Plan Review Details - Permit 09070433
Plan Review Stops For Permit 09070433
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-09-16 Cont ID  
Sent By jwitmer Date 2009-09-10 Time 10:18 Rev Time 0.00
Received By jwitmer Date 2009-09-10 Time 10:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-07-27 Cont ID  
Sent By jwitmer Date 2009-07-27 Time 10:21 Rev Time 1.55
Received By jwitmer Date 2009-07-27 Time 10:05 Sent To  
Notes
2009-07-27 11:06:49BUILDING PLAN REVIEW
 PERMIT: 09070433
 ADD: 1731 OLD OKEECHOBEE RD
 CONT: GLOBAL CONSTRUCTION
 TEL: (954)444-8463
  
 FL BLDG CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE. THE BUILDING
 STATS SHEET A-0.0 DOES NOT PROVIDE THIS INFORMATION.
  
 2) SHEET A-1.0 INDICATES THE REMOVAL OF THE EXTERIOR
 OVERHEAD DOORS AND NEW STOREFRONT WINDOWS AND DOORS,
 PLEASE PROVIDE THE WIND DESIGN CRITERIA: 1603.1.4 WIND
 DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 2.1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2.2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 2.3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 2.4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 2.5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL.
  
 3) THE PRODUCT APPROVAL NOA 06-1026.08 YKK SERIES
 YHS-50 FS FLUSH GLAZED ALUMINUM STOREFRONT SYSTEM-LMI
 W/ AND W/O STEEL REINFORCEMENT, PLEASE CIRCLE IF THE
 APPROPRIATE BOX FOR MULLIONS FOR MULLION IF THE MULLION
 WILL BE STEEL REINFORCED OR NOT WITH ASSOCIATED
 PRESSURES.
  
 4) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIES OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 5A) PREMANUFACTURED A/C STANDS
  
 5B) PLEASE REVIEW THE MECHANICAL REVIEWERS COMMENTS
 ABOUT A/C EQUIPMENT BEING REQUIRED TO WITHSTAND WIND
 PRESSURE PER MECHCANICAL SECTION: 301.13 FBC
 MECHANICAL. WIND RESISTANCE. MECHANICAL EQUIPMENT,
 APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO WIND SHALL
 BE DESIGNED AND INSTALLED TO RESIST WIND PRESSURES ON
 THE EQUIPMENT AND THE SUPPORTS AS DETERMINED IN
 ACCORDANCE WITH THE FLORIDA BUILDING CODE, BUILDING.
 PLEASE PROVIDE DOCUMENTATION ON THE ROOF TOP EQUIPMENT
 .
  
 6) PLANS INDICATE A 1 HR RATED WALL BETWEEN THE
 SHOWROOM AND THE WAREHOUSE AND ALSO BETWEEN THE
 SHOWROOM AND OFFICE AREAS. THERE IS A SECOND SET OF
 DOORS LEADING FROM THE SHOWROOM TO WAREHOUSE WITHOUT
 ANY FIRE RATING, THE DOORS NEXT TO THE MOVED
 TRANSFOREMER. PLEASE SEE REQUIRED OPENING PROTECTIVES
 SECTION 715.3 AND TABLE 715.3.
  
 7) THE ENERGY CALCULATIONS SUBMITTED ARE ON FORM
 400A-2008 WHICH IS THE WHOLE BUILDING METHOD, THIS
 SPACE IS ONLY A PORTION OF THE BUILDING REQUIRING
 METHOD "B" 13-400.0.B
 THE BUILDING ENVELOPE TRADE- OFF METHOD.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-10-15 Cont ID  
Sent By dpalmer Date 2009-10-15 Time 09:43 Rev Time 0.00
Received By dpalmer Date 2009-10-15 Time 09:43 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-09-18 Cont ID  
Sent By dpalmer Date 2009-09-18 Time 17:08 Rev Time 0.00
Received By dpalmer Date 2009-09-18 Time 17:08 Sent To PC
Notes
2009-09-18 17:08:17 
 ** PROVISO **
  
 ** A PROVISO IS BEING GIVEN AFTER CALL WAS MADE TO
 ENGINEERING FIRM. THE DESIGNER AND ENGINEER OF RECORD
 WERE NOT AVAILABLE. HOWEVER ANOTHER DESIGNER FROM THE
 FIRM KNOWN TO THIS REVIEWER WAS AVAILABLE TO GO OVER
 COMMENTS. A REQUEST THAT A PROVISO WAS GRANTED AND
 PLANS TO BE REDLINED WAS GONE OVER. A CALL WAS PLACED
 TO GC TO LET THEM KNOW THE OUTCOME OF REVIEW AND PHONE
 CALL.
  
 1) NOTE: THE PREVIOUS COMMENT FROM MR. WILLIAM TROBAUGH
 WAS NOT ADDRESSED. THE COMMENT MADE WAS THAT THE USE OF
 METHOD *A* WAS NOT PERMITTED.
 THE RESPONSE LETTER FROM DESIGN TEAM STATES THIS IS AN
 *ADDITION* TO AN EXISTING BUILDING. SUPPORTING
 DOCUMENTATION WAS SUBMITTED WITH COPIES OF SEVERAL
 SECTIONS OF THE FLORIDA BUILDING CODE.
  
 THE INPUT DATA REPORT IS NOT COMPLETE FOR THIS BEING AN
 ADDITION.
  
 THE CONFUSION COMES WHEN THE RESPONSE LETTER FROM
 DESIGN TEAM CLEARLY STATES METHOD *B* CAN NOT BE USED
 BASED ON THIS BEING AN ADDITION. HOWEVER THE LIGHTING
 PLANS SUBMITTED CLEARLY INDICATE METHOD *B*. IN FACT
 THE PLANS STATE COMPLIANCE FOR SPACE BY SPACE PER
 13-415.B.1. THIS IS IN CONFLICT WITH THE RESPONSE
 LETTER AND SUBMITTED SUPPORTING FLA COM METHOD *A*.
 PLEASE SEE 13-415.AB.5 OF THE FBC. THIS SECTION CLEARLY
 STATES THE FOLLOWING.
  
 ** TRADE-OFFS OF INTERIOR LIGHTING POWER ALLOWANCE
 AMONG PORTIONS OF THE BUILDING FOR WHICH A DIFFERENT
 METHOD OF CALCULATION HAS BEEN USED IS NOT PERMITTED*.
  
 THIS MEANS IT IS NOT PERMISSIBLE TO USE TWO DIFFERENT
 METHODS TO SHOW COMPLIANCE. THE SUBMITTED INPUT DATA
 REPORT OF THE METHOD *A* IN BOTH CASES IS NOT COMPLETE.
 SOME INFORMATION ON THE IDR IS NOT WHAT IS SHOWN/STATED
 ON PLANS AND/OR INCOMPLETE FOR WHOLE BUILDING/ WHOLE
 ADDITION COMPLIANCE.
  
 ** THEREFORE COMPLIANCE FOR METHOD B AS SHOWN ON PLANS
 FOR PRESCRIPTIVE FOR NEW BEING INSTALLED IS ACCEPTABLE.
 13-415.AB.5, 13-415.B.1, 13-400.0.B.4. "LAST SENTENCE
 FOR * BUILDINGS NOT MEETING THE DEFINITION OF A
 RENOVATION.
  
 2) NOTE: COMPLIANCE FOR NEW LIGHTING CONTROLS BEING
 INSTALLED SHALL MEET 13-415.AB.1.1,.1.2. THE PREVIOUS
 REVIEW DOES NOT HAVE ANY COMMENTS RELEVANT TO THESE
 SECTIONS. THIS IS A BUILDING LARGER THAN 5K SQ FT. BY
 DEFINITION IT IS NOT WHETHER OR NOT A TENANT SPACE IS
 OVER 5K SQ FT.
 AUTOMATED CONTROLS OF SOME KIND ARE REQUIRED. THERE ARE
 SEVERAL WAYS TO COMPLY FOR MINIMUM CODE COMPLIANCE.
 PLEASE CHOSE ONE OR MORE AND REVISE PLANS.
 ** THIS IS REQUIRED FOR NEW ONLY.
  
 3) NOTE: LOAD CALCULATIONS DO NOT SHOW LOADS FOR SHOW
 WINDOWS FIGURED PER 220.14G AND 220.43A.
 PLEASE ALSO INDICATE ALL CONTINUOUS LOADS AND LARGEST
 MOTOR LOADS AT 125%. IF ALREADY FIGURED INTO SERVICE
 THEN PLEASE SHOW WHERE OR NOTE THIS WAS DONE ON PLANS.
 215.3, 230.42 ETC
  
 *** PLEASE SUBMIT REVISED PLANS BEFORE ANY ROUGH
 ELECTRICAL INSPECTIONS. A HOLD WILL BE PLACED ON
 ELECTRICAL SUB PERMIT UNTIL REVISED PLANS ARE
 SUBMITTED, REVIEWED AND STAMPED FOR CODE COMPLIANCE.
  
 ** LOW VOLTAGE SYSTEMS, INCLUDING FIRE ALARMS ARE NOT
 INCLUDED. SEPARATE PERMITS AS INDICATED ON PLANS
 REQUIRED.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-07-29 Cont ID  
Sent By btrobaug Date 2009-07-29 Time 15:33 Rev Time 0.00
Received By btrobaug Date 2009-07-29 Time 13:17 Sent To  
Notes
2009-07-29 14:19:26 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2006, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 COMMENTS REFERENCING SHEETS E1
  
 1} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE
 INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A
 SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD
 DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR
 LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING
 FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN
 USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING
 POWER IDENTIFIED IN ACCORDANCE WITH SECTION
 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING
 POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION13-415.B.1***THIS CAN BE DEMONSTRATED ON THE
 PLANS INDICATING THE WATTAGES OF THE LUMINAIRES CHOSEN
 FOR THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS.
 INDICATE WATTAGES ON THE FIXTURE SCHEDULE TO CORRELATE
 WITH THE ONES IN THE CALCULATION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-09-15 Cont ID  
Sent By mawillia Date 2009-09-15 Time 14:04 Rev Time 0.00
Received By mawillia Date 2009-09-15 Time 13:20 Sent To  
Notes
2009-09-15 14:03:30*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED AND/OR ACKNOWLEDGED; PLAN SHEETS A1.0,
 E1, AND FP-1 WERE STAMPED,INTITLED, AND DATED.
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-08-14 Cont ID  
Sent By mawillia Date 2009-08-14 Time 15:36 Rev Time 0.00
Received By mawillia Date 2009-08-14 Time 14:20 Sent To  
Notes
2009-08-10 15:06:38*****DENIED*****
  
  
 1. THE ADDRESS FOR THE PROJECT SITE SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. (SEE A-0.0
 AND A-1.0 DRAWINGS)
  
 2. EFFECTIVE 12/31/2009, NFPA 1, UNIFORM FIRE CODE,
 2006 EDITION AND NFPA 101, LIFE SAFETY CODE, 2006
 EDITION IN ADDITION TO THE 2004 EDITION OF NFPA 241
 SHALL BE REFERENCED. AMEND DRAWING A-0.0
  
 3. PLEASE INDICATE POINT OF COMPASS FOR THE APPROPIATE
 PLAN SHEETS.
  
 4. SPECIFY THE INTERIOR FINISH MATERIAL FOR THE NEW
 WALL IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 5. THE SUBMITTED FIRE PROTECTION SHEET (FP-1) IS NOT
 STAMPED AND SEALED AS THE OTHER SHEETS IN THE PLAN SET.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-08-26 Cont ID  
Sent By lmartine Date 2009-08-26 Time 16:01 Rev Time 0.00
Received By lmartine Date 2009-08-26 Time 16:01 Sent To  
Notes
2009-08-26 16:09:46B-21

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-08-10 Cont ID  
Sent By mawillia Date 2009-08-10 Time 14:29 Rev Time 0.00
Received By mawillia Date 2009-07-21 Time 14:27 Sent To  
Notes
2009-07-21 14:27:17B-24

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-08-04 Cont ID  
Sent By rregueir Date 2009-08-04 Time 15:31 Rev Time 0.00
Received By rregueir Date 2009-08-04 Time 15:29 Sent To  
Notes
2009-08-04 15:31:51**PROVISOS**
 1. CONDENSATE DRAIN LINE HORIZONTAL SECTION AS SHOWN IS
 VERY LONG. CONDENSATE PIPING SHALL BE INSTALLED AT A
 UNIFORM 1/8 INCH PER FOOT IN ACCORDANCE WITH FBC-M
 307.2.2.
  
 2. PROVIDE THE ACTUAL PRODUCT APPROVAL DOCUMENTATION
 WITH INSTALLATION INSTRUCTIONS ON SITE FOR FIELD
 INSPECTOR TO VERIFY SIZE OF CONDENSING UNIT IS
 COMPATIBLE WITH THE PROPOSED STAND.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2009-07-28 Cont ID  
Sent By kdfreema Date 2009-07-28 Time 13:26 Rev Time 0.00
Received By kdfreema Date 2009-07-28 Time 13:26 Sent To  
Notes
***NONE***