Plan Review Details - Permit 09070711
Plan Review Stops For Permit 09070711
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-12-29 Cont ID  
Sent By jwitmer Date 2009-12-29 Time 08:07 Rev Time 3.00
Received By jwitmer Date 2009-12-29 Time 08:07 Sent To  
Notes
2009-12-29 08:09:02CHANGE OF CONTRACTOR NO PRODUCT APPROVALS WERE
 SUBMITTED, CALLED ROSE KENNEY WILL REQUIRE 2 SETS OF
 ALL PRODUCT APPROVALS!
  
  
 BUILDING PLAN REVIEW
 PERMIT: 09070711/REV. 09120410
 ADD: 2401 SPRUCE AVE
 CONT: CLEARSPAN STRUCTURES
 TEL: (561)662-1819 ROSE KENNEY
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW:
 # 4 DATED 9-11-09
 #5 DATED 10-26-09
 DEC.29/2009
  
 BUILDING APPROVED WITH EXCEPTION!
  
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S).
  
 1) SHEET A-4 INDICATES WINDOWS WITH THE USE OF GLASS
 BLOCK PLEASE PROVIDE PRODUCT APPROVALS FOR LARGE
 MISSILE TESTED GLASS BLOCKRULE 9B-72 AND 1609.1.
  
 2) SHEET A-6 INDICATES A DOORWAY WITH NEW TRANSOM,
 PLEASE SUBMIT NEW PRODUCT APPROVALS, IT IS UNCLEAR IF
 THIS WAS TESTED AS A SINGLE UNIT OR IF 3 PRODUCT
 APPROVALS WILL BE REQUIRED. (1) DOOR, (2) HORIZONTAL
 MULLION & (3) STOREFRONT GLAZED WINDOW UNIT , RULE
 9B-72 & 1609.1.
  
 2A) PRODUCT APPROVALS THAT WERE LISTED ABOVE WILL ALSO
 NEED TO BE REVIEWED BY THE DESIGNER OF RECORD AND AFFIX
 THEIR SHOP DRAWING STAMP. 106.3.3 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITTING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. PLEASE NOTE IF OTHER PRODUCT
 APPROVALS ARE TO BE INSTALLED UNDER THIS PERMIT NOT
 MENTIONED ABOVE BUT ARE SUBJECT TO RULE 9B-72 THEY WILL
 ALSO NEED TO BE SUBMITTED FOR REVIEW.
  
 3) SHEET A7 DETAIL# 3 STAIR AND LANDING WILL REQUIRE
 HANDRAILS PER 1009.11 2004 FBC- BUIULDING.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE
 CUSTOMER SERVICE SURVEY AT:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-10-07 Cont ID  
Sent By jwitmer Date 2009-10-07 Time 13:03 Rev Time 0.00
Received By jwitmer Date 2009-09-23 Time 11:46 Sent To  
Notes
2009-09-23 11:47:32CHANGE OF CONTRACTOR NO PRODUCT APPROVALS WERE
 SUBMITTED, CALLED ROSE KENNEY WILL REQUIRE 2 SETS OF
 ALL PRODUCT APPROVALS.\
  
  
 BUILDING PLAN REVIEW
 PERMIT: 09070711
 ADD: 2401 SPRUCE AVE
 CONT: CLEARSPAN STRUCTURES
 TEL: (561)662-1819 ROSE KENNEY
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION REVIEW # 4 DATED 9-11-09
 ACTION: DENIED
  
 1) THE COVER SHEET OR INDEX SHEET INDICATES THERE TO BE
 A NEW LS-1 SHEET, MISSING.
  
 2) PLEASE INDICATE THE WALL OR CEILING MOUNTED
 DIRECTIONAL AND EXIT SIGNAGE, THE SIGNAGE ON SHEET A-1
 IS NOT CLEAR IN WHICH CORRIDOR THE OCCUPANT LOAD IS
 BEING DIRECTED. 1006.3.8.
  
 3A) SHEET A-1, A-3, A-7 & A-8 ALL INDICATE A NEW STAIR
 & LANDING AT DOOR# 104. THE DETAIL D3 / SHEET A-7
 INDICATES THE LANDING BEING 3'-8" IN LENGTH SECTION
 1009.4 INDICATES THE MINIMUM LENGTH IN THE DIRECTION OF
 TRAVEL OF 48".
  
 3B) THIS SAME STAIRAND LANDING APPEAR TO CROSS THE
 PROPERTY LINE OR AS INDICATED ON THE PLANS THEY ARE
 JUSST CUT OFF, THE TOP CORNER OF THE LANDING AND
 PORTION OF STEP. 101.3* THE OTHER ISSUE EACH STEP SHALL
 BE READILY VISIBLE. 1003.5.1.
  
 4) SHEET A-4 INDICATES WINDOWS WITH THE USE OF GLASS
 BLOCK PLEASE PROVIDE PRODUCT APPROVALS FOR LARGE
 MISSILE TESTED GLASS BLOCKRULE 9B-72 AND 1609.1.
  
 5) A-5 THE COMMENTARY SHEET SUPPLIED FOR THE REVISIONS
 INDICATES ON A-5 ABOVE THE TECHNICAL SUPPORRT PLATFORM
 THE METAL RAILING WAS ELININATED AND A NEW DRYWALL
 PARTITION WILL TAKE ITS PLACE PLEASE REVIEW SECTION 6
 IT STILL APPEARS TO BE THERE. DISCREPANCY, 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 6) SHEET A-6 INDICATES A DOORWAY WITH NEW TRANSOM,
 PLEASE SUBMIT NEW PRODUCT APPROVALS, IT IS UNCLEAR IF
 THIS WAS TESTED AS A SINGLE UNIT OR IF 3 PRODUCT
 APPROVALS WILL BE REQUIRED. (1) DOOR, (2) HORIZONTAL
 MULLION & (3) STOREFRONT GLAZED WINDOW UNIT , RULE
 9B-72 & 1609.1.
  
 7) SHEET A-12 NOTE BOTTOM LEFT CORNER OF PLANS
 INDICATES THE FINAL FINISHES TO BE CONFIRMED WITH CCE.
 PLEASE PROVIDE THE MINIMUM CRITICAL RADIENT FLUX FOR
 CARPETS FOR THE A & B OCCUPANCIES 804.5.1. BEFORE FLOOR
 FINISHES ARE INSTALLED.
  
 8) A-14 PLEASE REMOVE NOTES INDICATING THE RESIDENTIAL
 CODE.
  
 9A) PRODUCT APPROVALS THAT WERE LISTED ABOVE WILL ALSO
 NEED TO BE REVIEWED BY THE DESIGNER OF RECORD AND AFFIX
 THEIR SHOP DRAWING STAMP. 106.3.3 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITTING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 9B) PLEASE NOTE IF OTHER PRODUCT APPROVALS ARE TO BE
 INSTALLED UNDER THIS PERMIT NOT MENTIONED ABOVE BUT ARE
 SUBJECT TO RULE 9B-72 THEY WILL ALSO NEED TO BE
 SUBMITTED FOR REVIEW.
  
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2009-07-28 Cont ID  
Sent By swurafti Date 2009-07-28 Time 15:54 Rev Time 0.00
Received By swurafti Date 2009-07-28 Time 15:54 Sent To  
Notes
2009-07-28 15:54:39OKAY TO ISSUE PER RBROWN - NOTE UNDER PERMIT # 06090625

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-10-09 Cont ID  
Sent By dpalmer Date 2009-10-09 Time 10:51 Rev Time 0.00
Received By dpalmer Date 2009-10-09 Time 10:51 Sent To  
Notes
2009-10-09 10:51:25 
  
 ** DENIED **
  
 1) NOTE: THE SUBMITTED PLANS CONTAIN THE OLD ADDRESS
 UNDER THE PREVIOUS EXPIRED PERMIT OF 425 24TH ST.
 HOWEVER PLANS ARE NOW SUBMITTED UNDER A NEW PERMIT WITH
 AN APPLIED LOCATION OF 2401 SPRUCE AVE.
 PLEASE COORDINATE THE ACTUAL APPLIED LOCATION WITH
 PLANS.
  
 2) NOTE: THE SUBMITTED ENERGY CALCULATIONS DO NOT
 COORDINATED FOR ELECTRICAL AS WELL AS OTHER TRADES.
 PLEASE SEE COMMENTS FROM OTHER TRADES SUCH AS BUILDING
 FOR FLOOR TYPES WHICH ARE ALL SHOWN AS CARPET AND
 RUBBER PADDING.
 THE INPUT DATA REPORT INDICATES EXTERIOR LIGHTING WHICH
 IS EXEMPT BASED ON THE ENERGY CODE. HOWEVER NO
 LOCATIONS ON THIS BUILDING ARE HISTORIC LANDMARK OR
 MONUMENT. NO LOCATIONS ARE REQUIRED BY STATUTE, HEALTH,
 LIFE SAFETY ORDINANCE ETC.
 THE MANUAL ON/OFF IS NOT ACCURATE BASED ON THE REQUIRED
 AUTOMATED CONTROLS.
 13-415.2.ABC.1.3,13-415.2, 13-415.1.AB.1
  
 3) NOTE: PLEASE COMPLETE LIGHTING CONTROLS PER FBC
 13-415.1.ABC.1.1,.1.2,.1.3, .1.4.
 PLEASE SEE ROOMS SUCH AS STORAGE ROOM, CHAIR STORAGE,
 MULTI-PURPOSE STORAGE, HALLWAYS ALL SHOW STANDARD
 CONTROL DEVICES WITHOUT AUTOMATED CONTROLS OF SOME
 KIND.
 PLEASE REVISE PLANS AND PROVIDE DETAILS FOR THESE
 AREAS. MOST OTHER AREAS ARE STILL SHOWING MOTION
 SENSORS. PLEASE VERIFY IF THESE ARE IN FACT MOTION
 SENSORS OR OCCUPANCY SENSORS?
 PLEASE ALSO KNOW THAT DEVICES IN MULTI-GANG BATHROOMS
 ARE REQUIRED TO BE DUAL TECHNOLOGY.
  
 4) NOTE: PLEASE SEE RISER AND PANEL DP2 WHICH INDICATES
 A 400AMP BREAKER FEEDING PANEL E YET THE RISER
 INDICATES 350MCM WHICH IS NOT RATED FOR THE 400AMP OVER
 CURRENT PROTECTION SHOWN.
 310.16,110.14,240.4
  
 5) NOTE: PLEASE CONFIRM AIC RATINGS FOR ALL SERVICE
 EQUIPMENT. PLANS AND PANEL SCHEDULES STATE 42K FOR ALL
 PANELS AND BREAKERS. IF 42K RATED PANELS ARE USED FOR
 ALL PANELS AND BREAKERS THIS WOULD BE A SUBSTANTIAL
 EXPENSE. THIS IS OK HOWEVER IF ALL IS SHOWN AT 42K,
 THEN ALL PANELS AND BRANCH BREAKERS WILL BE REQUIRED TO
 BE INSTALLED PER PLANS.
 110.9
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2010-01-04 Cont ID  
Sent By mawillia Date 2010-01-04 Time 13:52 Rev Time 0.00
Received By mawillia Date 2010-01-04 Time 13:20 Sent To  
Notes
2010-01-04 13:50:31*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS PLAN REVIEW HAVE BEEN
 ADDRESSED; PLAN SHEETS D-1, LS-1, A-1, A-3, A-13, A-14,
 E-3, AND E-6 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-10-08 Cont ID  
Sent By mawillia Date 2009-10-08 Time 15:52 Rev Time 0.00
Received By mawillia Date 2009-10-08 Time 10:45 Sent To  
Notes
2009-10-08 15:27:21*****DENIED*****
  
  
 1. THE ACTUAL PROJECT ADDRESS SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET. THE ADDRESS OF 425
 24TH STREET IS CURRENTLY SHOWN IN THE PLANS.
  
 2. AS PER 12/31/2008, NFPA 101, LIFE SAFETY CODE, 2006
 EDITION SHALL BE REFERENCED. THE 2003 EDITION IS LISTED
 IN THE APPLICABLE CODE SECTION ON SHEET SP-1 (COVER
 PAGE).
  
 3. UNABLE TO LOCATE THE LIFE SAFETY PLAN (LS-1) IN THE
 PLAN PACKAGE AS INDICATED ON THE COVER SHEET (SP-1).
  
 4. ON THE APPROPITE EXTERIOR ELEVATION WHICH FRONTS THE
 STREET, DISPLAY/SHOW THE NUMERICAL ADDRESS OF THE
 PROPERTY.
  
 5. DISPLAY/SHOW THE LOCATION OF THE REQUIRED KNOX BOX.
  
 6. SPECIFY THE INTERIOR FINISH MATERIALS FOR THE WALLS
 AND CEILINGS IN TERMS OF CLASS A. CLASS B, OR CLASS C.
  
 7. SHOW THE LOCATION OF THE 2A10:BC RATED FIRE
 EXTINGUISHERS WHICH SATISFY THE 75' TRAVEL DISTANCE.
  
 8. PROVIDE A LAYOUT OF THE PROPOSED FIRE SPRINKLER
 HEADS.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-09-15 Cont ID  
Sent By kstevens Date 2009-09-15 Time 16:49 Rev Time 0.00
Received By kstevens Date 2009-09-15 Time 16:49 Sent To  
Notes
2009-09-15 16:54:10SENT TO C-25.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-09-23 Cont ID  
Sent By rregueir Date 2009-09-23 Time 08:59 Rev Time 0.00
Received By rregueir Date 2009-09-23 Time 08:54 Sent To  
Notes
2009-09-23 08:59:35REVIEW #: 1ST REVISION
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NOTE: THIS REVISION CONSTITUTES A COMPLETE REDESIGN OF
 THE HVAC SYSTEM FROM THE ORIGINAL PERMITTED SET FO
 PLANS. PLANS HAVE BEEN REVIEWED ACCORDINGLY.
  
 1. ARCHITECTURAL FLOOR PLAN SHOWS CORRIDOR WALLS AS
 FIRE RESISTANCE RATED. DUCT PENETRATIONS AND AIR
 TRANSFER OPENINGS AT CORRIDOR WALLS SHALL BE PROTECTED
 WITH FIRE AND SMOKE DAMPERS IN ACCORDANCE WITH FBC-M
 607.5.3 AND FBC-M 607.5.4. SEVERAL PENETRATIONS OR
 OPENINGS SHOW FIRE DAMPERS WITH NO SMOKE DAMPERS WHILE
 OTHERS SHOW NO PROTECTION AT ALL. PLEASE CHECK ALL
 OPENINGS AND PENETRATIONS OF CORRIDOR WALLS AND SHOW
 COMPLIANCE WITH THESE SECTIONS.
  
 2. PAGE M-1, FLOOR PLAN SHOWS A FIRE DAMPER IN THE WALL
 ABOVE THE DOOR INTO ROOM STUDIO 1. THERE IS NO DUCT OR
 TRANSFER OPENING SHOWN AT THIS LOCATION. PLEASE
 CLARIFY. IF A TRANSFER OPENING EXISTS AT THIS LOCATION,
 PROVIDE A SIZE IN ACCORDANCE WITH FBC-M 601.4 AND
 603.1.
  
 3. PLEASE ADD THE SYMBOL USED FOR A MOTORIZED VOLUME
 DAMPER TO THE SYMBOL LEGEND. THIS WILL ALLOW A THOROUGH
 REVIEW TO DETERMINE WHETHER MOTORIZED DAMPERS ARE BEING
 PROVIDED AT ALL REQUIRED LOCATIONS IN ACCORDANCE WITH
 FBC-B 13-409.AB.3.3 FOR SHUTOFF DAMPER CONTROLS. ALSO,
 PLEASE CHECK THE ENTIRE SYMBOL LEGEND TO ENSURE ALL
 SYMBOLS AND ABBREVIATIONS USED ON PLANS ARE REPRESENTED
 IN THE LEGEND AND CORRESPOND WITH PLANS.
  
 4. THE SYMBOL LEGEND ON PAGE M-1 INDICATES A ???SD???
 SYMBOL FOR DUCT MOUNTED SMOKE DETECTORS WHILE THE FLOOR
 PLAN APPEARS TO USE A DIFFERENT SYMBOL. PLEASE
 COORDINATE SYMBOLS USED ON FLOOR PLAN WITH THOSE SHOWN
 IN THE SCHEDULE IN ORDER TO FACILITATE A REVIEW FOR
 COMPLIANCE WITH THE SMOKE DETECTOR REQUIREMENTS OF
 FBC-M 606.2.
  
 5. AHU-1 AND AHU-2 SERVE A COMBINED SUPPLY DUCT. DUCT
 SMOKE DETECTORS ARE REQUIRED ON THE SUPPLY AND RETURN
 OF EACH UNIT IN ACCORDANCE WITH FBC-M 606.2.2. FLOOR
 PLAN APPEARS TO BE MISSING THE RETURN SMOKE DETECTOR ON
 AHU-2.
  
 6. PAGE M-1, ALL OUTSIDE AIR DUCTS ON FLOOR PLAN ARE
 MISSING SIZE. PROVIDE MISSING INFORMATION BY SHOWING
 ALL DUCT SIZES ON PLANS IN ACCORDANCE WITH FBC-M 603.1
 AND FBC-B 13-410.AB.1.2.
  
 7. SUPPLY BRANCH DUCT SERVING ROOM 105 IS MISSING SIZE.
 PROVIDE MISSING INFORMATION BY SHOWING ALL DUCT SIZES
 ON PLANS IN ACCORDANCE WITH FBC-M 603.1 AND FBC-B
 13-410.AB.1.2.
  
 8. THE SUPPLY REGISTERS IN MEN???S H/C RESTROOM,
 WOMEN???S H/C RESTROOM AND ADJACENT JANITOR???S CLOSET
 ARE MISSING CFM AND GRILL DESIGNATIONS. PROVIDE MISSING
 DATA ON PLANS TO SHOW MINIMUM AIRFLOW REQUIREMENTS PER
 FBC-M 603.1 AND FBC-B 13-410.AB.4.1.
  
 9. EXHAUST FANS 6, 7 AND 8 APPEAR TO BE LOCATED IN A
 PLENUM CEILING. EXHAUST DUCTS UNDER POSITIVE PRESSURE
 SHALL NOT PASS THROUGH A PLENUM IN ACCORDANCE WITH
 FBC-M 601.3.
  
 10. IT IS NOT CLEAR ON PLANS WHETHER THE WOOD RAFTERS
 AND ROOF DECKING ABOVE THE PLENUM CEILING AREAS ARE
 EXPOSED TO THE PLENUM. THESE ITEMS AND ANY OTHER
 COMBUSTIBLE MATERIALS SHALL NOT BE EXPOSED TO THE
 PLENUM IN ACCORDANCE WITH FBC-M 602.2.1.
  
 11. ENERGY CODE COMPLIANCE FORM INDICATES ROOF IS
 INSULATED TO R-11.53. CAVITIES BENEATH A ROOF DECK
 WHICH WILL BE USED AS SUPPLY OR RETURN PLENUMS SHALL
 HAVE AN INSULATED ROOF. THE INSULATION SHALL HAVE AN
 R-VALUE OF AT LEAST R-19 IN ACCORDANCE WITH FBC-B
 13-404.AB.2.
  
 12. GRAVITY RELIEF VENTILATOR SCHEDULE SHOWS GRF-5 AS
 SERVING AHU-10. HOWEVER, FLOOR PLAN SHOWS AHU-10 AS
 SERVED BY GRF-4. PLEASE CORRELATE FLOOR PLANS AND
 EQUIPMENT SCHEDULES TO VERIFY MINIMUM REQUIRED
 VENTILATION RATES CAN BE PROVIDED IN ACCORDANCE WITH
 FBC-M 403.3.
  
 13. FLOOR PLAN SHOWS A FABRIC DUCT USED IN SEVERAL
 LOCATIONS. PROVIDE SUBMITTAL DATA FOR THE FABRIC DUCT
 TO SHOW COMPLIANCE WITH FBC-M 603.4.
  
 14. FLOOR PLAN SHOWS AHU-1 AND AHU-2 PROVIDING 4000 CFM
 EACH WHILE THE AHU SCHEDULE AND COOLING LOAD
 CALCULATIONS SHOW EACH UNIT PROVIDING 2900 CFM.
 COORDINATE FLOOR PLANS WITH EQUIPMENT SCHEDULE TO SHOW
 REQUIRED AIRFLOWS IN ACCORDANCE WITH FBC-M 603.1, FBC-M
 403.3 AND FBC-B 13-410.AB.4.1.
  
 15. OUTDOOR AIR SCHEDULE CALLS FOR AHU-1 AND AHU-2 TO
 PROVIDE 4500 COMBINED CFM OF OUTDOOR AIR WHILE THE
 FLOOR PLAN SHOWS THE SYSTEM WITH A TOTAL OF 5800 CFM OF
 RETURN, WHICH EQUALS THE TOTAL OF THE SUPPLY. HOW WILL
 THIS ALLOW FOR INTRODUCTION OF OUTDOOR AIR? THE FLOOR
 PLAN SHOWS THAT CO2 SENSORS WILL CONTROL THE MOTORIZED
 ODA DAMPERS, PRESUMABLY BASED ON DEMAND. HOW WILL THE
 REQUIRED VENTILATION RATE BE PROVIDED WITHOUT MOTORIZED
 DAMPERS TO REDUCE RETURN AIRFLOW IN CONJUNCTION WITH
 MODULATION OF THE ODA DAMPERS? PLEASE SHOW ON PLANS HOW
 THE REQUIRED VENTILATION RATE IS TO BE ACHIEVED IN THIS
 LOCATION IN ACCORDANCE WITH FBC-M 403.3.
 NOTE: IS ANY RELIEF AIR TO BE PROVIDED IN THIS AREA TO
 ALLOW FOR THIS INTRODUCTION OF OUTDOOR AIR?
  
 16. AHU-3 SERVING THE WORK/AREA SHOWS TWO 16X16 R/A
 TRANSFER OPENINGS, WITH ONE OF THESE LOCATED IN A
 CLOSET. THE CLOSET APPEARS TO BE SEPARATED FROM THE
 CONDITIONED SPACE BEING SERVED BY AHU-3. SHOW HOW
 BALANCED RETURN IS TO BE ACHIEVED IN THIS AREA IN
 ACCORDANCE WITH FBC-M 601.4.
  
 17. IN ROOM 103, WHAT IS THE PURPOSE OF THE 30X18 SOUND
 TRAP SHOWN BETWEEN ROOM 103 AND ROOM 100? PLEASE
 CLARIFY PER FBC-M 603.1.
  
 18. PAGE M-1, SEVERAL ???SOUND TRAP??? RETURN AIR
 TRANSFER OPENINGS ARE SHOWN ON THE PLANS WITH NO SIZE.
 PLEASE SHOW THE SIZE OF EACH SOUND TRAP FOR BALANCED
 RETURN IN ACCORDANCE WITH FBC-M 601.4.
  
 19. WHAT IS THE HEIGHT OF THE ROOFTOP CHILLER PAD ABOVE
 GRADE? PROVIDE A MEANS OF PERMANENT ACCESS TO THE
 SERVICE PLATFORM IN ACCORDANCE WITH FBC-M 306.5.
 PROVIDE WIND RESISTANCE DATA FOR ALL PROPOSED OUTDOOR
 APPLIANCES AND EQUIPMENT, SUCH AS GRF???S CONDENSING
 UNITS AND CHILLER. PROVIDE DETAILS FOR WIND RESISTANT
 INSTALLATION OF CHILLER, GRF???S AND ANY ASSOCIATED
 ROOF CURBS IN ACCORDANCE WITH FBC-M 301.13. ALSO,
 PROVIDE PRODUCT APPROVAL FOR PRE-ENGINEERED A/C STANDS
 USED FOR ROOFTOP CONDENSERS IN ACCORDANCE WITH FAC RULE
 9B-72 AND FBC-B 106.3.3.
  
 NOTE: PLEASE RESPOND TO EACH COMMENT IN WRITING,
 DESCRIBING HOW EACH COMMENT WAS ADDRESSED AS WELL AS
 WHERE THE RELEVANT INFORMATION CAN BE LOCATED WITHIN
 THE SUBMITTED DOCUMENTS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-09-17 Cont ID  
Sent By kstevens Date 2009-09-17 Time 16:25 Rev Time 0.00
Received By kstevens Date 2009-09-17 Time 16:25 Sent To  
Notes
2009-09-17 16:26:33SHTS P-1, P-2, P-3 & P-4 HAVE NO REVISIONS/CHANGES
 INDICATED. PLANS TO BE RETURNED TO CONTRACTOR.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-10-13 Cont ID  
Sent By eschneid Date 2009-10-13 Time 15:16 Rev Time 0.75
Received By eschneid Date 2009-10-13 Time 15:16 Sent To  
Notes
2009-10-13 15:26:33FAILED
  
 1) SHEET L.1-1 (LANDSCAPE PLAN) MISSING.
  
 2) GLAZING CALCULATIONS HAVE NOT BEEN PROVIDED FOR THE
 SOUTH FACADE. THIS WAS SUBMITTED (AND REDLINED BY RAR)
 AS SHEET SK-7 ON THE EXPIRED PERMIT. THE INFORMATION
 MAY BE PUT ON SHEET A-3 OR A SEPARATE SHEET AS DONE
 BEFORE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
 NOTE - SHEETS A1, A2, A3, A4, A8, A9, A15, SP1 & SP2 OK
 AS SUBMITTED FOR ZONING.