Plan Review Details - Permit 09070624
Plan Review Stops For Permit 09070624
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-08-04 Cont ID  
Sent By jwitmer Date 2009-08-04 Time 11:54 Rev Time 1.55
Received By jwitmer Date 2009-08-04 Time 09:10 Sent To E
Notes
2009-08-04 12:12:33FL# 10605-R0
 NOA# 07-0803.01
 ADVANCED GREEN TECHNOLOGIES, INC
 ROOF PERMITED WITH BASE BUILDING
 ATLANTIC & CARIBBEAN ROOF CONSULTING
 NOA# 08-0221.02
 PAGES 20,21
 PAGE 21 SURFACING COMMENT# 7 ALLOWS ADVANCED GREEN
 TECHNOLOGIES PHOTOVOLTAIC LAMINATE ROOF SYSTEMS ,
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-09-15 Cont ID  
Sent By dpalmer Date 2009-09-15 Time 17:57 Rev Time 0.00
Received By dpalmer Date 2009-09-15 Time 17:57 Sent To PC
Notes
2009-09-15 17:57:44 
 ** PROVISO **
  
  
 1) NOTE: FINAL APPROVAL OF INTERCONNECTION DOCUMENTS
 FROM FLORIDA POWER AND LIGHT TO BE SUBMITTED FOR FILE.
  
 2) NOTE: REDLINED PLANS: THE OPTIONAL METER SHOWN ON
 RISER WHICH IS NOTED TO BE INSTALLED BY OTHERS SHALL BE
 UNDER SEPARATE PERMIT IF NOT INSTALLED BY FPL.
 RISER SHALL BE REVISED BEFORE FINAL IN ORDER TO REFLECT
 ACCURATELY WHAT WAS INSTALLED EVEN IF INSTALLED BY
 OTHERS.
 ONLY WORK DONE AND INSTALLED BY THE UTILITY COMPANY IS
 EXEMPT FROM PERMITTING. ALL OTHER WORK SHALL OBTAIN
 PERMIT.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-09-08 Cont ID  
Sent By dpalmer Date 2009-09-08 Time 11:00 Rev Time 0.00
Received By dpalmer Date 2009-09-08 Time 11:00 Sent To PC
Notes
2009-09-08 11:01:10** DENIED REVIEW **
  
 ** COMMENTS #1 AND #2 FROM PREVIOUS REVIEW ARE STILL IN
 NEED OF ADDRESSING.
  
 1) NOTE: NO PRODUCT CUT SHEETS/SPECS SUBMITTED. 110.3
  
 2) NOTE: NO LETTER SUBMITTED FROM FPL THAT INSTALLATION
 WILL MEET THEIR SERVICE STANDARDS. PLANS NOW STATE THAT
 A UTILITY BI-DIRECTIONAL METER WILL BE INSTALLED BY
 OTHERS.
 THE APPLIED SCOPE OF WORK IS NOT PERMITTED UNTIL
 SERVICE WORK IS CLEARED UP.
 THIS IS A 1000AMP SERVICE.
  
 3) NOTE: SHOW LOCATIONS OF DISCONNECTING MEANS MEETING
 690.13,14,15, 230.2E
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-08-12 Cont ID  
Sent By dpalmer Date 2009-08-12 Time 10:52 Rev Time 0.00
Received By dpalmer Date 2009-08-12 Time 10:51 Sent To  
Notes
2009-08-12 10:55:05 
 ** DENIED REVIEW **
  
 1) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE PROPOSED PHOTOVOLTAIC SYSTEM. PLEASE BE
 SURE LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY IS SHOWN. ( NRTL) 110.3
  
 2) NOTE: PLEASE SEE PHOTOVOLTAIC RISER WHICH INDICATES
 THE SERVICE AS HAVING A *MULTI-DIRECTIONAL METER*.
 BASED ON THE ORIGINAL RISER AND PLANS THIS IS A 1000AMP
 SERVICE. HOW DOES THIS SIZE SERVICE HAVE A
 MULTI-DIRECTIONAL METER?
 PLEASE OBTAIN LETTER FROM LOCAL POWER COMPANY FLORIDA
 POWER AND LIGHT ( FPL) FOR THE INSTALLATION MEETING
 SERVICE STANDARDS.
  
 3) NOTE: PLEASE SEE NOTES ON PLANS MENTIONS COLOR
 CODING FROM THE 1990 NATIONAL ELECTRICAL CODE. (
 SPECIFICALLY) PLEASE BE SURE TO REVISE.
 THE PLANS ARE UNDER THE 2005 NEC.
  
 4) NOTE: PLEASE INDICATE PROTECTION PER 690.6 (D).
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-09-14 Cont ID  
Sent By lmartine Date 2009-09-14 Time 16:00 Rev Time 0.00
Received By lmartine Date 2009-09-14 Time 16:00 Sent To  
Notes
2009-09-14 16:01:49***EXPEDITED**** GAVE TO DEWEY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-08-27 Cont ID  
Sent By lmartine Date 2009-08-27 Time 09:26 Rev Time 0.00
Received By lmartine Date 2009-08-27 Time 09:26 Sent To  
Notes
2009-08-27 09:27:05GAVE TO DEWEY

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-08-12 Time   Rev Time 0.00
Received By jgomez Date 2009-07-28 Time 13:01 Sent To  
Notes
2009-07-28 13:01:31SENT TO COMMERCIAL BOX # C-11

Review Stop Z ZONING
Rev No 1 Status N Date 2009-08-07 Cont ID  
Sent By astelly Date 2009-08-07 Time 19:31 Rev Time 0.00
Received By astelly Date 2009-08-07 Time 19:31 Sent To  
Notes
***NONE***