Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-09-09 Cont ID  
Sent By mcarsill Date 2009-09-09 Time 07:33 Rev Time 0.00
Received By mcarsill Date 2009-09-09 Time 07:31 Sent To  
Notes
2009-09-09 07:33:13222 LAKEVIEW AVENUE
 PERMIT # 09070347
 NEW FIRE ALARM SYSTEM
  
 1. DUCT DETECTORS WHEN ACTIVATED SHALL ACTIVE THE
 BUILDINGS FIRE ALARM SYSTEM.
  
 2. ENTIRE INSTALLATION IS SUBJECT TO FIELD INSPECTION
 AND VERIFICATION.
  
 3. SYSTEM AFTER INSTALLATION IS TO BE TESTED TO ENSURE
 PROPER OPERATION AND FUNCTION.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-07-27 Cont ID  
Sent By mcarsill Date 2009-07-27 Time 16:18 Rev Time 0.00
Received By mcarsill Date 2009-07-27 Time 12:44 Sent To  
Notes
2009-07-27 13:03:31UPGRADE FIRE ALARM SYSTEM
  
 1. THE PERMIT APPLICATION INDICATES A VALUE OF $
 259,000 DOLLARS. PLEASE PROVIDE A COPY OF THE CONTRACT
 REPRESENTING THE COST OF LABOR AND PARTS TO PERFORM
 THIS WORK.
  
 2. PLEASE PROVIDE INFORMATION ON THE C I CABLE THAT IS
 PLANNED TO BE USED TO MEET THE SURVIVABILITY
 REQUIREMENTS.
  
 3. A GENERAL DISCUSSION NEEDS TO OCCUR REGARDING IT,
 STORAGE, RESTROOMS, ELECTRICAL, AND LARGE CONFERENCE
 ROOMS. IN SOME LOCATIONS NO DEVICES ARE SHOWN ON THE
 PLANS. ARE SOME OF THE STORAGE AREAS DISPLAYED ON THE
 PLANS THAT ARE ABSENT OF DEVICES PAPER CLOSETS. PLEASE
 PROVIDE RATIONALE FOR MISSING DEVICES.
  
 4. PLEASE INDICATE ON THE PLANS WHAT THE VOICE
 EVACUATION MESSAGE IS EXPECTED TO ADVISE PERSONS IN THE
 BUILDING.
  
 5. SIGNALING APPLIANCES MISSING FROM MENS AND WOMENS
 RESTROOM NEAR STAIR # 3 ON PAGE FA-02.
  
 6. CORRIDOR BELOW SECURITY DESK APPEAR TO CONTAIN
 INSUFFICIENT SIGNALING APPLIANCES ON PAGE FA-03.
  
 7. THERE DOES NOT APPEAR TO BE ENOUGH SIGNALING
 APPLIANCES ON PAGE FA-05.
  
 8. ON PAGE FA-06 NO INITIATING DEVICES SHOWN AT TOP OF
 THE ATRIUM. IS THIS CORRECT.
  
 9. NO MANUAL PULL STATIONS SHOWN IN PARKING GARAGE. IS
 THIS CORRECT.
  
 10. PLEASE INDICATE ON THE DRAWINGS THE SEQUENCE FOR
 REPLACING FIRE ALARM EQUIPMENT AND STILL BE ABLE TO
 PROVIDE FIRE ALARM COVERAGE FOR THE BUILDING.
  
 11. WHAT EXISTING DEVICES ARE PRESENT IN THE
 CONDOMINIUMS.
  
 12. THE NEW FIRE ALARM SYSTEM WHEN COMPLETED SHALL BE
 MONITORED BY A UL LISTED CENTRAL STATION APPROVED FOR
 CENTRAL STATION SERVICE.
  
 13. WHEN SYSTEM IS COMPLETED, SYSTEM IS TO BE TESTED
 AND APPROVED BY CITY OFFICIALS.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-02 Cont ID  
Sent By kstevens Date 2009-09-02 Time 11:25 Rev Time 0.00
Received By kstevens Date 2009-09-02 Time 11:25 Sent To  
Notes
2009-09-02 11:25:35SENT TO FIRE.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-07-16 Cont ID  
Sent By rmcdouga Date 2009-07-16 Time 16:49 Rev Time 0.00
Received By rmcdouga Date 2009-07-16 Time 16:49 Sent To  
Notes
2009-07-16 16:49:54TO FIRE