Plan Review Details - Permit 09070377
Plan Review Stops For Permit 09070377
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-11-16 Cont ID  
Sent By jwitmer Date 2009-11-16 Time 17:23 Rev Time 2.00
Received By jwitmer Date 2009-11-05 Time 17:16 Sent To  
Notes
2009-11-09 17:30:1211-05-09 SPOKE WILL PERMIT EXPEDITER, ONLY 1 COMPLETE
 SET OF PLANS SUBMITTED, THREE SETS SUBMITTED WWITHOUT
 CITY PLACE STAMPS.
  
 11-09-09 3 SETS OF REVISED PLANS RESUBMITTED, WITH CITY
 PLACE STAMPS BUT SHEETS:
 A0.01
 A2.2.0,
 A3.2.0,
 S-1,
 E1.01,
 E1.02,
 E2.01,
  
 REVIEWS ON HOLD UNTIL (3) SETS OF PLANS CAN BE
 ASSEMBLED FOR REVIEW. I CALLED TTHE PERMIT EXPEDITER AS
 WELL AS SCOTT KREMPOSKY TO TRY TO GET THREE SETS OF
 PLANS FOR THE REVIEW TO BEGIN.
  
 11-16-09 2 COMPLETE SETS OF PLANS SUBMITTED MATCH THE
 THIRD SET IN OFFICE BUILDING REVIEW -OK WILL STILL NEED
 TO HAVE A SPECIAL INSPECTOR SIGNED ON BECAUSE OF TTHE
 BUILDING A THRESHOLD BUILDING. A SET OF DOCUMENTS FOR
 SIGNATURE ARE WITH THE BUILDING PERMIT APPLICATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-07-30 Cont ID  
Sent By jwitmer Date 2009-07-30 Time 01:27 Rev Time 1.50
Received By jwitmer Date 2009-07-30 Time 12:00 Sent To  
Notes
2009-07-30 12:33:41 
 BUILDING PLAN REVIEW
 PERMIT: 09070377
 ADD: 550 S ROSEMARY
 CONT: TO BE DETERMINED
 TEL: (561) 856-6655/ NEYITA
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 2) 1009.5.3 ENCLOSURES UNDER STAIRWAYS. THE WALLS AND
 SOFFITS WITHIN ENCLOSED USABLE SPACES UNDER ENCLOSED
 AND UNENCLOSED STAIRWAYS SHALL BE PROTECTED BY 1-HOUR
 FIRE-RESISTANCE-RATED CONSTRUCTION OR THE
 FIRE-RESISTANCE RATING OF THE STAIRWAY ENCLOSURE,
 WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED SPACE
 SHALL NOT BE DIRECTLY FROM WITHIN THE STAIR ENCLOSURE.
  
 THERE SHALL BE NO ENCLOSED USABLE SPACE UNDER EXTERIOR
 EXIT STAIRWAYS UNLESS THE SPACE IS COMPLETELY ENCLOSED
 IN 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION. THE OPEN
 SPACE UNDER EXTERIOR STAIRWAYS SHALL NOT BE USED FOR
 ANY PURPOSE.
  
  
 3)FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE
 2 COPIES PRODUCT TESTING REPORTS, MISSING REPORTS ARE
 AS FOLLOWS:
 3A) EXTERIOR SWING DOORS
  
 4) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND
 APPROVED IN WRITTING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 5) PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6) SHEET A2.1.0 DETAIL# 3 INDICATES THE HANDRAIL AWAY
 FROM THE WALL 2 1/2". BOTH WITHIN THE BUILDING CODE
 1012.6 AND 11-4.9.4(3) INDICATE TTHE HANDRAILS ARE TO
 BE SET NO MORE THAN
 1 1/2 INCHES, THE NFPA 101 SECTION 7.2.2.4.4.5 STATES 2
 1/4 INCHES AWAY.
  
 7) SHEET S-1 DOES NOT INDICATE THE MINIMUM DISTRIBUTED
 LIVE LOADS, TABLE 1607.1.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-11-19 Cont ID  
Sent By btrobaug Date 2009-11-19 Time 13:03 Rev Time 0.00
Received By btrobaug Date 2009-11-19 Time 07:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-08-07 Cont ID  
Sent By dpalmer Date 2009-08-07 Time 12:00 Rev Time 0.00
Received By dpalmer Date 2009-08-07 Time 12:00 Sent To  
Notes
2009-08-07 12:01:03 
  
 ** DENIED REVIEW **
  
 1) NOTE: PLANS ARE ONLY SUBMITTED AS A *PROJECT/PLAN
 REVIEW* AND ARE NOT SUBMITTED UNDER PERMIT APPLICATION.
  
 2) NOTE: PLEASE SEE THE FOLLOWING CODES WHICH ARE
 STATED ON PLANS ARE EITHER NOT ADOPTED OR ARE INCORRECT
 EDITIONS..
  
 2007 FLORIDA BUILDING CODE. SHOULD BE 2007 FBC W/2009
 SUPPLEMENTS
  
 2007 NFPA-101 ON PLANS: SHOULD BE 2006 NFPA-101. THERE
 IS NO 2007 EDITION.
  
 2008 NFPA-70 ( NEC) ON PLANS. SHOULD BE 2005 EDITION.
 2008 HAS NOT YET BEEN ADOPTED PER THE STATE OF FLORIDA.
 AS PLANS WERE NOT SUBMITTED AS A PERMIT APPLICATION
 PLEASE BE AWARE THAT THE 2008 EDITION MAY GO INTO
 AFFECT OVER THE NEXT MONTH OR TWO. ** ONLY PERMIT
 APPLICATION WITH APPLICABLE FEES PAID WILL *LOCK* PLANS
 UNDER SPECIFIC CODES BEFORE THEY ARE REVISED.
  
 2007 NFPA-72 ON PLANS: SHOULD BE 2002 NFPA-72.
  
 ** MOST OF THE ABOVE REFERENCED CODES MAY BE FOUND IN
 FLORIDA ADMINISTRATIVE CODE 69A-60.004 AND 69A-3.012
 FOR NFPA ADOPTION DATES.
 ** 2007 FBC W/ 2009 REVISIONS REFERENCED CODES CAN BE
 FOUND IN CHAPTER 35 OF THE FBC.
  
 3) NOTE: PLEASE SUBMIT ELECTRICAL PLANS SHOWING
 LOCATIONS OF NEW LIGHTING REQUIRED FOR LIFE SAFETY.
 PLEASE SEE FBC 1016 AND NFPA-101 7.8.1.3, 7.9.1.2,
 7.9.2.2.
 PLEASE SHOW ALL LIGHTING FIXTURE TYPES AND CONTROLS.
  
 4) NOTE: PLEASE SHOW HOW EXTERIOR LIGHTING WILL BE
 CONTROLLED PER 13-415.AB.1.4.
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2009-11-20 Cont ID  
Sent By efabian Date 2009-11-20 Time 11:17 Rev Time 0.50
Received By efabian Date 2009-11-20 Time 11:17 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-11-30 Cont ID  
Sent By mawillia Date 2009-11-30 Time 13:23 Rev Time 0.00
Received By mawillia Date 2009-11-30 Time 13:02 Sent To  
Notes
2009-11-30 13:23:29*****APPROVED*****
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEETS A2.1.0, A3.1.0, AND E1.01
 WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-08-05 Cont ID  
Sent By mcarsill Date 2009-08-05 Time 13:11 Rev Time 0.00
Received By mcarsill Date 2009-08-05 Time 13:05 Sent To  
Notes
2009-08-05 13:11:24PLAN REVIEW FOR EGRESS STAIR AT CITY PLACE
  
 1. PLEASE DOCUMENT ON THE PLANS AN OCCUPANT LOAD FACTOR
 FOR THE NEW STAIRS. WHEN THE NEW STAIRS ARE COMPLETED,
 ARE THE EXISTING STAIR TO THE WEST REMOVED.
  
 2. PLEASE INDICATE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR HANDRAILS AND GUARDRAILS.
  
 3. PLEASE PROVIDE AN ELEVATION DRAWING OF THE NORTH
 SIDE OF THE BUILDING WHERE THE STAIRS ARE BEING
 PROPOSED.
  
 4. DOORS 100A AND 100B ARE TO BE EQUIPPED WITH FIRE
 EXIT PANIC HARDWARE.
  
 5. SEPARATE PLANS AND PERMIT REQUIRED FOR ANY FIRE
 SPRINKLER SYSTEM REMODEL.
  
 6. PLEASE INDICATE SLIP RESISTANT STRATEGIES PROPOSED
 TO PREVENT ACCIDENTS DURING INCLEMENT WEATHER.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-11-03 Cont ID  
Sent By lmartine Date 2009-11-03 Time 14:38 Rev Time 0.00
Received By lmartine Date 2009-11-03 Time 14:38 Sent To  
Notes
2009-11-04 16:34:59SUBMITTED EXPEDITED REQUEST 11/4/09
 ********************* EXPEDITED**********************
2009-11-03 14:43:35C--12

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-10-29 Cont ID  
Sent By jwitmer Date 2009-10-29 Time 08:12 Rev Time 0.00
Received By jwitmer Date 2009-10-29 Time 08:12 Sent To  
Notes
2009-10-29 08:20:55INCOMING TO C-4
 10-29-09/ 7:18 PM E-MAIL FORM ROBERT BROWN REMOVE PLANS
 FROM C-4 AND PUT ON HOLD PLANS CURRENTLY ARE BEING
 REVIEWED BY ERIC SCHNEIDER WHEN RETURNED WILL PUT ON
 HOLD AND BE FORWARDED TO THE DENIED PLAN CABINET.
 11-1-09 8:05 AM. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-08-31 Cont ID  
Sent By kstevens Date 2009-08-31 Time 13:11 Rev Time 0.00
Received By kstevens Date 2009-07-17 Time 12:40 Sent To  
Notes
2009-07-17 12:40:38SENT TO C-40.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2009-08-14 Cont ID  
Sent By rregueir Date 2009-08-14 Time 13:57 Rev Time 0.00
Received By rregueir Date 2009-08-10 Time 11:51 Sent To  
Notes
2009-08-14 13:58:37NO MECHANICAL SCOPE OF WORK SHOWN ON PLANS. SEPARATE
 PLANS AND PERMIT REQUIRED FOR ANY MECHANICAL WORK
 ASSOCIATED WITH THIS ALTERATION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status N Date 2009-12-01 Cont ID  
Sent By lmartine Date 2009-12-01 Time 11:45 Rev Time 0.00
Received By lmartine Date 2009-12-01 Time 11:44 Sent To  
Notes
2009-12-01 11:46:26REVIEW NOT REQUIRED PER KEN STEVENS

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-08-31 Cont ID  
Sent By kstevens Date 2009-08-31 Time 13:06 Rev Time 0.00
Received By kstevens Date 2009-08-31 Time 13:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2009-11-25 Cont ID  
Sent By eschneid Date 2009-11-25 Time 15:47 Rev Time 0.50
Received By eschneid Date 2009-11-25 Time 15:47 Sent To  
Notes
2009-11-25 15:47:45SEPARATE GAS PERMIT REQUIRED FOR THE METERS. ZONING
 NEEDS TO REVEIW.

Review Stop Z ZONING
Rev No 1 Status F Date 2009-07-27 Cont ID  
Sent By eschneid Date 2009-07-27 Time 14:18 Rev Time 0.33
Received By eschneid Date 2009-07-27 Time 14:18 Sent To  
Notes
2009-07-27 14:57:17PLAN REVIEW - FAIL
  
 1) THE ADDITION OF THE EXTERIOR STAIR REQUIRES THE
 SUBMITTAL AND APPROVAL OF A MINOR PD AMENDMENT TO THE
 PLANNING AND ZONING DIVISION.
  
 2) IS THE TREE ISLAND AT THE BOTTOM OF THE STAIR GOING
 TO BE AFFECTED BY THE STAIR LANDING?
  
 3) PLEASE REVIEW THE PARCEL CONTROL NUMBER FOR WHERE
 THE WORK IS TO OCCUR. THE PROPERTY APPRAISER SHOWS IT
 AS # 74434321130030010.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  