Plan Review Details - Permit 09070635
Plan Review Stops For Permit 09070635
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-10-07 Cont ID  
Sent By jwitmer Date 2009-10-07 Time 13:24 Rev Time 2.22
Received By jwitmer Date 2009-10-05 Time 16:17 Sent To  
Notes
2009-10-05 16:18:02BUILDING PLAN REVIEW
 PERMIT: 09070635
 ADD: 1600 N DIXIE HWY
 CONT: O/B CIOFFI, JOHN & GILDA
 TEL: (561)310-6252
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDER THIS
 PERMIT. 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST
 ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION
 PURSUANT TO SECTIONS 403, 404 AND 405 OF THIS CODE, IN
 THIS CASE CHANGE OF OCCUPANCY CHAPTER 9.
  
 2) EXISTING BUILDING CODE 904.1 GENERAL. FIRE
 PROTECTION REQUIREMENTS OF SECTION 912 SHALL APPLY
 WHERE A BUILDING OR PORTIONS THEREOF UNDERGO A CHANGE
 OF OCCUPANCY CLASSIFICATION.
  
 2A) EXIST BLDG CODE 912.2.1 FIRE SPRINKLER SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS THAT
 REQUIRES AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE
 PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE WITH
 CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING , SUCH
 SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE THE
 CHANGE OF OCCUPANCY OCCURS.
  
 2B) 2007 FBC 903.2.1.2 GROUP A-2. AN AUTOMATIC
 SPRINKLER SYSTEM SHALL BE PROVIDED FOR GROUP A-2
 OCCUPANCIES WHERE ONE OF THE FOLLOWING CONDITIONS
 EXISTS:
  
 1. THE FIRE AREA EXCEEDS 5,000 SQUARE FEET (464.5 M2).
  
 2. THE FIRE AREA HAS AN OCCUPANT LOAD OF 100 OR MORE.
  
 3. THE FIRE AREA IS LOCATED ON A FLOOR OTHER THAN THE
 LEVEL OF EXIT DISCHARGE.
  
 4. NIGHTCLUBS OR SIMILAR USAGE WHEN OCCUPANT LOAD IS
 100 OR MORE.
  
  
 3) EXIST BLDG CODE 912.2.2 FIRE ALARM AND DETECTION
 SYSTEM. WHERE A CHANGE IN OCCUPANCY CLASSIFICATION
 OCCURS THAT REQUIRES A FIRE ALARM AND DETECTION SYSTEM
 TO BE PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE
 WITH CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING ,
 SUCH SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE
 THE CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM
 NOTIFICATION APPLIANCES SHALL BE AUTOMATICALLY
 ACTIVATED THROUGHOUT THE BUILDING. WHERE THE BUILDING
 IS NOT EQUIPPED WITH A FIRE ALARM SYSTEM, ALARM
 NOTIFICATION APPLIANCES SHALL BE PROVIDED THROUGHOUT
 THE AREA WHERE THE CHANGE OF OCCUPANCY OCCURS AND SHALL
 BE AUTOMATICALLY ACTIVATED.
  
 4) 2997 FBC 907.2.1 GROUP A. A MANUAL FIRE ALARM SYSTEM
 SHALL BE INSTALLED IN GROUP A OCCUPANCIES HAVING AN
 OCCUPANT LOAD OF 300 OR MORE.
 PLANS INDICATE THE INSURANCE CERTIFICATE LIMITS THE
 OCCUPANT LOAD TO 250 BUT THE OCCUPANT LOAD IS BASED ON
 THE WORST CASE SCENARIO OF THE 508 AS INDICATED ON
 PLANS WWITHOUT DECLARING AN OCCUPANCY IN THE VACANT
 SPACES AS SHOWN ON PLANS.
  
 1004.1.1 AREAS WITHOUT FIXED SEATING. THE NUMBER OF
 OCCUPANTS SHALL BE COMPUTED AT THE RATE OF ONE OCCUPANT
 PER UNIT OF AREA AS PRESCRIBED IN TABLE 1004.1.1. FOR
 AREAS WITHOUT FIXED SEATING, THE OCCUPANT LOAD SHALL
 NOT BE LESS THAN THAT NUMBER DETERMINED BY DIVIDING THE
 FLOOR AREA UNDER CONSIDERATION BY THE OCCUPANT PER UNIT
 OF AREA FACTOR ASSIGNED TO THE OCCUPANCY AS SET FORTH
 IN TABLE 1004.1.1. WHERE AN INTENDED USE IS NOT LISTED
 IN TABLE 1004.1.1, THE BUILDING OFFICIAL SHALL
 ESTABLISH A USE BASED ON A LISTED USE THAT MOST NEARLY
 RESEMBLES THE INTENDED USE.
  
 5) EXISTING BLDG CODE 912.4.2 MEANS OF EGRESS FOR
 CHANGE OF USE TO EQUAL OR LOWER HAZARD CATEGORY. WHEN A
 CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO AN EQUAL
 OR LESSER HAZARD CATEGORY (HIGHER NUMBER) AS SHOWN IN
 TABLE 912.4, EXISTING ELEMENTS OF THE MEANS OF EGRESS
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTION 805 FOR
 THE NEW OCCUPANCY CLASSIFICATION. NEWLY CONSTRUCTED OR
 CONFIGURED MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING .
  
 5A ) PLEASE INDICATE HOW 254 OCCUPANTS WILL BE ABLE TO
 EXIT THROUGH A 3'-0" DOOR RATED FOR 170 OCCUPANTS (MAIN
 ENTRY) . 025.2 ASSEMBLY MAIN EXIT. EVERY ASSEMBLY
 OCCUPANCY SHALL BE PROVIDED WITH A MAIN ENTRANCE/EXIT.
 THE MINIMUM AGGREGATE WIDTH OF THE MAIN ENTRANCE FOR
 GROUP A OCCUPANCIES SHALL BE SUFFICIENT TO ACCOMMODATE
 50 PERCENT OF THE OCCUPANT LOAD AND SHALL BE AT THE
 LEVEL OF EXIT DISCHARGE OR SHALL CONNECT TO A STAIRWAY
 OR RAMP LEADING TO A STREET.
  
 5B) PLEASE INDICATE COMPLIANCE WITH EGRESS PATERNS
 PROVIDE EGRESS SIGNAGE AND DIRECTIONALS AS PER TABLE
 1006, 1006.2 FOR STANDBY POWER.
  
 5C) DOOR SWING AT THE GAME ROOM TO VACANT SPACE AT
 LEFT. 1008.1.2 DOORS SHALL SWING IN THE DIRECTION OF
 EGRESS TRAVEL WHERE SERVING AN OCCUPANT LOAD OF 50 OR
 MORE PERSONS OR A GROUP H OCCUPANCY.
  
 5D) PLANS INDICATE MANY VACANT ROOMS PLEASE REVIEW
 SECTION 1014.2 THIS LEAVES ROOMS WITH ONLY ONE MEANS OF
 EGRESS WHEN 2 WOULD BE REQUIRED FOR OCCUPANT LOADS 50
 OR GREATER. 1014.2 EGRESS THROUGH INTERVENING SPACES.
 EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH
 THIS SECTION.
  
 1.EGRESS FROM A ROOM OR SPACE SHALL NOT PASS THROUGH
 ADJOINING OR INTERVENING ROOMS OR AREAS, EXCEPT WHERE
 SUCH ADJOINING ROOMS OR AREAS ARE ACCESSORY TO THE AREA
 SERVED, ARE NOT A HIGH-HAZARD OCCUPANCY AND PROVIDE A
 DISCERNIBLE PATH OF EGRESS TRAVEL TO AN EXIT.
  
 6) EXISTING BLDG CODE 912.3 INTERIOR FINISH. IN AREAS
 OF THE BUILDING UNDERGOING THE CHANGE OF OCCUPANCY
 CLASSIFICATION, THE INTERIOR FINISH OF WALLS AND
 CEILINGS SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING , FOR THE NEW OCCUPANCY
 CLASSIFICATION.
  
 7) 912.8 ACCESSIBILITY. EXISTING BUILDINGS OR PORTIONS
 THEREOF THAT UNDERGO A CHANGE OF GROUP OR OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 STARTING AUGUST 21, 2009, THE CONSTRUCTION SERVICES
 DEPARTMENT WILL BE CLOSED ON FRIDAYS UNTIL FURTHER
 NOTICE.
  
 OPENING HOURS MONDAY - THURSDAY WILL REMAIN AT 8:00 AM
 - 5:00 PM.
  
 JIM WITMER C. B. O.
 COMMERCIAL COMBINATION PLAN REVIEW
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-07-30 Cont ID  
Sent By kconrad Date 2009-07-30 Time 08:42 Rev Time 0.00
Received By kconrad Date 2009-07-30 Time 08:42 Sent To  
Notes
2009-07-30 09:06:30TOM MOORE AND I MET WITH MR. CLARK TO PERFORM A CHANGE
 OF OCCUPANCY INSPECTION. THE FOLLOWING WAS OBSERVED:
  
 1) MR. CLARK STATED THAT HE WILL NOT BE UTILIZING THE
 KITCHEN OR SERVING FOOD AT THIS TIME. I ADVISED HIM
 THAT HE WILL NEED TO OBTAIN ADDITIONAL PERMITS FOR THE
 INSTALLATION OF A SUPPRESSION SYSTEM AS WELL AS A GAS
 PERMIT. HE STATED THAT HE WILL OBTAIN THESE PERMITS AT
 A LATER DATE AND THAT HE JUST WANTS TO CONDUCT A BAR
 BUSINESS.
  
 2) ADVISED MR. CLARK THAT HE WILL BE REQUIRED TO OBTAIN
 AN ELECTRICAL PERMIT AND OBTAIN ALL REQUIRE INSPECTIONS
 PRIOR TO THE ISSUANCE OF A C OF O FOR THE CHANGE OF
 OCCUPANCY ( A-3 TO A-2).
 ALSO THE EXISTING ELECTRICAL SYSTEM SHALL BE CERTIFIED
 BY A LICENSED ELECTRICAL CONTRACTOR.
  
 3) ADVISED MR. CLARK THAT HE MAY NOT CONDUCT BUSINESS
 UNTIL A C OF O AS BEEN ISSUED AS PER THE FBC, SECTION
 110.1.
  
 4) ISSUED A COPY OF THE FEBC, SECTION 900, CHANGE OF
 OCCUPANCY TO MR. CLARK AND REVIEWED THE SAME WITH HIM.
 I ADVISED HIM THAT HE WILL NEED TO SUBMIT 2 SETS OF
 PLANS TO THE CSD THAT COMPLY WITH THE MINIMUM
 REQUIREMENTS OF THE FORMER SECTION AND THAT IT MAY
 PROVE ADVANTAGEOUS FOR HIM TO RETAIN A LICENSED DESIGN
 PROFESSIONAL TO GENERATE THESE PLANS.
  
 5) MR. CLARK CHANGED THE APPLICATION PROJECT SCOPE:
 CHANGE FROM FUNERAL HOME TO A BAR AND GRILL TO, "
 CHANGE FROM FUNERAL HOME TO BAR".
  
 6) MR. CLARK INFORMED ME THAT HE SHOULD HAVE THE PLANS
 SUBMITTED WITHIN 24 HOURS.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-10-11 Cont ID  
Sent By dpalmer Date 2009-10-11 Time 11:32 Rev Time 0.00
Received By dpalmer Date 2009-10-11 Time 11:32 Sent To  
Notes
2009-10-11 11:32:58 
 ** DENIED **
  
 **** THE ELECTRICAL PERMIT AS APPLIED UNDER 09090346 IS
 BEING PLACED ON HOLD. NO CODE COMPLIANCE SHOWN FOR
 CHANGE IN OCCUPANCY.
  
 1) NOTE: THIS IS A CHANGE IN OCCUPANCY WHICH MUST BE
 APPLIED FOR UNDER PERMIT BY LICENSED CONTRACTOR.
 APPROPRIATE VALUE FOR SCOPE OF WORK NEEDS TO BE ON
 APPLICATION FOR VERIFICATION PER FBC 108.3.
  
 2) NOTE: A BATHROOM IS SHOWN IN THE ELECTRICAL ROOM.
 THIS IS NOT A LOCATION WHICH IS PERMITTED TO BE
 ACCESSED BY UNQUALIFIED PERSONS. BOTH DOORS SHOWN
 APPEAR THEY WOULD ACTUALLY HIT EACH OTHER?
  
 3) NOTE: PLEASE SEE FBC EXISTING BUILDING CODE 2007
 EDITION WITH 2009 SUPPLEMENTS CHAPTER 9, 908 FOR
 CHANGES IN OCCUPANCY. THIS REQUIRES THE ELECTRICAL TO
 MEET CHAPTER 27 OF THE FBC. PLANS NEED TO BE SUBMITTED
 SHOWING ELECTRICAL, ELECTRICAL SERVICE, SERVICE
 LOCATIONS, PANEL LOCATIONS, WIRING, BRANCH CIRCUITS,
 LOADS, CIRCUITING ETC MEETING CURRENT CODE.
 PLEASE SEE 110.26, 110.9, 210, 215.5, 215.3,240, 220,
 230,240, 310, 408.4 ETC. SOME CODE SECTIONS ARE GIVEN
 IN GENERAL AS NO ELECTRICAL PLANS WERE SUBMITTED. THE
 ELECTRICAL ROOM/LOCATION SHOWN IS OF CONCERN.
 PLEASE SEE 700.12F FOR WIRING OF EMERGENCY AND EXIT
 LIGHTS SEE COMMENTS BELOW ABOUT EGRESS LIGHTING.
  
 4) NOTE: PLEASE SEE FBC 13-101.3.2, FOR CHANGES IN
 OCCUPANCY UNDER ENERGY CODE EFFICIENCY REQUIREMENTS.
 PLEASE SUBMIT ACCORDINGLY.
  
 5) NOTE: PLEASE SHOW MINIMUM EGRESS LIGHTING
 REQUIREMENTS PER NFPA-101 7.8, 7.9. PLEASE BE SURE TO
 SEE NOTES ABOVE WITH RESPECT TO WIRING OF EMERGENCY AND
 EXIT LIGHT FIXTURES PER 700.12F OF THE NEC.
 PLANS CONTAIN A NOTE THAT LIGHTING SHALL BE PROVIDED
 HOWEVER NO ELECTRICAL PLANS AND DETAILS WERE SUBMITTED.
  
 6) NOTE: WHEN SUBMITTING RELEVANT PLANS SHOWING THE
 ABOVE MINIMUM REQUIREMENTS MEETING CODE PLEASE BE SURE
 THE FOLLOWING CODES ARE LISTED ON PLANS FOR THIS
 REVIEW.
 2005 NFPA-70 ( NEC)
 2006 NFPA-101
 2002 NFPA-72 ( IF APPLICABLE, SEE COMMENTS FROM FIRE
 REVIEW AND BUILDING REVIEW IF A SYSTEM IS REQUIRED.
  
  
 7) NOTE: WHEN RESUBMITTING DOCUMENTS, PLEASE BE SURE TO
 SUBMIT TWO COPIES OF ALL PLANS AND DOCUMENTS. FBC 106.1
 ONLY ONE SET SUBMITTED.
  
 ** IT IS IMPORTANT TO KNOW THAT AS NO MINIMUM PLANS
 WERE SUBMITTED FOR REVIEW THE FOLLOWING REVIEW MAY
 CREATE NEW COMMENTS WHICH CAN NOT BE MADE AT THIS TIME.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-10-21 Cont ID  
Sent By mcarsill Date 2009-10-21 Time 08:32 Rev Time 0.00
Received By mcarsill Date 2009-10-21 Time 08:04 Sent To  
Notes
2009-10-21 08:31:591600 NORTH DIXIE HIGHWAY
  
 1. THE BUILDING WILL BE REQUIRED TO BE COMPLETELY FIRE
 SPRINKLER PROTECTED. THE PLANS SUGGESTS THAT DIFFERENT
 OCCUPANT LOADS EXIST. ONE OCCUPANT LOAD IS STATED ON
 THE PLANS AND ANOTHER ONE REFERS TO INSURANCE
 REGULATIONS. IN EITHER CASE THESE NUMBERS HAVE NO
 BEARING OF THE AVAILABLE SPACE AND THE CAPACITY. THE
 OCCUPANT LOAD SHOWN ON THE PLANS IS INCORRECT.
  
 2. CROWD MANAGERS ARE REQUIRED IN ASSEMBLY OCCUPANCIES
 WITH OCCUPANT LOADS OF 250 OR MORE PERSONS. PLEASE GO
 MARYLAND STATE FIRE MARSHALS OFFICE AND CLICK THE
 ON-LINE CROWD MANAGEMENT TRAINING ICON, WATCH THE
 VIDEO, COMPLETE THE TEST, AND SUBMIT THE CERTIFICATE TO
 THIS OFFICE. THIS IS A MINIMUM CODE REQUIREMENT OF THE
 FLORID FIRE PREVENTION CODE. THE ON-LINE COURSE IS FREE
 AND ONLY TAKES A FEW MINUTES.
  
 3. ALL EXIT DOORS SUBJECT TO AN OCCUPANT LOAD OF 100 OR
 MORE PERSONS SHALL BE EQUIPPED WITH PANIC HARDWARE. NO
 OTHER LOCKS OR LATCHES ARE PERMITTED. THE PLANS SEEM TO
 SUGGEST ON DOOR WITH PANIC HARDWARE.
  
 4. PLANS DO NOT ILLUSTRATE ANY MECHANICAL, ELECTRICAL,
 PLUMBING, FIRE SPRINKLER OR FIRE ALARM SYSTEM DRAWINGS.
 NO ILLUMINATED EXIT SIGNS OR EMERGENCY LIGHT FIXTURES
 ARE ILLUSTRATED ON THE DRAWINGS.
  
 5. PLANS DO NOT INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS WITHIN THE
 ASSEMBLY OCCUPANCY. MINIMUM FLAME SPREAD REQUIREMENTS
 FOR WALLS AND CEILINGS MATERIALS ARE REQUIRED AND SHALL
 BE DOCUMENTED ON THE PLANS.
  
 6. AT LEAST TWO EXIT DOORS ARE DISPLAYED THAT ARE
 ACCESSED FROM VACANT SPACE WITH DOORS. HOW IS EXIT
 ACCESS MAINTAINED AND CONTROLLED IN THESE AREAS.
  
 7. THE FLOOR PLAN IS VERY CONFUSING AS TO WHAT EXIT
 STRATEGY WILL BE EMPLOYED AT THE FACILITY. NUMEROUS
 WALLS AND HALLWAYS EXIST WHERE EXITING DOES NOT APPEAR
 TO BE CLEAR. A MINIMUM NUMBER OF OCCUPANTS ARE EXPECTED
 TO EXIT THROUGH THE MAIN EXIT DOORS. THE 50 PERCENT
 DISCHARGE CODE OF THE TOTAL OCCUPANT LOAD CANNOT BE
 ACHIEVED AS SHOWN.
  
 8. PLEASE INDICATE SEATING ACCOMMODATIONS FOR THE
 HANDICAPPED.
  
 9. SEPARATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 SPRINKLER AND FIRE ALARM SYSTEMS.
  
 10. THE FIRE SPRINKLER SYSTEM AND FIRE ALARM SYSTEM
 SHALL BE MONITORED BY A UL LISTED CENTRAL STATION
 APPROVED FOR CENTRAL STATION SERVICE.
  
 11. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY HOOD,
 DUCT, AND FIRE SUPPRESSION SYSTEMS FOR THE KITCHEN
 AREA.
  
 12. PLEASE INDICATE TYPE OF CONSTRUCTION OF PLATFORM.
 IS THE PLATFORM PERMANENT OR TEMPORARY.
  
 13. PLEASE INDICATE THE LOCATIONS OF ANY RAMPS OR
 STAIRS FROM PLATFORM.
  
 14. TACTILE SIGN REQUIRED AT EXIT DOORS.
  
 DENIED.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 WEST PALM BEACH FIRE RESCUE
 BUREAU OF FIRE PREVENTION
 500 NORTH DIXIE HIGHWAY
 WEST PALM BEACH, FLORIDA 33401
 (561) 804-4709 PHONE
 (561) 804-4774 FAX
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-07-30 Time   Rev Time 0.00
Received By rmcdouga Date 2009-09-30 Time 13:59 Sent To  
Notes
2009-09-30 14:00:01B-16

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-10-17 Cont ID  
Sent By rregueir Date 2009-10-17 Time 13:50 Rev Time 0.00
Received By rregueir Date 2009-10-17 Time 13:43 Sent To  
Notes
2009-10-17 13:50:51REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NO INFORMATION REGARDING THE EXISTING VENTILATION
 SYSTEM OR VENTILATION RATES WAS PROVIDED. WHERE THE
 OCCUPANCY OF AN EXISTING BUILDING OR PART OF AN
 EXISTING BUILDING IS CHANGED SUCH THAT THE NEW
 OCCUPANCY IS SUBJECT TO DIFFERENT KITCHEN EXHAUST
 REQUIREMENTS OR TO INCREASED MECHANICAL VENTILATION
 REQUIREMENTS IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, MECHANICAL , THE INTENT OF THE RESPECTIVE FLORIDA
 BUILDING CODE, MECHANICAL PROVISIONS SHALL BE COMPLIED
 WITH FOR THE NEW OCCUPANCY PER FBC-EB 909.1. PROVIDE
 VANTILATION CALCULATIONS BASED ON FBC-M TABLE 403.3 FOR
 THE NEW OCCUPANCY, BASED ON THE OCCUPANCY
 CLASSIFICATIONS FOUND IN TE TABLE AND SHOW HOW THE
 REQUIRED RATES OF VENTILATION ARE TO BE PROVIDED IN
 ACCORDANCE WITH FBC-M SECTION 403.
  
 NOTE: ANY FUTURE COMMERCIAL KITCHEN VENTILATION SYSTEM
 MAY BE APPLIED FOR UNDER SEPARATE PERMIT AT A LATER
 DATE (PRIOR TO INSTALLATION).
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-10-14 Cont ID  
Sent By kstevens Date 2009-10-14 Time 16:48 Rev Time 0.00
Received By kstevens Date 2009-10-14 Time 16:48 Sent To  
Notes
2009-10-14 17:03:27DENIED
 REFERENCE:
 FBC-2007 EXISTING BUILDING
 FBC-2007 PLUMBING
 FBC-2007 CHAPTER 1
 FBC-2007 CHAPTER 11
  
 1. SHT A-3 PER TABLE 1004.1.1 (BLDG) 1,091 SF
 UNCONCENTRATED EQUALS 73 OCCUPANTS, 15 SF CONCENTRATED
 EQUALS 44 OCCUPANTS & 2541 SF STANDING EQUALS 509
 OCCUPANTS FOR A TOTAL OF 636 OCCUPANTS. 636 DIVIDED BY
 2 EQUALS 313 DIVIDED BY 40 EQUALS 8 MALE & 8 FEMALE
 WATER CLOSETS REQUIRED, 9 TOTAL LAVS REQUIRED, 1
 DRINKING FOUNTAIN, & 1 SERVICE SINK, (PER TABLE 403.1
 PLMG). SEE SECTION 910.1 EXISTING BUILDING CODE. -- THE
 OCCUPANCY LOAD IS NOT TO BE DETERMINED BY INSURANCE
 LIMITATIONS.
  
 2, PER SECTION 906.1 ACCESSIBILITY IN PORTIONS OF
 BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH CHAPTER 11 OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3. PER SECTION 106.3.5.1.3 A WATER ISOMETRIC RISER
 DIAGRAM & A SANITARY ISOMETRIC RISER DIAGRAM ARE
 REQUIRED. FOR THE WATER RISER DIAGRAM SHOW ALL PIPE
 SIZES, VALVES AND (WHERE REQUIRED), WATER HAMMER
 ARRESTORS. FOR THE SANITARY RISER DIAGRAM SHOW ALL PIPE
 SIZES, TRAPS, VENTS ETC. SECTIONS 601, 701, 901 & 1001.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-10-05 Cont ID  
Sent By eschneid Date 2009-10-05 Time 12:01 Rev Time 0.50
Received By eschneid Date 2009-10-05 Time 11:53 Sent To  
Notes
2009-10-05 12:08:46FAILED
  
 1) WHAT IS THE SCOPE AND COST OF WORK FOR THIS PERMIT?
  
 2) THE SITE PLAN SHOWS DIFFERENT CONDITIONS THAN THE
 2009 AERIALS. PROVIDE A SURVEY THAT IS LESS THAN ONE
 YEAR OLD.
  
 3) THERE IS NO PERMIT TO RESTRIPE THE PARKING AS SHOWN
 ON THE PLAN.
  
 4) THE LANDSCAPE IS SHOWN INCORRECTLY ON THE SITE PLAN,
 BOTH ON AND OFF SITE.
  
 5) THE BUSINESS TAX/CERTIFICATE OF USE APPLICATION
 SIGNED BY ZONING IS FOR A BAR AND GRILLE. THIS PERMIT
 INDICATES THAT THE KITCHEN IS GONE. THIS MAY REQUIRE A
 CHANGE TO THE BUSINESS TAX/CERTIFICATE OF USE
 APPLICATION TO REMOVE THE GRILLE.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.