Plan Review Details - Permit 09070587
Plan Review Stops For Permit 09070587
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-11-17 Cont ID  
Sent By rmcdouga Date 2009-11-17 Time 14:43 Rev Time 0.00
Received By rmcdouga Date 2009-11-17 Time 14:43 Sent To  
Notes
2009-11-17 14:44:29PROCESS PLANS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-11-16 Cont ID  
Sent By rmcdouga Date 2009-11-16 Time 11:48 Rev Time 0.00
Received By rmcdouga Date 2009-11-16 Time 11:48 Sent To  
Notes
2009-11-16 11:54:052007 FBC W/2007 REVISIONS
  
 BUILDING PROVISO
  
 1) SUBMIT TWO SETS OF REVISED SHEET A1 WITH A CORRECTED
 SITE PLAN THAT CORRESPONDS TO THE SURVEY AND COMPLY
 WITH ZONING COMMENTS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-10-27 Cont ID  
Sent By rmcdouga Date 2009-10-27 Time 09:45 Rev Time 0.00
Received By rmcdouga Date 2009-10-27 Time 06:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-08-14 Cont ID  
Sent By rmcdouga Date 2009-08-14 Time 14:16 Rev Time 0.00
Received By rmcdouga Date 2009-08-14 Time 14:16 Sent To  
Notes
2009-08-14 15:30:272007 FBC W/2009 REVISIONS
 ADDITION
  
 DENIED BY BUILDING
  
 1) NOTE: IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) UPDATE REFERENCES TO THE 2007 FBC W/2009 REVISIONS.
 SHEETS A1 AND A3 SPECIFY THE 2004 FBC.
  
 3) ON SHEET A3 ONE OF THE NOTES FOR THE TYPICAL WALL
 SECTION APPEARS TO BE MISSING SOME OF THE TEXT. IT
 STATES " 8'- 0" O.C. W/ 8D NAILS. PLEASE CLARIFY.
  
 4) SHOW COMPLIANCE WITH FBC R313.4 FOR CARBON MONOXIDE
 PROTECTION.
  
 5) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY CALCULATION FORMS. 2007 ENERGY GLITCH AMENDMENTS
 N1100.2.2
  
 6) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) ON THE DOOR SCHEDULE ON A3 THE OPENING WITH FOR THE
 16' WIDE GARAGE DOOR IS SPECIFIED AS 108" (9') WIDE.
  
 8) SUBMIT PRODUCT APPROVALS FOR THE TRUSS CONNECTORS OR
 SPECIFY THE NOA OR FL# ON THE PLANS. DCA RULE 9B-72
  
 9) SUBMIT PRODUCT APPROVALS FOR THE 8" PRECAST CONCRETE
 LINTELS. DCA RULE 9B-72
  
 10) THE NEW FRONT DOOR SHOWN ON THE PLANS HAS SIDELITES
 AND IS GLAZED. THE PRODUCT APPROVAL SUBMITTED FOR THE
 DOORS IS FOR UNGLAZED DOORS WITH NON-IMPACT RATED
 SIDELITES. SUBMIT PRODUCT APPROVALS FOR IMPACT RATED
 FRONT DOOR ASSEMBLY OR PRODUCT APPROVALS FOR THE IMPACT
 PROTECTION THAT WILL BE INSTALLED.
  
 11) PROVIDE A CONSTRUCTION DETAIL FOR THE ARCH AT THE
 NEW ENTRY. FBC R601.2
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-10-22 Cont ID  
Sent By btrobaug Date 2009-10-22 Time 16:01 Rev Time 0.00
Received By btrobaug Date 2009-10-22 Time 12:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-08-13 Cont ID  
Sent By btrobaug Date 2009-08-13 Time 13:15 Rev Time 0.00
Received By btrobaug Date 2009-08-13 Time 12:21 Sent To  
Notes
2009-08-13 13:11:45THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 9B-3.0472 CARBON MONOXIDE PROTECTION.
 (1) EVERY BUILDING FOR WHICH A PERMIT FOR NEW
 CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A
 FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE,
 OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON
 MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM
 USED FOR SLEEPING PURPOSES. COMBINATION SMOKE/CARBON
 MONOXIDE ALARMS SHALL BE LISTED OR LABELED BY A
 NATIONALLY RECOGNIZED TESTING LABORATORY.
  
 2} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.2
 RESIDENTIAL FLORIDA BUILDING CODE.
  
 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI
 PROTECTED PER 210.8(A) (1).***THE ADDED BATH DOES NOT
 COMPLY WITH SPACING.ALSO THE NEW BATH CIRCUIT INDICATES
 THE UTILITY ROOM LISTED ON THE PANEL SCHEDULE IN
 VIOLATION OF 210.11(C)(3).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-11-03 Cont ID  
Sent By rmcdouga Date 2009-11-03 Time 11:18 Rev Time 0.00
Received By rmcdouga Date 2009-11-03 Time 11:18 Sent To  
Notes
2009-11-03 11:19:02TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-10-20 Cont ID  
Sent By shill Date 2009-10-20 Time 16:54 Rev Time 0.00
Received By shill Date 2009-10-20 Time 16:54 Sent To  
Notes
2009-10-20 16:54:28R19
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-08-14 Cont ID  
Sent By rmcdouga Date 2009-08-14 Time 16:32 Rev Time 0.00
Received By rmcdouga Date 2009-07-24 Time 16:27 Sent To  
Notes
2009-07-24 16:27:42R-18

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2009-11-17 Cont ID  
Sent By rmcdouga Date 2009-10-27 Time 09:50 Rev Time 0.00
Received By rmcdouga Date 2009-10-27 Time 09:50 Sent To  
Notes
2009-10-27 09:53:07STATUS WILL BE CHANGED TO 'P' WHEN PLANS HAVE BEEN
 STAMPED BY PALM BEACH COUNTY AND COPY OF PAID RECEIPT
 IS SUBMITTED. OWNER/AGENT NEEDS TO SIGN ENERGY
 CALCULATIONS.
2009-09-30 11:53:05R19
  

Review Stop L LANDSCAPING
Rev No 3 Status P Date 2009-11-03 Cont ID  
Sent By rkussner Date 2009-11-03 Time 17:03 Rev Time 0.00
Received By rkussner Date 2009-11-03 Time 17:03 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2009-10-07 Cont ID  
Sent By rkussner Date 2009-10-07 Time 14:47 Rev Time 0.00
Received By rkussner Date 2009-10-07 Time 14:47 Sent To  
Notes
2009-10-07 14:57:12***LANDSCAPE REVIEW FAILED***
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENT IN WRITTEN
 FORMAT.
  
 1. SUBMIT COST ESTIMATE THAT INCLUDES THE TOTAL COST OF
 ALL LANDSCAPE MATERIALS AND LABOR. IT SHALL BE BROKEN
 DOWN INTO UNIT COST.
  
 2. REPEAT COMMENT: PLEASE PROVIDE THE TABULATION
 NECESSARY FOR THE EVALUATION OF COMPLIANCE WITH ARTICLE
 XIV OF THE ZONING AND LAND DEVELOPMENT REGULATIONS,
 INCLUDING THE XERISCAPE DESIGN OPTIONS.
  
 3. TREES IN THE RIGHT-OF-WAY CANNOT BE COUNTED TOWARD
 MEETING THE REQUIREMENTS OF ARTICLE XIV. TREES THAT
 WILL BE COUNTED TOWARD MEETING THE REQUIREMENT SHALL BE
 ACCCURATELY IDENTIFIED BY NAME AND SIZE.
  
 4. PROVIDE SIZE AND SPACING FOR ALL PROPOSED PLANT
 MATERIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-07-29 Cont ID  
Sent By rkussner Date 2009-07-29 Time 15:34 Rev Time 0.00
Received By rkussner Date 2009-07-29 Time 15:34 Sent To  
Notes
2009-07-29 17:02:53***LANDSCAPE REVIEW FAILED***
  
 1. PURSUANT TO SECTION 94-441 (B), BECAUSE THE
 RENOVATION EXCEEDS 50 PERCENT OF THE VALUE OF THE
 STRUCTURE, THE ENTIRE LANDSCAPING OF THE SITE SHALL BE
 BROUGHT UP TO CURRENT STANDARDS.
  
 2. SUBMIT A LANDSCAPE PLAN THAT MEETS ALL REQUIREMENTS
 SETFORTH IN ARTICLE XIV OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS. SHOW ALL EXISTING AND PROPOSED
 PLANT MATERIAL. THE LANDSCAPE PLAN SHALL CONTAIN ALL
 THE ITEMS LISTED IN SECTION 94-448 (D).
  
 3, PLEASE PROVIDE THE TABULATION NECESSARY FOR THE
 EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING
 AND LAND DEVELOPMENT REGULATIONS, INCLUDING THE
 XERISCAPE DESIGN OPTIONS.
  
 4. A LANDSCAPE PERMIT IS REQUIRED. PLEASE SUBMIT A COST
 ESTIMATE THAT INCLUDES THE TOTAL COST OF ALL LANDSCAPE
 MATERIALS AND LABOR, BROKEN DOWN INTO UNIT COST.
  
 5. AN IRRIGATION PERMIT IS REQUIRED. ALL LANDSCAPED
 AREAS SHALL RECEIVE 120% IRRIGATION COVERAGE, INCLUDING
 THE RIGHT-OF-WAY. THE IRRIGATION PLAN SHALL IDENTIFY
 ALL COMPONENTS OF THE SYSTEM AND SHOW THE LAYOUT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-10-27 Cont ID  
Sent By rmcdouga Date 2009-10-27 Time 10:56 Rev Time 0.00
Received By rmcdouga Date 2009-10-27 Time 10:56 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-08-04 Cont ID  
Sent By rregueir Date 2009-08-04 Time 13:38 Rev Time 0.00
Received By rregueir Date 2009-08-04 Time 11:08 Sent To  
Notes
2009-08-04 13:38:00REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. A MECHANICAL PERMIT HAS BEEN APPLIED FOR, YET NO
 MECHANICAL SCOPE OF WORK IS SHOWN ON PLANS. DUCT
 SYSTEMS SHALL BE DESCRIBED IN SUFFICIENT DETAIL TO
 ALLOW THE BUILDING OFFICIAL TO DETERMINE CODE
 COMPLIANCE IN ACCORDANCE WITH FBC-R SECTION N1110.A.1.
  
 2. EVERY BUILDING FOR WHICH A PERMIT FOR NEW
 CONSTRUCTION IS ISSUED HAVING A FOSSIL-FUEL-BURNING
 HEATER OR APPLIANCE, A FIREPLACE, OR AN ATTACHED GARAGE
 SHALL HAVE AN OPERATIONAL CARBON MONOXIDE ALARM
 INSTALLED WITHIN 10 FEET OF EACH ROOM USED FOR SLEEPING
 PURPOSES IN ACCORDANCE WITH FBC-R313.4.
  
 3. PAGE A2 SHOWS NEW BATH EXHAUST FAN. SHOW LOCATION OF
 EXHAUST DUCT TERMINATION AND DISCHARGE LOCATION IN
 ACCORDANCE WITH FBC-R303.4 AND FBC-R SECTION M1501.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-10-26 Cont ID  
Sent By rmcdouga Date 2009-10-26 Time 15:20 Rev Time 0.00
Received By rmcdouga Date 2009-10-26 Time 15:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-08-14 Cont ID  
Sent By rmcdouga Date 2009-08-14 Time 15:30 Rev Time 0.00
Received By rmcdouga Date 2009-08-14 Time 15:30 Sent To  
Notes
2009-08-14 16:31:142007 FBC W/2009 REVISIONS
 ADDITION
  
 DENIED BY PLUMBING
  
 1) THE PLUMBING RISER ON SHEET A1 DOES NOT CORRESPOND
 WITH THE FLOOR PLAN. TWO SINKS ARE SHOWN ON THE RISER
 PLAN AND ONE LAVATORY IS SHOWN ON THE FLOOR PLAN.
  
 2) SPECIFY ALL OF THE PIPE SIZES ON THE RISER PLANS.
 FBC R P 3005.4 AND P3113.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2009-11-17 Cont ID  
Sent By lfranco Date 2009-11-17 Time 14:02 Rev Time 0.00
Received By lfranco Date 2009-11-17 Time 14:02 Sent To B
Notes
2009-11-17 14:04:24PLANNING AND ZONING: **** PASSED ****
  
 11/17/09 ROUTED TO RMCD FOR PROCESSING. LMF
 11/17/09 CUSTOMER CAME IN W/REVISED SHEET A-1 SHOWING
 DIMS, S&S BY LUIS LOPEZ, P.E. OKAY TO SWITCH SHEETS PER
 LMARTINEZ. LMF

Review Stop Z ZONING
Rev No 3 Status F Date 2009-11-16 Cont ID  
Sent By lfranco Date 2009-11-16 Time 10:54 Rev Time 0.00
Received By lfranco Date 2009-11-16 Time 10:53 Sent To B
Notes
2009-11-16 11:12:47PLANNING AND ZONING DEPT: *** FAILED ***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
  
 2. COMMENT NOT ADDRESSED. THE SITE PLAN NEEDS TO SHOW
 THE CORRECT DIMENSIONS. CORRECTIONS TO SITE PLAN CANNOT
 BE MADE BY OTHERS OR AFTER IT HAS BEEN SIGNED AND
 SEALED, UNLESS THEY ARE DONE BY THE ENGINEER OF RECORD
 (LUIS A. LOPEZ). THE PLANS HAVE ALREADY BEEN STAMPED BY
 BUILDING. RESUBMIT SHEET A-1 TO ADDRESS COMMENTS.
  
 SHEET A-1, SITE PLAN SIDE SETBACK DIMENSIONS DO NOT
 MATCH SURVEY SUBMITTED DATED 7/13/09. REVISE
 ACCORDINGLY. PROVIDE SETBACKS FROM ALL PROPERTY LINES,
 MISSING NORTH SIDE SETBACK.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 2009-10-15 Cont ID  
Sent By lfranco Date 2009-10-15 Time 16:33 Rev Time 0.00
Received By lfranco Date 2009-10-15 Time 16:20 Sent To  
Notes
2009-10-15 16:34:22PLANNING AND ZONING DEPT: *** FAILED ***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. SHEET A-1, SITE PLAN SIDE SETBACK DIMENSIONS DO NOT
 MATCH SURVEY SUBMITTED DATED 7/13/09. REVISE
 ACCORDINGLY. PROVIDE SETBACKS FROM ALL PROPERTY LINES,
 MISSING NORTH SIDE SETBACK.
  
 3. LANDSCAPE COMMENTS ARE STILL OUTSTANDING:
  
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), SECTION 94-441(C)(2)
 OF: AS THE VALUE OF THE PROPOSED WORK EXCEEDS 50% OF
 THE STRUCTURE'S VALUE (LISTED AS "IMPROVEMENT VALUE"
 WITH THE P.B.C. PROPERTY APPRAISER'S OFFICE),
 LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 LINDA MIA FRANCO
 SENIOR PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1443
 E-MAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2009-08-04 Cont ID  
Sent By mcruz Date 2009-08-04 Time 15:38 Rev Time 0.00
Received By mcruz Date 2009-08-04 Time 14:57 Sent To  
Notes
2009-08-04 15:38:38PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-441(C)(2) OF: AS THE VALUE OF THE PROPOSED WORK
 EXCEEDS 50% OF THE STRUCTURE'S VALUE (LISTED AS
 "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  