCTURE
 COOLERS COMPLIES WITH SECTION 2603.4.1.2 (1-4).
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2010-04-28 Cont ID  
Sent By btrobaug Date 2010-04-28 Time 10:39 Rev Time 0.00
Received By btrobaug Date 2010-04-28 Time 09:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2010-02-25 Cont ID  
Sent By dpalmer Date 2010-02-25 Time 17:00 Rev Time 0.00
Received By dpalmer Date 2010-02-25 Time 17:00 Sent To  
Notes
2010-02-25 17:00:34** DENIED **
  
  
 1) NOTE: THERE ARE THREE NEW BOOKS SUBMITTED WITH TWO
 SETS OF FLA COM CALCULATIONS IN EACH OF THE NEW BLUE
 BINDER BOOKS.
 ONE SET FOR METHOD A FOR WHOLE BUILDING COMPLIANCE AND
 ONE SET OF METHOD B FOR RENOVATIONS/PRESCRIPTIVE
 REQUIREMENTS.
 PLEASE SEE PAGE TWO OF THE FLA COM CALCULATIONS. THIS
 REQUIRES THE INPUT DATA REPORT TO BE SUBMITTED WITH
 EACH OF THE FLA COM SUMMARY SHEETS COMPLIANCE REPORTS.
 NO INPUT DATA REPORT SHEETS WERE SUBMITTED. THIS OFFICE
 CAN NOT CONFIRM OR REVIEW FOR MINIMUM CODE COMPLIANCE.
  
 **METHOD B PRESCRIPTIVE FOR NEW BEING CHANGED OUT OR
 INSTALLED MUST BE USED INSIDE THE EXISTING STORE AREAS.
 13-400.B.0.4.
 PLEASE SEE 13-415.AB.5, 13-415.AB.5.1, 13-415.B.1 AND
 APPENDIX B 4.1.1 FOR INTERIOR.
 PLEASE SEE 13-415.AB.2.2 FOR EXTERIOR.
  
 **THE SUBMITTED METHOD *A* MAY BE USED FOR NEW
 CONSTRUCTION OF WHOLE BUILDINGS, NEW ADDITIONS/AIR
 CONDITIONED PORTIONS OF EXISTING BUILDINGS.
 IN EITHER CASE WHEN USING METHOD *A* ALL PORTIONS AND
 COMPONENTS OF THAT NEW AREA ARE REQUIRED TO BE ENTERED
 INTO THE IDR FOR COMPLIANCE.
  
 ** I NOTICED IN ONE OF THE SUMMARY REPORTS THE USE OF *
 LIGHTING DESIGNATED AS REQUIRED BY HEALTH OR LIFE
 SAFETY STATUTE, ORDINANCE OR OTHER REGULATION.
 THIS MAY NOT BE USED AS THERE ARE NO SUCH ADOPTED
 ALLOWANCES FOR THE STORE LOCATION KNOWN TO THIS OFFICE.
  
  
 2) NOTE: SIDE NOTE, THIRD COPY IS A PHOTO-COPY OF
 SIGNED AND SEALED COMPLIANCE REPORTS FOR METHOD *A*.
 ONLY TWO COMPLETE SETS ARE NEEDED HOWEVER IF A THIRD
 COPY IS NEEDED FOR YOUR RECORDS OR STAMPING THEN THE
 SETS MUST BE ORIGINAL.
  
 3) NOTE: NO LICENSED CONTRACTOR HAS APPLIED FOR PERMIT
 AS OF YET. REVIEW TO REMAIN IN FAILED STATUS UNTIL
 COMMENTS HAVE BEEN ADDRESSED AND LICENSED CONTRACTOR
 CAN BE VERIFIED.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-12-16 Cont ID  
Sent By dpalmer Date 2009-12-16 Time 15:28 Rev Time 0.00
Received By dpalmer Date 2009-12-15 Time 14:22 Sent To  
Notes
2009-12-16 15:29:07 
 ** DENIED **
  
 **** IMPORTANT**
 1) NOTE: AS NOTED PREVIOUSLY THE BREAKERS WHICH ARE IN
 THE ELECTRICAL SERVICE EQUIPMENT WHICH ARE NOT RATED
 FOR THE AVAILABLE FAULT CURRENT NEED TO BE CHANGED OUT.
 THIS IS A FIRE AND LIFE SAFETY HAZARD. THIS OFFICE HAS
 SEEN FAULTS ON ELECTRICAL SYSTEMS WHICH HAVE RESULTED
 IN FIRE, INJURY AND LOSS OF LIFE. THESE CAN BE CHANGED
 OUT UNDER A SEPARATE PERMIT BEFORE CONSTRUCTION BEGINS
 FOR THE REMAINDER OF THE PROJECT. PLEASE SUBMIT PERMIT
 APPLICATION AND SPECS/CUT SHEETS ON BREAKERS AND PERMIT
 WILL BE DONE ON A TURN AROUND BASIS. NOTICE HAS BEEN
 GIVEN IN PREVIOUS REVIEW AND NO PERMIT APPLICATION HAS
 BEEN MADE TO RESOLVE SAFETY CONCERNS. THE NEXT STEP
 WILL BE TO ISSUE CORRECTION NOTICE TO STORE LOCATION.
 PLEASE OBTAIN PERMIT AND CHANGE OUT BREAKERS AS SOON AS
 POSSIBLE. THE DISCONNECTION OF UTILITY SOURCE BASED ON
 LIFE SAFETY CONCERNS IS POSSIBLE IF THIS IS NOT DONE IN
 A TIMELY FASHION. PLEASE CALL TO GO OVER TO ALLEVIATE
 ANY POSSIBLE DELAYS. NEC 110.9
  
 2) NOTE: AS GONE OVER WITH THE STRUCTURAL ENGINEER,
 SHEET S6.3 CONTAINS THE OLD SEAL WITH THE WORDING
 *CERTIFICATE* INSTEAD OF THE NEW SEAL. A NEW SHEET IS
 TO BE REPLACED INTO SETS.
  
 3) NOTE: THE SUBMITTED ENERGY CALCULATIONS ARE NOT ALL
 ORIGINALS. IN FACT ONLY ONE SET SUBMITTED CONTAINS THE
 ORIGINAL SIGNATURE AND SEAL OF DESIGN PROFESSIONALS.
 THE OTHER TWO REQUIRED COPIES ARE ACTUALLY PHOTO-COPIES
 OF THE SIGNED AND SEALED ORIGINALS. THE CERTIFICATION
 SHEETS ARE ALL REQUIRED TO CONTAIN ORIGINAL SIGNATURE,
 DATE AND SEAL.
 FAC 61G15-23.002, FS471.025
  
 4) NOTE: THE SUBMITTED ENERGY PERFORMANCE CALCULATIONS
 CONTAIN A SIGNATURE FROM THE PERSON WHO PREPARED
 DOCUMENTS NOT AS ONE OF THE LICENSED DESIGN
 PROFESSIONALS LISTED ON PROJECT. THE ONLY PERSON
 PERMITTED TO PREPARE DOCUMENTS IS THAT LISTED AS THE
 LICENSED DESIGN PROFESSIONAL AS REQUIRED UNDER FBC
 13-103.1, FS 471.005. FS 481.221, FAC 61G15-23.002.
  
 5) NOTE: PREVIOUS REVIEW GAVE CODE SECTIONS FOR
 REQUIRED LIGHTING CONTROLS. RESPONSE STATES THE CODE IS
 MET HOWEVER BASED ON THE PLANS AND RESPONSE THERE IS
 STILL SOME ITEMS WHICH NEED TO BE ADDRESSED. FBC
 13-415.AB1.1 FIRST REQUIRES *ALL* LIGHTING IN BUILDING
 GREATER THAN 5K SQ FT TO BE AUTOMATICALLY CONTROLLED.
 THE CODE DOES GIVE DIFFERENT WAYS IN DOING THIS AND
 SOME EXCEPTIONS. HOWEVER THE INTENT OF THE ENERGY CODE
 IS TO SAVE ENERGY BY TURNING OFF ALL LIGHTING.
  
 SECTION 13-415.AB.1.2 REQUIRES EACH SPACE TO HAVE ITS
 OWN MANUAL CONTROL TO BE CAPABLE OF OVER RIDING ANY
 TIME OF DAY SCHEDULING SYSTEM OR IT MAY BE A SEPARATE
 CONTROL FOR SPACE SUCH AS TIMED OR OCCUPANCY SENSORS.
 IN EITHER CASE THIS DOES NOT MEAN INDIVIDUAL MANUAL
 CONTROL SUCH AS SINGLE POLE SWITCHES.
 SUCH LOCATIONS WOULD BE THE JANITOR CLOSET, MEAT
 COOLER, PRODUCE COOLER, MEAT PREP, UTILITY ROOM,
 PHOTO-LAB AREA, ROTISSERIE PREP, AND BAKER FREEZER.
 ** ALL SPACES.
  
 6) NOTE: PREVIOUS REVIEW REQUESTED TO INDICATE WHETHER
 OR NOT THE CONTINUOUS LOADS ARE ALREADY FIGURED AT
 125%. THE RESPONSE STATES SOME INFORMATION ABOUT THE
 AIR CURTAIN FOR THE DOORS. THIS WAS NOT PART OF THE
 ORIGINAL COMMENT.
 PLEASE SEE 215.3, 230.42 ETC FOR ALL CONTINUOUS LOADS
 WHICH ARE REQUIRED TO BE SHOWN AND FIGURED AT 125%.
  
 7) NOTE: COVER SHEET STATES A 2006 FLORIDA BUILDING
 CODE. THIS COULD BE REDLINED ON PLANS.
  
 8) NOTE: PLEASE SEE 13-415.AB.5, 13-415.AB.2.2 FOR
 EXTERIOR PERFORMANCE CALCULATIONS FOR PRESCRIPTIVE
 REQUIREMENTS. PLEASE EXPLAIN HOW THE INPUT DATA REPORT
 CAN BE BLANK FOR EXTERIOR LIGHTING WHEN THERE IS NEW
 LIGHTING BEING INSTALLED ON PLANS?
  
 ** COMMENTS: 1,2,3,4 AND 8 4 MUST BE ADDRESSED AT THIS
 TIME. COMMENTS #5 AND 6 CAN BE DONE AS A PROVISO WHICH
 WOULD ALLOW ISSUANCE OF PERMIT AND GIVE DESIGN TEAM
 TIME TO REVISE PLANS WITHIN A SPECIFIED TIME FRAME.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-08-26 Cont ID  
Sent By dpalmer Date 2009-08-26 Time 09:15 Rev Time 0.00
Received By dpalmer Date 2009-08-26 Time 09:15 Sent To  
Notes
2009-08-26 09:15:45 
 ** DENIED REVIEW **
  
  
  
 1) NOTE: THE SEAL IN USE OF STRUCTURAL PLANS IS NO
 LONGER VALID FOR USE IN THE STATE OF FLORIDA. PLEASE
 SEE RULING UNDER FLORIDA ADMINISTRATIVE CODE
 61G15-23.001. THIS SECTION WAS REVISED IN FEBRUARY OF
 2004 THAT THE WORDING OF *CERTIFICATE* ON SAID SEAL IS
 NO LONGER PERMITTED. THE NEW WORDING OF *LICENSE* WAS
 REQUIRED. ALL SEALS WERE REQUIRED TO BE REVISED/NEW. AN
 EXTENSION WAS GRANTED BY THE BOARD OF ENGINEERS TO THE
 DATE OF DECEMBER 31ST 2005. HOWEVER AFTER THAT DATE THE
 OLD SEALS COULD NOT LONGER BE USED.
 THIS COMMENT IS REQUIRED WHETHER OR NOT COMMENT IS MADE
 BY ANY OTHER TRADE.
  
  
 2) NOTE: THE SUBMITTED ENERGY CALCULATIONS ARE NOT CODE
 COMPLIANT.
 THE VERSION SUBMITTED IS FROM THE 2004 FLORIDA BUILDING
 CODE. PLEASE KNOW THAT ALL PERMIT APPLICATIONS
 SUBMITTED AFTER MARCH 1ST 2009 SHALL BE UNDER THE 2007
 FBC W/ 2009 REVISIONS.
 PLEASE SEE 13-400.3.A, 13-400.3.B.
 AS THIS IS NOT A WHOLE BUILDING PLEASE SEE
 13-400.0.B.4, 13-415.AB.5, 13-415.B.1 FOR LIGHTING
 PERFORMANCE CALCULATIONS FOR PRESCRIPTIVE REQUIREMENTS.
  
 MAY NOT SUBMIT AND USE AND METHOD *A* WHOLE BUILDING
 CALCULATION UNLESS IT IS A WHOLE BUILDING WITHIN THE
 SCOPE.
 PLEASE ALSO SEE THAT NO INPUT DATA REPORT WAS
 SUBMITTED. IN ORDER TO VERIFY CODE COMPLIANCE FOR THE
 INFORMATION ON PLANS COORDINATING WITH THE SUBMITTED
 CALCULATIONS, THE INPUT DATA REPORT MUST ACCOMPANY THE
 SUBMITTED SUMMARY SHEETS OF THE CALCULATIONS.
  
 ** IMPORTANT, PLEASE BE SURE ALL INFORMATION ON THE
 IDR, IS COORDINATED WITH PLANS.
  
 ** IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 3) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR STAIR EGRESS
 AREAS. PLEASE SEE NFPA-101 7.8.1.3, 7.9.1.2 AND 7.9.2.2
 OF THE LIFE SAFETY CODE. REQUIRES A MINIMUM OF 10FT
 CANDLES UNDER NORMAL AND IS PERMITTED TO GO DOWN TO 1FT
 CANDLE UNDER EMERGENCY. THIS INCLUDES OUTSIDE EGRESS
 STAIRS.
 PLEASE SEE NFPA-70 700.12 FOR ACCEPTABLE BACK UP AND
 CIRCUITING PER 700.12F. CHAPTER 10 OF THE FBC ALSO
 GOVERNS EGRESS ILLUMINATION.
  
 4) NOTE: ANY NEW LIGHTING CONTROLS ARE REQUIRED TO MEET
 PRESCRIPTIVE REQUIREMENTS OF 13-415.AB.1.1,.1.2, .1.3
 AND .1.4.
 EXAMPLE: INTERIOR JANITOR CLOSET INDICATING ONLY A
 STANDARD WALL SWITCH.
 EXAMPLE: OUTSIDE LIGHTS NEEDING TO MEET ONE OF TWO
 MINIMUM REQUIRED METHODS.
 EXAMPLE: RECEIVING AREA. WHERE ARE THE EXISTING
 LIGHTING CONTROLS FOR SEPARATE SPACES? IF NEW, THEN
 MUST MEET REQUIREMENTS FOR SEPARATE SPACES. IF NOT NEW
 THEN PLEASE SHOW THE EXISTING.
 EXAMPLE: MEAT COOLER, PRODUCE COOLER ETC.
  
 ** ALL LOCATIONS AND SEPARATE SPACES ARE REQUIRED TO
 MEET MINIMUM PRESCRIPTIVE REQUIREMENTS FOR AUTOMATED
 LIGHTING CONTROLS.
  
 5) NOTE: SHEET E-2 STATES A NOTE #9 FOR A ROOM LOCATED
 ON THE EAST SIDE OF THE BUILDING WHICH STATES *
 REMODELED ELECTRICAL*. HOWEVER NO INFORMATION COULD BE
 LOCATED.
 ALL OF THE OTHER AREAS ARE NOTED TO OTHER SHEETS AND
 ENLARGED DETAILS HOWEVER THIS ROOM/LOCATION COULD NOT
 BE FOUND.
 PLEASE EXPLAIN.
 AS THE SCOPE IS NOT CLEAR IT IS NOT POSSIBLE TO REVIEW.
  
 6) NOTE: PLEASE SEE 210.8B2 FOR THE 2005 NEC. ALL
 15/20AMP RECEPTACLES LOCATED IN KITCHEN AREAS SHALL BE
 GFI/GFI PROTECTED. THIS IS REQUIRED WHETHER OR NOT
 THESE ARE FEEDING COUNTER SPACES.
  
 8) NOTE: PLEASE SHOW ALL CLASS AND DIVISION LOCATIONS
 PER NEC 500.
  
 9) NOTE: PLEASE INDICATE IF THE CONTINUOUS LOADS ARE
 ALREADY FIGURED AT 125% ALONG WITH LARGEST MOTORS LOADS
 OR CONTINUOUS MOTOR LOADS.
 EXAMPLE: LIGHTING, STORAGE TYPE WATER HEATERS, ETC.
 PLEASE ALSO PROVIDE INFORMATION ON AIR CURTAIN MOTORS.
 ARE THESE CONTROLLED FOR OPERATION DURING THE DOOR
 OPENING OR CONTINUOUS DURING THE HOURS OF STORE
 OPERATION/OPEN HOURS?
 215.3, 230.42
  
 10) NOTE: THE NOTE ON RISER SHEET 16.R64 INDICATES
 THERE IS AN ISSUE WITH THE RATING OF THE BREAKERS BEING
 EXCEEDED BY THE AVAILABLE FAULT CURRENT. PLEASE VERIFY
 THIS AT THIS TIME. PLEASE KNOW THAT IF THIS IS INDEED
 THE CASE A SEPARATE ELECTRICAL PERMIT SHOULD BE APPLIED
 FOR AS SOON AS POSSIBLE TO ADDRESS THIS ISSUE. MINIMUM
 CODE COMPLIANCE FOR SAFETY OF THESE ISSUES INCLUDING
 ANY FIRE HAZARDS NEEDS TO BE ADDRESSED.
 110.9.
  
 ** PERMIT HAS BEEN APPLIED FOR HOWEVER NOT BY ANY
 LICENSED CONTRACTOR. PERMIT MAY NOT BE ISSUED UNTIL
 LICENSED CONTRACTOR HAS APPLIED UNDER THIS PERMIT
 NUMBER.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 5 Status F Date 2010-08-30 Cont ID  
Sent By mgonzale Date 2010-08-30 Time 14:24 Rev Time 1.00
Received By mgonzale Date 2010-08-30 Time 14:24 Sent To  
Notes
2010-08-30 14:37:10PLANS SUBMITTED DO NOT MATCH ENGINEERING SERVICES
 SUBMITTAL.
 SUBMIT MODIFICATION REVIEW WITH ENGINEERING SERVICES
 WITH LATEST CHANGES.
  
 #1 DRAINAGE HAS CHANGED.
 #2 ADDITIONAL SHEETS SUCH AS 6032 HAVE BEEN ADDED.
 #3 REVISIONS ON SHEETS (FOR EXAMPLE 6030, 6050) ARE NOT
 REFLECTED IN ENGINEERING APPROVED SET.
  
 PLEASE SUPPLY UPDATED SET TO ENGINEERING SERVICES
 DEPARTMENT FOR REVIEW:
  
 MANUEL JULIAN GONZALEZ
 CSD ENGINEERING REVIEW
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2010-05-06 Cont ID  
Sent By mgonzale Date 2010-05-06 Time 15:33 Rev Time 0.50
Received By mgonzale Date 2010-05-06 Time 15:33 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2010-03-25 Cont ID  
Sent By mgonzale Date 2010-03-25 Time 11:03 Rev Time 1.00
Received By mgonzale Date 2010-03-25 Time 11:03 Sent To  
Notes
2010-03-25 11:07:48PASSED WITH PROVISOS:
  
 #1 ENGINEERING SERVICES APPROVED PLANS DATED FEB 17,
 2010, ANY DEVIATION FROM THIS PLAN MUST BE SENT INTO
 ENGINEERING SERVICES DEPARTMENT AS A REVISION.
 #2 ALL REVISIONS MUST BE SENT TO ENGINEERING SERVICES
 DEPARTMENT FOR APPROVAL PRIOR TO CONSTRUCTION. A
 PRE-CONSTRUCTION CONFERENCE IS REQUIRED.
 #3 NO LARGE ROOT BEARING TREES IN CITY OF WEST PALM
 BEACH UTILITY EASEMENTS. ANY LANDSCAPOE IMPACT ON
 UTILITY EASEMENT MUST BE SUBMITTED AS A REVISION.
  
 MANUEL JULIAN GONZALEZ
 CSD ENGINEERING REVIEW
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2010-01-05 Cont ID  
Sent By mgonzale Date 2010-01-05 Time 13:53 Rev Time 1.00
Received By mgonzale Date 2010-01-05 Time 13:49 Sent To  
Notes
2010-01-05 13:53:07*** ENGINEERING REVIEW FAILED ***
  
 PREVIOUS COMMENTS HAVE BEEN ADDRESSED THRU ESD.
  
 ITEM PENDING: MUST PROCESS A MINOR AMENDMENT PRIOR TO
 FINAL REVIEW OF PERMIT.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING REVIEW AT CSD
 401 CLEMATIS STREET
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2009-09-22 Cont ID  
Sent By mgonzale Date 2009-09-22 Time   Rev Time 1.00
Received By mgonzale Date 2009-09-22 Time   Sent To  
Notes
2009-09-22 12:29:21PLAN COMMENTS FROM ENGINEERING 09-08-09 - STATUS IS
 FAILED
 SOME OF THE ISSUES HAVE BEEN DISCUSSED VIA PHONE
 CONVERSATIONS.
  
 #1 PROVIDE FFE EL OF SAM'S STORE AND MC DONALDS
 #2 REMOVE DOOR CHART SCHEDULE ON TOPOGRAPHIC SHEET (NOT
 NEEDED)
 #3 PROVIDE WRITTEN EXPLANATION FOR DRAINAGE PORTION
 (EXISTING DRAINAGE) WHICH DOES NOT FALL WITHIN
 PROPERTY.
 (IS THERE A DRAINAGE EASEMENT OR CROSS ACCESS EASEMENT?
 ETC..)
 #4 RETENTION POND NEXT TO SAM'S BUILDING IS FOR SAM'S
 USE ONLY?
 #5 SODDING NOTES NEED TO BE ON SHEET 6030, ITS PART OF
 EROSION CONTROL.
 #6 CHECK NEW SWALE IN THE BACK, IT MAY NEED A HAND RAIL
 DUE TO THE SLOPES.
 #7 FIRE SERVICE WILL STILL BE SUFFICIENT TO SERVE NEW
 ADDITIONAL S.F.
 #8 DOMESTICS SERVICE AND FIRE SERVICE BACKFLOWS MUST BE
 TO UNIVERSITY OF SOUTHERN CALIFORNIA APPROVED LIST.
 #9 PROVIDE DETAIL FOR A TYPE F DITCH BOTTOM INLET.
 #10 SEWER CLEAN-OUT NEEDED EVERY 75' , SEE PLAN
 #11 PROVIDE INVERT AT EXISTING SEWER LATERAL
 #12 HYDRANT SHOWN ON-SITE OFF CITY'S WM NEEDS A DCDA
 (SHT. 6060)
 #13 SEWER FLOWS SOUTH TO LIFT STATION (SHT. 6060)
 #14 S2 IS CALLING OUT MANHOLE WHEN IT SHOULD BE GREASE
 INTERCEPTOR
 #15 OUR STANDARD GREASE INTERCEPTOR IS NOT UP TO CODE.
 PROVIDE SHOP DRAWING.
 #16 S1 AND S2 CALL OUT SHEET XXXX, STATE SHEET NUMBER.
 #17 WATER SERVICE MUST HAVE THE REQUIRED DEPT. PLEASE
 CHECK GRADES AND DEPTH. 30" MIN DEPTH.
 #18 LARGE TREES ALONG CITY'S UTILITY EASEMENT ARE NOT
 ALLOWED. THERE IS WATER AND SEWER ALONG THESE
 EASEMENTS. ROOT BARRIER WILL BE REQUIRED FOR ANY
 VEGETATION ON THIS EASEMENT.
 #19 ALL ACCESS OFF 45TH STREET MUST MEET ADA.
 #20 SUPPLY COMMENTS FROM SFWMD AS ADVISED.
  
 COMMENTS SPECIFIC TO ENGINEERING HAVE BEEN REMOVED FROM
 LIST.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2010-03-25 Cont ID  
Sent By mawillia Date 2010-03-25 Time 17:13 Rev Time 0.00
Received By mawillia Date 2010-03-25 Time 16:23 Sent To  
Notes
2010-03-25 18:28:43*****FIRE-STAMPING NEEDED*****
  
 THE APPROPIATE PLAN SHEETS ARE TO BE FIRE-STAMPED WHEN
 A GENERAL CONTRACTOR HAS BEEN SIGNED/CONTRACTOR FOR THE
 SCOPE OF WORK.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2009-12-29 Cont ID  
Sent By mawillia Date 2009-12-29 Time 12:43 Rev Time 0.00
Received By mawillia Date 2009-12-29 Time 11:19 Sent To  
Notes
2009-12-29 12:43:00*****FIRE-STAMPING NEEDED*****
  
 THE COMMENTS FROM THE PREVIOUS REVIEW HAVE BEEN
 ADDRESSED OR ACKNOWLEDGED. HOWEVER, THE APPROPIATE PLAN
 SHEETS ARE TO BE FIRE-STAMPED WHEN THE OTHER TRADES'
 PLAN EXAMINERS COMMENTS AS WELL AS THE FOLLOWING
 COMMENT HAS BEEN ADDRESSED:
  
 1. THE PROJECT SITE ADDRESS SHALL BE IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-08-19 Cont ID  
Sent By mcarsill Date 2009-08-19 Time 12:24 Rev Time 0.00
Received By mcarsill Date 2009-08-19 Time 11:56 Sent To  
Notes
2009-08-19 12:23:541. MEZZANINE FLOOR AREA TOTAL ON PAGE CS DOES NOT
 APPEAR CORRECT. THE TOTAL FLOOR AREA TOTAL AMOUNT MAY
 ALSO BE INCORRECT.
  
 2. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 3. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR HANDRAILS AND GUARDRAILS.
  
 4. DUST WALLS SHOWN ON PAGE D1 SHALL NOT CONSIST OF
 NON-RATED VISQUEEN OT OTHER MATERIALS. PLEASE SEE NOTES
 ON DUCT WALLS AND DRAPES ON PAGE D1.3.
  
 5. IF GASOLINE POWERED SAWS ARE USED, PROPER
 CONSIDERATION TO THE PRODUCTION AND ACCUMULATION OF
 CARBON MONOXIDE (CO) . PROPER VENTILATION CONTROLS ARE
 TO BE UTILIZED TO PREVENT THE PRODUCTION OF CARBON
 MONOXIDE WHICH IS A COLORLESS, ODORLESS, AND IN THE
 PROPER CONCENTRATION FLAMMABLE.
  
 6. IF ANY REQUIRED FIRE PROTECTION SYSTEMS ARE OUT OF
 SERVICE MORE THAN FOUR HOURS IN A TWENTY FOUR HOUR
 PERIOD A FIRE WATCH WILL BE REQUIRED. ALL FIRE WATCHES
 MUST BE APPROVED BY THE BATTALION CHIEF OR HIS DESIGNEE
 AND ALL FIRE WATCHES REQUESTS MUST BE IN WRITING.
  
 7. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE
 SPRINKLER OR FIRE ALARM SYSTEM REMODELING.
  
 8. NEW AUTOMATIC SLIDING DOORS ON PAGE A3 SHALL MEET
 THE REQUIREMENTS FOR POWERED OPERATED DOORS.
  
 9. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY NEW
 HOOD, DUCT, AND FIRE SUPPRESSION SYSTEMS.
  
 10. ALL FREEZERS AND COOLER SHALL BE PROTECTED WITH
 FIRE SPRINKLER PROTECTION AS SHOWN ON THE SPRINKLER
 PLANS.
  
 11. NOTES ON PAGE 6025 MENTIONS THE JURISDICTION OF
 PORT CHARLOTTE, FLORIDA. WRONG LOCATION.
  
 12. PLEASE PROVIDE FLAME SPREAD REQUIREMENTS FOR NEW
 CEILING TILES PLANNED FOR THE LOCATION.
  
 13. ALL WORK IS SUBJECT TO FIELD INSPECTION AND
 APPROVAL.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2010-03-25 Cont ID  
Sent By lwagner Date 2010-03-25 Time 10:38 Rev Time 0.00
Received By lwagner Date 2010-03-25 Time 08:59 Sent To  
Notes
2010-03-25 10:40:25NOTE:
 VALVE REQUIRED BEFORE ANY REGULATOR
 FBC GAS 2007 409.4

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2009-12-16 Cont ID  
Sent By kstevens Date 2009-12-16 Time 11:42 Rev Time 0.00
Received By kstevens Date 2009-12-15 Time 17:53 Sent To  
Notes
2009-12-16 12:05:04DENIED
 REFERENCE: FBC-2007 FUEL GAS
  
 ****FROM PREVIOUS REVIEW:
  
 A. SHEETS M2 & M3.1 SHOW A GAS PIPING RISER DIAGRAM & A
 GAS EQUIPMENT DETAIL. ALL NATURAL OR LP GAS INFIRMATION
 SHALL BE SUBMITTED ON THE PLUMBING SHEETS AS IT IS IN
 THE SCOPE OF WORK OF THE PLUMBING CONTRACTOR. A
 SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS PERMIT:
  
 1. OK
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
 ****RESPONSE NOTED, BUT THE PIPING MATERIAL WAS NOT
 FOUND IN THE SPECIFICATION BOOK. NO SECTION 15190 WAS
 INDICATED.
  
 3. OK
 4. OK
 5. OK
 6. OK
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. -- IF 2 PSI SUBMIT
 THE MANUF. SPECIFICATION SHEETS FOR THE REGULATORS.
 ****RESPONSE NOTED, BUT SINCE THIS IS A 2 PSI SYSTEM,
 THE REGULATORS SHALL BE INDICATED ON THE GAS ISOMETRIC
 RISER DIAGRAM. ALSO THE LOCATION FOR EACH MANUFACTURE &
 MODEL NUMBER SHALL BE INDICATED FOR EACH REGULATOR ON
 THE ISOMETRIC TO VERIFY COMPLIANCE OF USAGE AT EACH
 REGULATOR. THE MANUF SHEETS SHALL SHOW APPROVAL
 LISTING. THIS IS NOT SHOWN OR INDICATED ON THE
 REGULATOR SPEC SHEET. (P4, NOT M4 AS INDICATED IN THE
 RESPONSE).
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2007 FUEL GAS CODE
 SECS. 502 THRU 505 & RESIDENTIAL CODE SECS. G2426 THRU
 G2429.
 ****RESPONSE NOTED, BUT 4-M3.1DOES NOT INDICATE THE
 INFORMATION REQUESTED IN COMMENT. PLEASE SHOW
 INFORMATION REQUESTED.
  
 9. OK
 10. N/A
 11. N/A
  
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. -- UNION NOT INDICATED.
 ****RESPONSE NOTED, BUT UNION NOT SHOWN IN DETAIL
 3-MP1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-08-13 Cont ID  
Sent By kstevens Date 2009-08-13 Time 10:32 Rev Time 0.00
Received By kstevens Date 2009-08-13 Time 10:32 Sent To  
Notes
2009-08-13 10:41:45DENIED
 REFERENCE: FBC-2007 FUEL GAS
  
 A. SHEETS M2 & M3.1 SHOW A GAS PIPING RISER DIAGRAM & A
 GAS EQUIPMENT DETAIL. ALL NATURAL OR LP GAS INFIRMATION
 SHALL BE SUBMITTED ON THE PLUMBING SHEETS AS IT IS IN
 THE SCOPE OF WORK OF THE PLUMBING CONTRACTOR. A
 SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED FOR THE GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR
 2007 FUEL GAS CODE.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 3. TYPE OF GAS, (LP OR NATURAL).
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2007 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33) OR RESIDENTIAL CODE SECTIONS G2412.8 THRU
 G2413.6.1 AND TABLES G2413.4(1) THRU 2413.4(8).
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2007 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 6. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2007 FUEL
 GAS CODE SECTION 304 & RESIDENTIAL CODE SECTION G2407.
  
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI. -- IF 2 PSI SUBMIT
 THE MANUF. SPECIFICATION SHEETS FOR THE REGULATORS.
  
 8. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2007 FUEL GAS CODE
 SECS. 502 THRU 505 & RESIDENTIAL CODE SECS. G2426 THRU
 G2429.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE
 SEC. G2413.2.
  
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 12. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. -- UNION NOT INDICATED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2011-09-21 Cont ID  
Sent By hmoser Date 2011-09-21 Time 11:46 Rev Time 0.00
Received By hmoser Date 2011-05-20 Time 10:44 Sent To  
Notes
2011-05-20 10:44:33TO JW DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2010-04-21 Cont ID  
Sent By jwitmer Date 2010-04-21 Time 11:45 Rev Time 0.00
Received By jwitmer Date 2010-04-21 Time 11:45 Sent To  
Notes
2010-04-21 11:47:051 SET OF PLANS RESUBMITTED FROM IMPACT FEE ASSESSMENT
 ROUTED TO C-31 BOX WITH OTHER PLAN.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2010-02-17 Cont ID  
Sent By lmartine Date 2010-02-16 Time 08:38 Rev Time 0.00
Received By lmartine Date 2010-02-16 Time 08:37 Sent To  
Notes
2010-02-17 08:49:20C--33,34

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-11-25 Cont ID  
Sent By lmartine Date 2009-11-23 Time 12:17 Rev Time 0.00
Received By lmartine Date 2009-11-23 Time 12:17 Sent To  
Notes
2009-11-25 12:17:52C--41 & 42

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-08-26 Time   Rev Time 0.00
Received By btrobaug Date 2009-08-03 Time 13:31 Sent To  
Notes
2009-08-03 13:34:26C 45

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2010-03-23 Cont ID  
Sent By jwitmer Date 2010-03-23 Time 11:49 Rev Time 0.00
Received By jwitmer Date 2010-03-23 Time 11:48 Sent To  
Notes
2010-03-23 11:50:50 
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
  

Review Stop L LANDSCAPING
Rev No 4 Status P Date 2010-04-16 Cont ID  
Sent By rkussner Date 2010-04-16 Time 16:57 Rev Time 0.00
Received By rkussner Date 2010-04-16 Time 16:56 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 3 Status F Date 2010-03-09 Cont ID  
Sent By rkussner Date 2010-03-09 Time 12:49 Rev Time 0.00
Received By rkussner Date 2010-03-09 Time 12:49 Sent To  
Notes
2010-03-09 13:20:19***LANDSCAPE REVIEW FAILED***
  
 PLEASE RESPOND TO REVIEW COMMENTS IN WRITTEN FORMAT.
  
 1. THERE ARE CONFLICTS BETWEEN VARIOUS UTILITIES AND
 PROPOSED LANDSCAPING. A WATER MAIN RUNS DIRECTLY UNDER
 PROPOSED TREES IN THE TERMINAL ISLANDS SOUTH OF THE
 EXISTING WET POND. A CLEAN-OUT, 3" VENT AND OTHER ITEMS
 ARE SHOWN IN THE FIRE LANE. THERE IS ALSO A WATER LINE
 ALONG THE NORTH PERIMETER OF THE SITE IN CONFLICT WITH
 SOME EXISTING AND PROPOSED TREES.
  
 2. PURSUANT TO SECTION 94-442 (D), PRIVATE LAND AND
 PUBLIC RIGHTS-OF-WAY BETWEEN STREET OR SIDEWALK
 SURFACES AND REQUIRED BUFFER STRIPS AND LANDSCAPED OPEN
 SPACE AREAS SHALL BE PLANTED WITH GRASS. GRASS AREAS
 SHALL BE SODDED. MULCH HAS BEEN PROPOSED ALONG THE
 SOUTH END OF THE PARKING LOT AND IN THE 5 X 5 FOOT
 AREAS ALONG THE LANDSCAPE STRIPS THAT SEPARATE THE
 PARKING ROWS. MULCH CANNOT BE A SUBSTITUTE FOR SOD.
 GROUND COVER SHALL BE PLANTED IN THE 5 X 5 FOOT
 LANDSCAPE AREAS (JUST OUTSIDE OF THE ROOTBALL OF THE
 TREE) AND THE AREA ALONG THE SOUTH END OF THE PARKING
 LOT SHALL BE SODDED.
  
 3. STAFF STRONGLY RECOMMENDS THAT THE PALM GROUPINGS BE
 UNDERPLANTED WITH SHRUBS AND GROUND COVER.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.,

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2010-01-15 Cont ID  
Sent By rkussner Date 2010-01-15 Time 17:03 Rev Time 0.00
Received By rkussner Date 2010-01-15 Time 17:03 Sent To  
Notes
2010-01-15 17:04:59***LANDSCAPE REVIEW FAILED***
  
 MUST PROCESS A MINOR AMENDMENT PRIOR TO REVIEW OF
 PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-08-13 Cont ID  
Sent By rkussner Date 2009-08-13 Time 17:27 Rev Time 0.00
Received By rkussner Date 2009-08-13 Time 17:27 Sent To  
Notes
2009-08-13 17:28:47***LANDSCAPE REVIEW FAILED***
  
 MUST PROCESS A MINOR AMENDMENT PRIOR TO REVIEW OF
 PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2011-09-21 Cont ID  
Sent By hmoser Date 2011-09-21 Time 11:45 Rev Time 0.00
Received By hmoser Date 2011-09-21 Time 11:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2010-05-04 Cont ID  
Sent By rregueir Date 2010-05-04 Time 10:51 Rev Time 0.00
Received By rregueir Date 2010-05-04 Time 10:50 Sent To  
Notes
2010-05-04 10:51:46**PROVISO**
  
 PROVIDE MANUFACTURER'S WIND RESISTANCE DATA FOR ALL
 OUTDOOR APPLIANCES AND EQUIPMENT WHICH IS EXPOSED TO
 WIND IN ACCORDANCE WITH FBC-M 301.12.
  
 SEPARATE PLANS AND PERMIT APPLICATIONS REQUIRED FOR
 KITCHEN HOODS, HOOD SUPPRESSION AND WALK-IN COOLERS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2010-03-26 Cont ID  
Sent By hmoser Date 2010-03-26 Time 12:02 Rev Time 0.00
Received By hmoser Date 2010-03-26 Time 12:02 Sent To  
Notes
2010-03-26 12:37:19PLAN DENIED
 COMMENTS # 3, FROM LAST REVIEW WAS NOT ADDRESSED ,
 COMMENT # 4 THE PRODUCT APPROVALS ARE FOR GREENHECK
 FANS NOT PENNBARRY FANS ,COULD NOT FIND THE WIND
 CALCULATIONS FOR THE RTU UNITS OR EXHAUST FANS .
 COMMENT # 5 NOT ADDRESSED ,
 PLAN REVIEW BY HAROLD MOSER 561-805-6732
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-12-19 Cont ID  
Sent By rregueir Date 2009-12-19 Time 14:43 Rev Time 0.00
Received By rregueir Date 2009-12-19 Time 14:02 Sent To  
Notes
2009-12-19 14:43:01REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS FOR CONTINUITY:
  
 1. OK
  
 2. OK
  
 3. **NOT ADDRESSED** NOTE 15.710 ON PG M2 CALLS FOR FAN
 TO RUN CONTINUOUSLY DURING OPERATION, BUT THERE IS NO
 INDICATION ON PLANS AS TO HOW THIS WILL BE
 ACCOMPLISHED. ALSO, NOTE H ON PAGE M4 EF SCHEDULE CALLS
 FOR INTERLOCK WITH MUA FANS. THIS IS A DIFFERENT
 REQUIREMENT FROM THE INTERLOCK WITH COOKING APPLIANCES
 AS REQUIRED PER FNC-M 507.2.1.1. KITHCEN HOOD EXHAUST
 SYSTEM IS NO LONGER PART OF THIS REVIEW. PROVIDE
 SEPARATE PLANS AND PERMIT APPLICATIONS FOR COMMERCIAL
 KITCHEN HOOD EXHAUST SYSTEMS AND HOOD SUPPRESSION
 SYSTEMS.
  
 4. **NOT ADDRESSED** THE CUT SHEETS PROVIDED DO NOT
 CONTAIN ANY INFORMATION FROM THE APPLIANCE
 MANUFACTURERS REGARDING THE WIND RESISTANCE
 CAPABILITIES OF THE APPLIANCES. PROVIDE MANUFACTURER'S
 DATA SHOWING ALL OUTDOOR APPLIANCES (RTU, EF,
 CONDESNER, ETC.) ARE DESIGNED FOR WIND RESISTANCE IN
 ACCORDANCE WITH FBC-M 301.12.
  
 5. ENERGY CALCULATIONS: UPDATED FORM 400B-08 WAS
 PROVIDED, HOWEVER, THE CERTIFICATION PAGE IN THE CODE
 COMPLIANCE FORM IS A PHOTOCOPY. PROVIDE ORIGINAL SIGNED
 AND SEALED CODE COMPLIANCE FORMS IN ACCORDANCE WITH
 FBC-B 13-103.2. ALSO, ENERGY CALCULATIONS DO NOT
 INCLUDE THE NEW RTU 25. PLANS AND ENERGY CALCULATIONS
 SHALL MATCH IN ACCORDANCE WITH 13-103.2.
  
 6. **NOT ADDRESSED** NO COOLING LOAD CALCULATIONS COULD
 BE FOUND IN THE SUBMITTED PACKAGE. COOLING LOAD
 CALCULATIONS SHALL BE APENDED TO THE ENERGY CODE
 COMPLIANCE FORM IN ACCORDANCE WITH FBC-B 13-407.AB.1.
  
 NOTE: SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 COMMERCIAL KITCHEN HOOD EXHAUSTSYSTEMS, HOOD
 SUPPRESSION SYSTEMS, AND REMOTE REFRIGERATION SYSTEMS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-08-06 Cont ID  
Sent By rregueir Date 2009-08-06 Time 09:43 Rev Time 0.00
Received By rregueir Date 2009-08-05 Time 16:02 Sent To  
Notes
2009-08-06 09:43:15REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. RETURN AIR TRANSFER GRILLS IN SOME AREAS ARE NOT
 SIZED TO MEET THE EXCEPTIONS UNDER FBC-M 601.4.
 EXAMPLES: DETAIL 1 (COMPUTER/COUNTDOWN/CASH ROOM AREAS)
 AND DETAIL 9 (DEMO ROOM) ON PAGE M2. PLEASE CHECK ALL
 RETURN AIR TRANFER GRILL SIZES FOR COMPLIANCE.
  
 2. PAGE M2: DETAIL 1 SHOWS THE MANUAL PULL STATION FOR
 THE HOOD SUPPRESSION SYSTEM IN EXCESS OF 20 FEET FROM
 THE KITCHEN EXHAUST SYSTEM. ALSO, DETAIL 2 SHOWS A
 MANUAL PULL STATION LESS THAN 10 FEET FROM THE KITCHEN
 EXHAUST SYSTEM. THESE MANUAL ACTUATION DEVICES SHALL BE
 LOCATED AT OR NEAR A MEANS OF EGRESS FROM THE COOKING
 AREA A MINIMUM OF 10 FEET AND A MAXIMUM OF 20 FEET FROM
 THE KITCHEN EXHAUST SYSTEM IN ACCORDANCE WITH FBC-B
 904.11.1.
  
 3. PAGE M2: MECHANICAL KEYNOTE 15.722 CALLS FOR EXHAUST
 FAN INTERLOCK WITH PIZZA OVEN OPERATION. INTERLOCK OF
 EXHAUST FAN WITH ROTISSERIE OPERATION IS ALSO REQUIRED
 IN ACCORDANCE WITH FBC-M 507.2.1.1. THE ACTIVATION OF
 THE EXHAUST FAN SHALL OCCUR THROUGH AN INTERLOCK WITH
 THE COOKING APPLIANCES, BY MEANS OF HEAT SENSORS OR BY
 MEANS OF OTHER APPROVED METHODS.
  
 4. PROVIDE MANUFACTURER'S DATA FOR THE WIND RESISTANT
 CONSTRUCTION AND INSTALLATION OF ALL APPLIANCES EXPOSED
 TO WIND SUCH AS: NEW RTUS, EXHAUST FANS, MUA FANS,
 REMOTE CONDENSERS IN ACCORDANCE WITH FBC-M 301.12.
  
 5. ENERGY CALCULATIONS: THIS JOB CONSTITUTES A
 RENOVATION AS DEFINED IN FBC-B SECTION 13-202. AS SUCH,
 THIS BUILDING SHALL COMPLY WITH METHOD B OF SUBCHAPTER
 13-4 FOR INSULATION, HVAC SYSTEMS, LIGHTING, WATER
 HEATING SYSTEMS AND EXTERIOR ENVELOPE COMPONENTS BEING
 RETROFITTED OR REPLACED IN ACCORDANCE WITH FBC-B
 13-101.1.3. SUBMIT A COMPLETED ENERGY CODE COMPLIANCE
 FORM 400B-08 TO DEMONSTRATE COMPLIANCE WITH THIS
 SECTION. THE FORM 400A-04R WHICH WAS SUBMITTED IS OUT
 OF DATE AND NO LONGER VALID AS OF MARCH 1, 2009, THE
 EFFECTIVE DATE OF THE 2007 FLORIDA BUILDING CODE.
  
 6. A COOLING LOAD CALCULATION FOR ALL NEW AIR
 CONDITIONING APPLIANCES BEING INSTALLED SHALL BE
 ATTACHED TO THE ENERGY CODE COMPLIANCE FORM IN
 ACCORDANCE WITH FBC-B SECTION 13-407.AB.1.
  
 NOTE: SEPARATE PERMITS ARE REQUIRED FOR THE KITCHEN
 HOOD EXHAUST AND HOOD SUPPRESSION SYSTEMS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-12-15 Cont ID  
Sent By kstevens Date 2009-12-15 Time 17:45 Rev Time 0.00
Received By kstevens Date 2009-12-15 Time 17:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-08-13 Cont ID  
Sent By kstevens Date 2009-08-13 Time 10:32 Rev Time 0.00
Received By kstevens Date 2009-08-13 Time 10:32 Sent To  
Notes
2009-08-13 10:54:07DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
  
 1. INFORMATIONAL: SEPARATE PERMITS ARE REQUIRED FOR THE
 TEMP. TOILET ROOM TRAILER & THE GREASE INTERCEPTORS.
 SECTION 105.1.
  
 2. SHTS SP2.1, P1 & P3.1 DETAIL #2 A 2-WAY CLEANOUT IS
 REQUIRED ON THE INLET PIPING TO THE GREASE
 INTERCEPTORS. (UTILITY STANDARD)
  
 3. SHTS SP2 COMPACTOR PAN PLAN INDICATES A DRAIN &
 SP2.1 DETAILS 2 & 3. PLEASE INDICATE IF THE COMPACTOR
 WILL BE COVERED AS TO NOT ALLOW STORM WATER TO ENTER
 THE DRAIN. THE DRAIN SHALL CONNECT TO THE GREASE
 INTERCEPTOR. IF THE STORM WATER WILL DRAIN AT THE
 COMPACTOR DRAIN, THEN THE DRAIN WILL HAVE TO BE
 DELETED. PLEASE CLARIFY. SECTION 106.1.2 (MORE INFO
 REQD).
  
 4. SHT P2.1 DETAIL #1. SUBMIT CALCULATIONS FOR THE
 STORM DRAINAGE. SHOW THE SQUARE FOOT AREA OF THE ROOF
 PLUS 1/2 AREA OF ALL VERTICAL WALLS INCLUDING PARAPETS
 ADDED TO THE SQUARE FOOTAGE OF THE ROOF & TOTAL SQUARE
 FOOTAGE BEING DRAINED BY THE ROOF TABLE. TABLE 1106.3 &
 SECTIONS 1106.3 & 1106.4.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date 2010-04-21 Cont ID  
Sent By lfranco Date 2010-04-21 Time 17:01 Rev Time 1.50
Received By lfranco Date 2010-04-21 Time 17:01 Sent To E
Notes
2010-04-26 12:03:15PLANNING AND ZONING: PASSED WITH PROVISO - SHEET LS1,
 PROPOSED MECHANICAL EQUIPMENT ON ROOFTOP SHALL BE
 SCREENED FROM ALL SIDES. SHEET A3.1 DEPICTS A VERY LOW
 PARAPET W/ NO DIMENSION OF THE TOP OF ROOF OR CROSS
 SECTION OF HOW HIGH THE MECHANICAL EQUIPMENT WILL BE.
 REVISE PLANS ACCORDINGLY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date 2010-03-10 Cont ID  
Sent By lfranco Date 2010-03-10 Time 14:22 Rev Time 0.00
Received By lfranco Date 2010-03-10 Time 14:22 Sent To B
Notes
2010-03-10 14:34:42PLANNING AND ZONING **** FAILED ****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. LANDSCAPE COMMENTS ARE OUTSTANDING. SEE LANDSCAPE
 COMMENTS FOR DETAILS.
  
 IF YOU HAVE ANY QUESTIONS, CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status F Date 2009-12-21 Cont ID  
Sent By lfranco Date 2009-12-21 Time 12:06 Rev Time 0.00
Received By lfranco Date 2009-12-21 Time 12:06 Sent To  
Notes
2009-12-21 12:07:15PLANNING AND ZONING: ***** FAILED****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. REPEAT COMMENT: THE PROPOSED WORK IS WITHIN THE
 SAM'S CLUB PROJECT THAT IS PART OF THE NORTH TRAIL
 COMMERCIAL PLANNED DEVELOPMENT ("CPD") . THE PROPOSED
 AMENDMENTS ARE CURRENTLY BEING REVIEWED FOR A MINOR PD
 AMENDMENT WITH THE PLANNING AND ZONING DEPARTMENT.
 THEREFORE, THIS PERMIT CANNOT BE APPROVED UNTIL FINAL
 APPROVAL OF THE MINOR AMENDMENT HAS BEEN MADE BY THE
 PLANNING AND ZONING DEPARTMENT, DUE TO PERTINENT
 CHANGES/REVISIONS THAT MAY BE REQUIRED, WHICH WILL NEED
 TO BE REFLECTED ON THIS PERMIT.
  
 ANY WORK PERFORMED WITHOUT FIRST OBTAINING THE MINOR
 AMENDMENT AND BUILDING PERMIT APPROVAL SHALL BE THE
 FULL RESPONSIBILITY OF THE OWNER TO RECTIFY AND
 CORRECT, SHOULD IT BE REQUIRED THROUGH OUR REVIEW
 PROCESS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-08-13 Cont ID  
Sent By lfranco Date 2009-08-13 Time 17:15 Rev Time 0.00
Received By lfranco Date 2009-08-13 Time 17:15 Sent To  
Notes
2009-08-13 17:21:51PLANNING AND ZONING: ***** FAILED****
  
 1. RESPOND TO COMMENTS IN WRITING.
  
 2. THE PROPOSED WORK IS WITHIN THE SAM'S CLUB PROJECT
 THAT IS PART OF THE NORTH TRAIL COMMERCIAL PLANNED
 DEVELOPMENT ("CPD") . THE PROPOSED AMENDMENTS ARE
 CURRENTLY BEING REVIEWED FOR A MINOR PD AMENDMENT WITH
 THE PLANNING AND ZONING DEPARTMENT. THEREFORE, THIS
 PERMIT CANNOT BE APPROVED UNTIL FINAL APPROVAL OF THE
 MINOR AMENDMENT HAS BEEN MADE BY THE PLANNING AND
 ZONING DEPARTMENT, DUE TO PERTINENT CHANGES/REVISIONS
 THAT MAY BE REQUIRED, WHICH WILL NEED TO BE REFLECTED
 ON THIS PERMIT.
  
 ANY WORK PERFORMED WITHOUT FIRST OBTAINING THE MINOR
 AMENDMENT AND BUILDING PERMIT APPROVAL SHALL BE THE
 FULL RESPONSIBILITY OF THE OWNER TO RECTIFY AND
 CORRECT, SHOULD IT BE REQUIRED THROUGH OUR REVIEW
 PROCESS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 EMAIL: [email protected]
  
  
  


Account Summary | Usage Policy | Privacy Policy