| 2009-08-26 11:01:31 | |
| | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: ALL OF THE FOLLOWING CODES SHALL BE LISTED ON |
| | PLANS FOR MINIMUM DESIGN. |
| | 2005 NFPA-70 |
| | 2006 NFPA-101 |
| | 2005 NFPA-110 |
| | |
| | 2) NOTE: ** PLANS ARE NOT COMPLETE WITH ENOUGH |
| | INFORMATION FOR REVIEW FOR CODE COMPLIANCE. THE PLANS |
| | STATE THIS IS A LEVEL 2, CLASS X TYPE 60 UNIT, HOWEVER |
| | BASED ON THE PANEL SCHEDULE THIS IS NOT POSSIBLE. |
| | PLEASE SUBMIT AND SHOW ALL INFORMATION ON THE TYPE AND |
| | CLASS OF SYSTEMS. PLEASE LOOK AT 700.9 OF THE NEC FOR |
| | WIRING OF SYSTEMS. BASE DON THE SCHEDULE THERE ARE WHAT |
| | APPEARS TO BE 700 SYSTEMS, POSSIBLY 701 SYSTEMS AND |
| | THERE ARE 702 SYSTEMS ALL SHOWN ON THE SAME TRANSFER |
| | SWITCH. THIS IS NOT PERMITTED. |
| | THIS IS NOT A CLASS X TYPE 60 LEVEL 2 SYSTEMS. |
| | PLEASE SEE NFPA-110 CHAPTER 4, THIS WOULD BE A LEVEL 1, |
| | TYPE 10, CLASS 2 AT A MINIMUM. DESIGN ACCORDINGLY. SEE |
| | NEC 700.12 ( ALL) FOR BACK UP OF EMERGENCY LIGHTS WITH |
| | ACCEPTABLE POWER AND MINIMUM TIME TO COME ON. |
| | CLASS X PER NFPA-110 IS A HIGHER AMOUNT OF FUEL THAN |
| | SHOWN. |
| | |
| | 2) NOTE: PLEASE SEE 700.27, 701.18 OF THE NEC AND |
| | NFPA-110 6.5 (ALL) |
| | |
| | 3) NOTE: PLEASE SEE NFPA-110 7.3.1 AND PROVIDE LIGHTING |
| | ACCORDINGLY |
| | |
| | 4) NOTE: PLEASE SEE NFPA-110 7.2, 7.2.1, 7.2.1.2, ETC. |
| | BASED ON THE SUBMITTED PLANS THIS EQUIPMENT/ EPS IS |
| | PART OF A 700 SYSTEM WHICH IS NOT PERMITTED IN THE |
| | MECHANICAL EQUIPMENT ROOM. |
| | PLEASE SHOW LOCATIONS OF ALL ELECTRICAL EQUIPMENT. |
| | |
| | 5) NOTE: PLEASE PROVIDE INFORMATION ON RISER ON WHETHER |
| | OR NOT THE ATS WILL BE 4-POLE OR 3-POLE. THE RISER |
| | INDICATES A NEW GROUND HOWEVER NO INFORMATION ON THE |
| | ATTACHMENT IS SHOWN. |
| | SEE NFPA-110 6.2.15 |
| | |
| | 6) NOTE: HOW WILL THE POWER BE SHUT DOWN IN THE EVENT |
| | OF AN EMERGENCY WHEN FIRE DEPARTMENT OR OTHER PERSONNEL |
| | SHUTS DOWN MAINS POWER AND THE GENERATOR WHICH IS |
| | LOCATED ON THE ROOF AREA STARTS AND RE-FEEDS 480V |
| | ELECTRICAL SYSTEMS? |
| | SEE 445.18 ETC. |
| | SEE COMMENTS FROM FIRE MARSHAL. |
| | |
| | ** AS THERE WILL BE CHANGES TO THE DESIGN, SOME NEW |
| | COMMENTS MAY ARISE ONCE MORE INFORMATION IS SUBMITTED |
| | AND/OR DESIGN CHANGES HAVE BEEN MADE. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |