| Plan Review Stops For Permit 09070587 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2009-11-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-11-17 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-11-17 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2009-11-17 14:44:29 | PROCESS PLANS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2009-11-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-11-16 |
Time |
11:48 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-11-16 |
Time |
11:48 |
Sent To |
|
|
| Notes |
| 2009-11-16 11:54:05 | 2007 FBC W/2007 REVISIONS | | | | | | BUILDING PROVISO | | | | | | 1) SUBMIT TWO SETS OF REVISED SHEET A1 WITH A CORRECTED | | | SITE PLAN THAT CORRESPONDS TO THE SURVEY AND COMPLY | | | WITH ZONING COMMENTS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2009-10-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-10-27 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-10-27 |
Time |
06:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-08-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-08-14 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-08-14 |
Time |
14:16 |
Sent To |
|
|
| Notes |
| 2009-08-14 15:30:27 | 2007 FBC W/2009 REVISIONS | | | ADDITION | | | | | | DENIED BY BUILDING | | | | | | 1) NOTE: IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 2) UPDATE REFERENCES TO THE 2007 FBC W/2009 REVISIONS. | | | SHEETS A1 AND A3 SPECIFY THE 2004 FBC. | | | | | | 3) ON SHEET A3 ONE OF THE NOTES FOR THE TYPICAL WALL | | | SECTION APPEARS TO BE MISSING SOME OF THE TEXT. IT | | | STATES " 8'- 0" O.C. W/ 8D NAILS. PLEASE CLARIFY. | | | | | | 4) SHOW COMPLIANCE WITH FBC R313.4 FOR CARBON MONOXIDE | | | PROTECTION. | | | | | | 5) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE | | | ENERGY CALCULATION FORMS. 2007 ENERGY GLITCH AMENDMENTS | | | N1100.2.2 | | | | | | 6) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | 7) ON THE DOOR SCHEDULE ON A3 THE OPENING WITH FOR THE | | | 16' WIDE GARAGE DOOR IS SPECIFIED AS 108" (9') WIDE. | | | | | | 8) SUBMIT PRODUCT APPROVALS FOR THE TRUSS CONNECTORS OR | | | SPECIFY THE NOA OR FL# ON THE PLANS. DCA RULE 9B-72 | | | | | | 9) SUBMIT PRODUCT APPROVALS FOR THE 8" PRECAST CONCRETE | | | LINTELS. DCA RULE 9B-72 | | | | | | 10) THE NEW FRONT DOOR SHOWN ON THE PLANS HAS SIDELITES | | | AND IS GLAZED. THE PRODUCT APPROVAL SUBMITTED FOR THE | | | DOORS IS FOR UNGLAZED DOORS WITH NON-IMPACT RATED | | | SIDELITES. SUBMIT PRODUCT APPROVALS FOR IMPACT RATED | | | FRONT DOOR ASSEMBLY OR PRODUCT APPROVALS FOR THE IMPACT | | | PROTECTION THAT WILL BE INSTALLED. | | | | | | 11) PROVIDE A CONSTRUCTION DETAIL FOR THE ARCH AT THE | | | NEW ENTRY. FBC R601.2 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2009-10-22 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-10-22 |
Time |
16:01 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-10-22 |
Time |
12:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-08-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-08-13 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-08-13 |
Time |
12:21 |
Sent To |
|
|
| Notes |
| 2009-08-13 13:11:45 | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009 | | | REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} 9B-3.0472 CARBON MONOXIDE PROTECTION. | | | (1) EVERY BUILDING FOR WHICH A PERMIT FOR NEW | | | CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A | | | FOSSIL-FUEL-BURNING HEATER OR APPLIANCE, A FIREPLACE, | | | OR AN ATTACHED GARAGE SHALL HAVE AN OPERATIONAL CARBON | | | MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM | | | USED FOR SLEEPING PURPOSES. COMBINATION SMOKE/CARBON | | | MONOXIDE ALARMS SHALL BE LISTED OR LABELED BY A | | | NATIONALLY RECOGNIZED TESTING LABORATORY. | | | | | | 2} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.2 | | | RESIDENTIAL FLORIDA BUILDING CODE. | | | | | | 3} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE | | | PER 210.11(C) (3), LOCATED PER 210.52(D), AND BE GFI | | | PROTECTED PER 210.8(A) (1).***THE ADDED BATH DOES NOT | | | COMPLY WITH SPACING.ALSO THE NEW BATH CIRCUIT INDICATES | | | THE UTILITY ROOM LISTED ON THE PANEL SCHEDULE IN | | | VIOLATION OF 210.11(C)(3). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-11-03 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-11-03 |
Time |
11:18 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-11-03 |
Time |
11:18 |
Sent To |
|
|
| Notes |
| 2009-11-03 11:19:02 | TO ZONING BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-10-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-10-20 |
Time |
16:54 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-10-20 |
Time |
16:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2009-08-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-08-14 |
Time |
16:32 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-07-24 |
Time |
16:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
P |
Date |
2009-11-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-10-27 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-10-27 |
Time |
09:50 |
Sent To |
|
|
| Notes |
| 2009-10-27 09:53:07 | STATUS WILL BE CHANGED TO 'P' WHEN PLANS HAVE BEEN | | | STAMPED BY PALM BEACH COUNTY AND COPY OF PAID RECEIPT | | | IS SUBMITTED. OWNER/AGENT NEEDS TO SIGN ENERGY | | | CALCULATIONS. | | 2009-09-30 11:53:05 | R19 | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
3 |
Status |
P |
Date |
2009-11-03 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2009-11-03 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2009-11-03 |
Time |
17:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
F |
Date |
2009-10-07 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2009-10-07 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2009-10-07 |
Time |
14:47 |
Sent To |
|
|
| Notes |
| 2009-10-07 14:57:12 | ***LANDSCAPE REVIEW FAILED*** | | | | | | PLEASE PROVIDE RESPONSES TO REVIEW COMMENT IN WRITTEN | | | FORMAT. | | | | | | 1. SUBMIT COST ESTIMATE THAT INCLUDES THE TOTAL COST OF | | | ALL LANDSCAPE MATERIALS AND LABOR. IT SHALL BE BROKEN | | | DOWN INTO UNIT COST. | | | | | | 2. REPEAT COMMENT: PLEASE PROVIDE THE TABULATION | | | NECESSARY FOR THE EVALUATION OF COMPLIANCE WITH ARTICLE | | | XIV OF THE ZONING AND LAND DEVELOPMENT REGULATIONS, | | | INCLUDING THE XERISCAPE DESIGN OPTIONS. | | | | | | 3. TREES IN THE RIGHT-OF-WAY CANNOT BE COUNTED TOWARD | | | MEETING THE REQUIREMENTS OF ARTICLE XIV. TREES THAT | | | WILL BE COUNTED TOWARD MEETING THE REQUIREMENT SHALL BE | | | ACCCURATELY IDENTIFIED BY NAME AND SIZE. | | | | | | 4. PROVIDE SIZE AND SPACING FOR ALL PROPOSED PLANT | | | MATERIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT | | | KUSSNER @ (561) 822-1462. |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
2009-07-29 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2009-07-29 |
Time |
15:34 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2009-07-29 |
Time |
15:34 |
Sent To |
|
|
| Notes |
| 2009-07-29 17:02:53 | ***LANDSCAPE REVIEW FAILED*** | | | | | | 1. PURSUANT TO SECTION 94-441 (B), BECAUSE THE | | | RENOVATION EXCEEDS 50 PERCENT OF THE VALUE OF THE | | | STRUCTURE, THE ENTIRE LANDSCAPING OF THE SITE SHALL BE | | | BROUGHT UP TO CURRENT STANDARDS. | | | | | | 2. SUBMIT A LANDSCAPE PLAN THAT MEETS ALL REQUIREMENTS | | | SETFORTH IN ARTICLE XIV OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS. SHOW ALL EXISTING AND PROPOSED | | | PLANT MATERIAL. THE LANDSCAPE PLAN SHALL CONTAIN ALL | | | THE ITEMS LISTED IN SECTION 94-448 (D). | | | | | | 3, PLEASE PROVIDE THE TABULATION NECESSARY FOR THE | | | EVALUATION OF COMPLIANCE WITH ARTICLE XIV OF THE ZONING | | | AND LAND DEVELOPMENT REGULATIONS, INCLUDING THE | | | XERISCAPE DESIGN OPTIONS. | | | | | | 4. A LANDSCAPE PERMIT IS REQUIRED. PLEASE SUBMIT A COST | | | ESTIMATE THAT INCLUDES THE TOTAL COST OF ALL LANDSCAPE | | | MATERIALS AND LABOR, BROKEN DOWN INTO UNIT COST. | | | | | | 5. AN IRRIGATION PERMIT IS REQUIRED. ALL LANDSCAPED | | | AREAS SHALL RECEIVE 120% IRRIGATION COVERAGE, INCLUDING | | | THE RIGHT-OF-WAY. THE IRRIGATION PLAN SHALL IDENTIFY | | | ALL COMPONENTS OF THE SYSTEM AND SHOW THE LAYOUT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT | | | KUSSNER @ (561) 822-1462. | | | | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2009-10-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-10-27 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-10-27 |
Time |
10:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2009-08-04 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-08-04 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-08-04 |
Time |
11:08 |
Sent To |
|
|
| Notes |
| 2009-08-04 13:38:00 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. A MECHANICAL PERMIT HAS BEEN APPLIED FOR, YET NO | | | MECHANICAL SCOPE OF WORK IS SHOWN ON PLANS. DUCT | | | SYSTEMS SHALL BE DESCRIBED IN SUFFICIENT DETAIL TO | | | ALLOW THE BUILDING OFFICIAL TO DETERMINE CODE | | | COMPLIANCE IN ACCORDANCE WITH FBC-R SECTION N1110.A.1. | | | | | | 2. EVERY BUILDING FOR WHICH A PERMIT FOR NEW | | | CONSTRUCTION IS ISSUED HAVING A FOSSIL-FUEL-BURNING | | | HEATER OR APPLIANCE, A FIREPLACE, OR AN ATTACHED GARAGE | | | SHALL HAVE AN OPERATIONAL CARBON MONOXIDE ALARM | | | INSTALLED WITHIN 10 FEET OF EACH ROOM USED FOR SLEEPING | | | PURPOSES IN ACCORDANCE WITH FBC-R313.4. | | | | | | 3. PAGE A2 SHOWS NEW BATH EXHAUST FAN. SHOW LOCATION OF | | | EXHAUST DUCT TERMINATION AND DISCHARGE LOCATION IN | | | ACCORDANCE WITH FBC-R303.4 AND FBC-R SECTION M1501.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2009-10-26 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-10-26 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-10-26 |
Time |
15:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2009-08-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2009-08-14 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-08-14 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2009-08-14 16:31:14 | 2007 FBC W/2009 REVISIONS | | | ADDITION | | | | | | DENIED BY PLUMBING | | | | | | 1) THE PLUMBING RISER ON SHEET A1 DOES NOT CORRESPOND | | | WITH THE FLOOR PLAN. TWO SINKS ARE SHOWN ON THE RISER | | | PLAN AND ONE LAVATORY IS SHOWN ON THE FLOOR PLAN. | | | | | | 2) SPECIFY ALL OF THE PIPE SIZES ON THE RISER PLANS. | | | FBC R P 3005.4 AND P3113.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2009-11-17 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2009-11-17 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2009-11-17 |
Time |
14:02 |
Sent To |
B |
|
| Notes |
| 2009-11-17 14:04:24 | PLANNING AND ZONING: **** PASSED **** | | | | | | 11/17/09 ROUTED TO RMCD FOR PROCESSING. LMF | | | 11/17/09 CUSTOMER CAME IN W/REVISED SHEET A-1 SHOWING | | | DIMS, S&S BY LUIS LOPEZ, P.E. OKAY TO SWITCH SHEETS PER | | | LMARTINEZ. LMF |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2009-11-16 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2009-11-16 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2009-11-16 |
Time |
10:53 |
Sent To |
B |
|
| Notes |
| 2009-11-16 11:12:47 | PLANNING AND ZONING DEPT: *** FAILED *** | | | | | | 1. PLEASE PROVIDE ALL RESPONSES IN WRITING. | | | | | | | | | 2. COMMENT NOT ADDRESSED. THE SITE PLAN NEEDS TO SHOW | | | THE CORRECT DIMENSIONS. CORRECTIONS TO SITE PLAN CANNOT | | | BE MADE BY OTHERS OR AFTER IT HAS BEEN SIGNED AND | | | SEALED, UNLESS THEY ARE DONE BY THE ENGINEER OF RECORD | | | (LUIS A. LOPEZ). THE PLANS HAVE ALREADY BEEN STAMPED BY | | | BUILDING. RESUBMIT SHEET A-1 TO ADDRESS COMMENTS. | | | | | | SHEET A-1, SITE PLAN SIDE SETBACK DIMENSIONS DO NOT | | | MATCH SURVEY SUBMITTED DATED 7/13/09. REVISE | | | ACCORDINGLY. PROVIDE SETBACKS FROM ALL PROPERTY LINES, | | | MISSING NORTH SIDE SETBACK. | | | | | | NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY | | | GENERATE ADDITIONAL COMMENTS. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2009-10-15 |
|
|
Cont ID |
|
| Sent By |
lfranco |
Date |
2009-10-15 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
lfranco |
Date |
2009-10-15 |
Time |
16:20 |
Sent To |
|
|
| Notes |
| 2009-10-15 16:34:22 | PLANNING AND ZONING DEPT: *** FAILED *** | | | | | | 1. PLEASE PROVIDE ALL RESPONSES IN WRITING. | | | | | | 2. SHEET A-1, SITE PLAN SIDE SETBACK DIMENSIONS DO NOT | | | MATCH SURVEY SUBMITTED DATED 7/13/09. REVISE | | | ACCORDINGLY. PROVIDE SETBACKS FROM ALL PROPERTY LINES, | | | MISSING NORTH SIDE SETBACK. | | | | | | 3. LANDSCAPE COMMENTS ARE STILL OUTSTANDING: | | | | | | PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND | | | DEVELOPMENT REGULATIONS (ZLDR), SECTION 94-441(C)(2) | | | OF: AS THE VALUE OF THE PROPOSED WORK EXCEEDS 50% OF | | | THE STRUCTURE'S VALUE (LISTED AS "IMPROVEMENT VALUE" | | | WITH THE P.B.C. PROPERTY APPRAISER'S OFFICE), | | | LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE | | | REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. | | | | | | PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN | | | SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF | | | THE ZLDR. | | | | | | | | | NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY | | | GENERATE ADDITIONAL COMMENTS. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | LINDA MIA FRANCO | | | SENIOR PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1443 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2009-08-04 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2009-08-04 |
Time |
15:38 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2009-08-04 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2009-08-04 15:38:38 | PLANNING AND ZONING DEPT: ***ZONING FAILED*** | | | | | | 1. PLEASE PROVIDE ALL RESPONSES IN WRITING. | | | | | | 2. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND | | | LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION | | | 94-441(C)(2) OF: AS THE VALUE OF THE PROPOSED WORK | | | EXCEEDS 50% OF THE STRUCTURE'S VALUE (LISTED AS | | | "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY | | | APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE | | | WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF | | | THE ZLDR. | | | | | | PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN | | | SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF | | | THE ZLDR. | | | | | | | | | NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY | | | GENERATE ADDITIONAL COMMENTS. | | | | | | FOR ADDITIONAL INFORMATION, THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT | | | WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH | | | PLANNING DEPARTMENT WEBSITE AT | | | WWW.CITYOFWPB.COM/PLAN/INDEX.HTM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO | | | CONTACT ME. | | | | | | MAGGIE CRUZ, ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1444 OR (561) 805-6720 | | | E-MAIL: [email protected] | | | |
|
|