Plan Review Details - Permit 09070208
Plan Review Stops For Permit 09070208
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-08-18 Cont ID  
Sent By jwitmer Date 2009-08-18 Time 10:29 Rev Time 0.33
Received By jwitmer Date 2009-08-18 Time 10:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-07-23 Cont ID  
Sent By jwitmer Date 2009-07-20 Time 14:01 Rev Time 0.77
Received By jwitmer Date 2009-07-20 Time 13:40 Sent To  
Notes
2009-07-20 14:36:10PAST COMMENET WERE IN ERROR, PAST OR REVIEWED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-08-13 Cont ID  
Sent By btrobaug Date 2009-08-13 Time 13:36 Rev Time 0.00
Received By btrobaug Date 2009-08-13 Time 13:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-07-22 Cont ID  
Sent By btrobaug Date 2009-07-22 Time 13:21 Rev Time 0.00
Received By btrobaug Date 2009-07-22 Time 11:07 Sent To  
Notes
2009-07-22 11:50:06 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA BUILDING CODE, 2009 REVISIONS, 2005
 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 13-415.AB.5 INTERIOR LIGHTING POWER, SCOPE. THE
 INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR A
 SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY THE SPACE-BY-SPACE METHOD
 DESCRIBED IN SECTION 13-415.B.1. TRADE-OFFS OF INTERIOR
 LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING
 FOR WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN
 USED ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING
 POWER IDENTIFIED IN ACCORDANCE WITH SECTION
 13-415.AB.5.1 SHALL NOT EXCEED THE INTERIOR LIGHTING
 POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH
 SECTION13-415.B.1*** SHOW COMPLIANCE ON THE PLAN. THIS
 CAN BE DEMONSTRATED ON THE PLANS INDICATING THE
 WATTAGES OF THE LUMINAIRES CHOSEN FOR THE PROJECT
 CONFORM TO THE DENSITY REQUIREMENTS. INDICATE WATTAGES
 ON THE FIXTURE SCHEDULE TO CORRELATE WITH THE ONES IN
 THE CALCULATIONS.
  
 2} SUBMIT A LEGEND OF FIXTURE TYPES AND WATTAGES ON THE
 PLAN TO CORRELATE WITH THE ONES IN THE CALCULATIONS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-08-14 Cont ID  
Sent By mawillia Date 2009-08-14 Time 11:28 Rev Time 0.00
Received By mawillia Date 2009-08-14 Time 11:19 Sent To  
Notes
2009-08-14 11:28:34*****RE-STAMP*****
  
 PLAN SHEETS A-1 AND ME-1 WERE STAMPED, INITIALED, AND
 DATED; PREVIOUSLY FIRE-STAMPED ON 08/04/2009.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-08-04 Cont ID  
Sent By mawillia Date 2009-08-04 Time 12:16 Rev Time 0.00
Received By mawillia Date 2009-08-04 Time 12:06 Sent To  
Notes
2009-08-04 12:12:38*****APPROVED*****
  
 PLAN SHEETS A-1 AND ME-1 WERE STAMPED, INITIALED, AND
 DATED.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-08-13 Cont ID  
Sent By jgomez Date 2009-08-13 Time 10:56 Rev Time 0.00
Received By jgomez Date 2009-08-13 Time 10:56 Sent To  
Notes
2009-08-13 10:58:54SENT TO COMMERCIAL BOX C11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-08-04 Cont ID  
Sent By mawillia Date 2009-08-04 Time 12:11 Rev Time 0.00
Received By mawillia Date 2009-07-14 Time 13:33 Sent To  
Notes
2009-07-14 13:33:49B-6

Review Stop M MECHANICAL (A/C)
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rregueir Date 2009-10-08 Time 07:39 Sent To  
Notes
2009-10-08 07:57:30**PROVISO**
  
 1. RETURN AIR TRANSFER DUCT AT OFFICE NOT SIZED TO MEET
 BALANCED RETURN EXCEPTIONS UNDER FBC-M 601.4. A FIELD
 TEST WILL BE REQUIRED AT FINAL INSPECTION TO CHECK FOR
 PRESSURE DIFFERENTIAL OF 0.01 INCHES WC OR LESS PER
 FBC-M 601.4.
  
 2. PROVIDE DOCUMENTATION TO FIELD INSPECTOR
 DEMONSTRATING A MATCHED SYSTEM BETWEEN THE NEW AHU AND
 THE EXISTING CU IN ACCORDANCE WITH FBC-B 13-101.6.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-08-27 Cont ID  
Sent By rregueir Date 2009-08-27 Time 18:26 Rev Time 0.00
Received By rregueir Date 2009-08-27 Time 18:26 Sent To  
Notes
2009-08-27 18:27:07**REVISION REQUIRED**
 1. REVISE PLANS SHOWING MISSING DUCT SIZES AT TRANSFERS
 FOR BATHROOM AND OFFICE.
 2. PROVIDE DOCUMENTATION SHOWING PROPOSED AHU AND
 CONDENSER COMPRISE A MATCHED SYSTEM IN ACCORDANCE WITH
 FBC-B 13-101.6.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2009-07-29 Cont ID  
Sent By rregueir Date 2009-07-29 Time 11:13 Rev Time 0.00
Received By rregueir Date 2009-07-29 Time 11:11 Sent To  
Notes
2009-07-29 11:13:42**REVISION REQUIRED**
 1. REVISE PLANS SHOWING MISSING DUCT SIZES AT TRANSFERS
 FOR BATHROOM AND OFFICE.
 2. PROVIDE DOCUMENTATION SHOWING PROPOSED AHU AND
 CONDENSER COMPRISE A MATCHED SYSTEM IN ACCORDANCE WITH
 FBC-B 13-101.6.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-08-19 Cont ID  
Sent By kstevens Date 2009-08-19 Time 10:18 Rev Time 0.00
Received By kstevens Date 2009-08-19 Time 10:18 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-07-14 Cont ID  
Sent By kstevens Date 2009-07-14 Time 16:34 Rev Time 0.00
Received By kstevens Date 2009-07-14 Time 16:25 Sent To  
Notes
2009-07-14 16:58:17 
  
 SEPARATE PLUMBING PERMIT AND PLANS ARE REQUIRED.
 *****I N C L U D I N G*****
  
 A. SUBMIT A SANITARY ISOMETRIC RISER DIAGRAM SHOWING
 ALL PIPE SIZES, TRAPS & VENTS PER SECTIONS 701.1, 901.1
 & 1001.1.
 B. SUBMIT A WATER ISOMETRIC RISER DIAGRAM SHOWING ALL
 PIPE SIZES, VALVES & (WHERE REQUIRED BY SECTION 604.9)
 WATER HAMMER ARRESTORS. SECTION 601.1.
 C. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED.
 SHOW THE REQUIRED DRINKING FOUNTAIN ON THE FLOOR PLAN
 AND SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.15 WITH ALL SUBSECTIONS AS WELL AS SECTION
 11-4.1.3(10(A) PROVISIONS FOR THOSE WHO HAVE DIFFICULTY
 BENDING OR STOOPING.
  
 ALL INFORMATION IS REQUIRED PRIOR TO STARTING ANY
 PLUMBING WORK.
  
  