| Plan Review Stops For Permit 09070491 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-07-22 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-07-22 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-07-22 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2009-07-22 11:00:21 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | | 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | | FLORIDA STATUTE. | | | | | | 2- PROPOSED SCOPE OF WORK IS FOR MORE THAN 25% OF THE | | | ROOF. NEED TO RE-ROOF ENTIRE ROOF AS REQUIRED BY SEC. | | | 611.1.1 OF 2007 FLORIDA EXISTING BUILDING CODE. | | | IN ADDITION ENGINEER REPORT SUBMITTED STATES ALSO THAT | | | ENTIRE ROOF NEEDS TO BE REPLACED BECAUSE ROOF DOESN'T | | | MEET THE FBC REQUIREMENTS. | | | | | | 3- REVISE PERMIT APPLICATION TO RE-ROOF ENTIRE ROOF, | | | NOT REPAIRS AND REVISE VALUATION AS REQUIRED. SPECIFY | | | TOTAL SQUARE FOOTAGE, ROOF PITCH AND MEAN ROOF HEIGHT. | | | PERMIT FEES WILL BE ADJUST ACCORDINGLY. | | | | | | 4- PROVIDE 2 COPIES OF PRODUCT APPROVAL AS REQUIRED BY | | | DCA RULE 9B-72 FOR THE ROOF TILE TO BE INSTALLED. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|