Plan Review Details - Permit 09070449
Plan Review Stops For Permit 09070449
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-07-30 Cont ID  
Sent By jwitmer Date 2009-07-30 Time 14:48 Rev Time 0.95
Received By jwitmer Date 2009-07-30 Time 14:00 Sent To  
Notes
2009-07-30 15:15:34BUILDING PLAN REVIEW
 PERMIT: 09070449
 ADD: 1801 PALM BEACH LAKES J. C. PENNY
 CONT: HENRY & CO.
 TEL: (954)527-1597
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2) PLANS AND SPEC INDICATE THE SIZE OF THE GENERATOR
 ASA A 50KW AND THE FUEL TANKS AS A DOUBLE WALL DESIEL
 FUEL TANK. PLEASE PROVIDE THE CAPACITY IN GALLONS.
 DEPENDING ON THE HEIGTH OF THE FUEL TANK STAIRS AND
 LANDING MAY BE REQUIRED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-08-26 Cont ID  
Sent By dpalmer Date 2009-08-26 Time 11:01 Rev Time 0.00
Received By dpalmer Date 2009-08-26 Time 11:01 Sent To  
Notes
2009-08-26 11:01:31 
 ** DENIED REVIEW **
  
 1) NOTE: ALL OF THE FOLLOWING CODES SHALL BE LISTED ON
 PLANS FOR MINIMUM DESIGN.
 2005 NFPA-70
 2006 NFPA-101
 2005 NFPA-110
  
 2) NOTE: ** PLANS ARE NOT COMPLETE WITH ENOUGH
 INFORMATION FOR REVIEW FOR CODE COMPLIANCE. THE PLANS
 STATE THIS IS A LEVEL 2, CLASS X TYPE 60 UNIT, HOWEVER
 BASED ON THE PANEL SCHEDULE THIS IS NOT POSSIBLE.
 PLEASE SUBMIT AND SHOW ALL INFORMATION ON THE TYPE AND
 CLASS OF SYSTEMS. PLEASE LOOK AT 700.9 OF THE NEC FOR
 WIRING OF SYSTEMS. BASE DON THE SCHEDULE THERE ARE WHAT
 APPEARS TO BE 700 SYSTEMS, POSSIBLY 701 SYSTEMS AND
 THERE ARE 702 SYSTEMS ALL SHOWN ON THE SAME TRANSFER
 SWITCH. THIS IS NOT PERMITTED.
 THIS IS NOT A CLASS X TYPE 60 LEVEL 2 SYSTEMS.
 PLEASE SEE NFPA-110 CHAPTER 4, THIS WOULD BE A LEVEL 1,
 TYPE 10, CLASS 2 AT A MINIMUM. DESIGN ACCORDINGLY. SEE
 NEC 700.12 ( ALL) FOR BACK UP OF EMERGENCY LIGHTS WITH
 ACCEPTABLE POWER AND MINIMUM TIME TO COME ON.
 CLASS X PER NFPA-110 IS A HIGHER AMOUNT OF FUEL THAN
 SHOWN.
  
 2) NOTE: PLEASE SEE 700.27, 701.18 OF THE NEC AND
 NFPA-110 6.5 (ALL)
  
 3) NOTE: PLEASE SEE NFPA-110 7.3.1 AND PROVIDE LIGHTING
 ACCORDINGLY
  
 4) NOTE: PLEASE SEE NFPA-110 7.2, 7.2.1, 7.2.1.2, ETC.
 BASED ON THE SUBMITTED PLANS THIS EQUIPMENT/ EPS IS
 PART OF A 700 SYSTEM WHICH IS NOT PERMITTED IN THE
 MECHANICAL EQUIPMENT ROOM.
 PLEASE SHOW LOCATIONS OF ALL ELECTRICAL EQUIPMENT.
  
 5) NOTE: PLEASE PROVIDE INFORMATION ON RISER ON WHETHER
 OR NOT THE ATS WILL BE 4-POLE OR 3-POLE. THE RISER
 INDICATES A NEW GROUND HOWEVER NO INFORMATION ON THE
 ATTACHMENT IS SHOWN.
 SEE NFPA-110 6.2.15
  
 6) NOTE: HOW WILL THE POWER BE SHUT DOWN IN THE EVENT
 OF AN EMERGENCY WHEN FIRE DEPARTMENT OR OTHER PERSONNEL
 SHUTS DOWN MAINS POWER AND THE GENERATOR WHICH IS
 LOCATED ON THE ROOF AREA STARTS AND RE-FEEDS 480V
 ELECTRICAL SYSTEMS?
 SEE 445.18 ETC.
 SEE COMMENTS FROM FIRE MARSHAL.
  
 ** AS THERE WILL BE CHANGES TO THE DESIGN, SOME NEW
 COMMENTS MAY ARISE ONCE MORE INFORMATION IS SUBMITTED
 AND/OR DESIGN CHANGES HAVE BEEN MADE.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-08-10 Cont ID  
Sent By mawillia Date 2009-08-10 Time 14:08 Rev Time 0.00
Received By mawillia Date 2009-08-10 Time 13:13 Sent To  
Notes
2009-08-10 14:08:01*****DENIED*****
  
  
 1. IN THE GENERAL ELECTRIC NOTES ON SHEET E-1, AMEND
 NOTE #1 TO REFLECT THE 2006 NFPA-101 AND 2005 NFPA-110
 EDITIONS.
  
 2. ON SHEET E-1, NFPA 101.7.10.2 AND 101.7.10.3 ARE
 REFERENCED IN THE NOTES. THIS WRITER COULD NOT LOCATE
 THESE VERBAGE IN EITHER THE 2003 OR 2006 EDITION OF
 NFPA 101.
  
 3. NO FLOOR PLAN AND/OR SITE PLAN TO INDICATE LOCATION
 OF THE EXISTING/PROPOSED GENERATOR.
  
 4. SHOW THE PROXIMITY OF ANY ANY EXIT DOORS, AIR INTAKE
 OR EXHAUST OPENINGS WITHIN TEN FEET OF THE GENERATOR
 AND OR FUEL TANK.
  
 5. NO WARNING LABELS OR PRODUCT LABELS DESCRIBED.
  
 6. WHAT SYSTEMS WILL THE GENERATOR SUPPLY?
  
 7. HOW IS THE FUEL TANK PROPOSED TO BE REFILLED SAFELY.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-27 Cont ID  
Sent By dpalmer Date 2009-07-27 Time 08:42 Rev Time 0.00
Received By dpalmer Date 2009-07-27 Time 08:42 Sent To  
Notes
2009-07-27 08:43:15B 17

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-08-26 Time   Rev Time 0.00
Received By lmartine Date 2009-07-22 Time 16:05 Sent To  
Notes
2009-07-22 16:05:22IN ZONING

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-08-04 Cont ID  
Sent By rregueir Date 2009-08-04 Time 16:06 Rev Time 0.00
Received By rregueir Date 2009-08-04 Time 15:38 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2009-07-24 Cont ID  
Sent By eschneid Date 2009-07-24 Time 17:01 Rev Time 0.25
Received By eschneid Date 2009-07-24 Time 17:01 Sent To  
Notes
2009-07-24 17:02:10NOT REQUIRED. GENERATOR IS ENCLOSED ENTIRELY WITHIN A
 ROOM.