Plan Review Details - Permit 09070076
| Plan Review Stops For Permit 09070076 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2009-11-16 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-11-16 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-11-16 |
Time |
13:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2009-10-26 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-10-26 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-10-26 |
Time |
13:50 |
Sent To |
PC |
|
| Notes |
| 2009-10-26 13:53:52 | ROOF A/C DUCTWORK INSTALLATION, BUILDING REVIEW | | | CHECKLIST. | | | 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- ENGINEER DETAIL NEEDS TO CLARIFY IF TAPCONS ARE TO | | | BE ANCHORED TO THE ROOF TRUSSES OR JUST TO ROOF | | | SHEATHING. IF TAPCONS ARE TO BE ATTACHED TO THE ROOF | | | SHEATHING, THEN PROVIDE CALCULATIONS SHOWING HOW THE | | | ROOF SHEATHING ALONE WILL SUPPORT THE DUCTWORK FOR THE | | | SPECIFIED WIND LOADS AS REQUIRED BY SEC. R301 OF 2007 | | | FLORIDA RESIDENTIAL CODE. | | | | | | 2- ENGINEER TO SPECIFY DESIGN CRITERIA, INCLUDING | | | CURRENT BUILDING CODE AND REVISIONS, BUILDING EXPOSURE, | | | WIND LOADING, ETC. | | | ***NOTE: ENGINEER TO TAKE INTO CONSIDERATION THAT | | | ACCORDING TO SEC. R301.2.1.4.3 OF 2009 REVISIONS TO THE | | | 2007 FLORIDA RESIDENTIAL CODE, THIS BUILDING IS LOCATED | | | ON EXPOSURE "C". | | | | | | 3- ENGINEER TO PROVIDE COMPLETE SPECIFICATIONS FOR TYPE | | | OF ANGLE OR STRAP TO BE USED. DRAWING ONLY SPECIFY | | | ANGLE OR STRAP. THIS IS NO ENOUGH INFORMATION TO VERIFY | | | IF PROPOSED ANCHORING IS ADEQUATE TO RESIST THE | | | CALCULATED LOADS AS REQUIRED BY SEC. R301 OF 2007 | | | FLORIDA RESIDENTIAL CODE. | | | | | | 4- PROVIDE SPECIFICATIONS FOR TYPE OF DUCTWORK TO BE | | | USED TO RESIST THE CALCULATED DESIGN LOADS OF SEC. R301 | | | OF 2007 FLORIDA RESIDENTIAL CODE. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
N |
Date |
2009-08-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-08-17 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-08-17 |
Time |
10:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2009-08-17 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-08-17 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-08-17 |
Time |
10:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2009-07-20 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2009-07-20 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2009-07-20 |
Time |
10:20 |
Sent To |
PC |
|
| Notes |
| 2009-07-20 11:29:44 | RESIDENTIAL (R3) NEW A/C SYSTEM MECHANICAL REVIEW | | | CHECKLIST. | | | 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- PROVIDE COMPLETE ENERGY CALCULATIONS. ONLY THE FIRST | | | PAGE OF THE CALCULATIONS WERE SUBMITTED. | | | ***NOTE: FORM 1100A-08 SUBMITTED IS THE METHOD A AND | | | REQUIRES ENTIRE HOUSE TO COMPLY WITH CURRENT CODE. FOR | | | NEW A/C SYSTEM ON EXISTING HOUSE THE REQUIRED FORM IS | | | 1100B-08 FOR THE METHOD B AND IT ONLY APPLIES TO THE | | | SPECIFIC SYSTEM TO BE INSTALLED. SEE SEC. N1100.0.8.1 | | | OF 2007 FLORIDA RESIDENTIAL CODE. | | | | | | 2- PROVIDE A/C SYSTEM COOLING LOAD CALCULATIONS AS | | | REQUIRED BY SEC. N1107.AB.1 OF 2007 FLORIDA RESIDENTIAL | | | CODE. | | | | | | 3- SHOWN ON PLANS LOCATION OF CONDENSER UNIT FOR ZONING | | | REVIEW OF THE SETBACKS. CONTACT ZONING AT 822-1435 OR | | | 805-6720 FOR REQUIREMENTS. | | | | | | 4- CONTRACTOR/INSTALLER TO PROVIDE HIS NAME AND SIGN | | | HIS PLANS AS REQUIRED BY FLORIDA STATUTE SEC. 471.003. | | | | | | 5- PLANS TO SHOW COMPLETE INFORMATION (SEC. 106.1.1 OF | | | CITY AMENDMENTS TO FBC): | | | A) SIZE OF ROOMS AND CFM'S ON EACH ROOM. | | | B) DUCT TYPE AND INSULATION. | | | C) BALANCE RETURN (SEC. M1602.4 OF 2007 FL. RESIDENTIAL | | | CODE). | | | D) BATHROOM EXHAUST FAN. | | | E) CONDENSATE LINES. | | | | | | JULIO GOMEZ | | | PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2009-08-13 |
|
|
Cont ID |
|
| Sent By |
mcruz |
Date |
2009-08-13 |
Time |
15:53 |
Rev Time |
0.00 |
| Received By |
mcruz |
Date |
2009-08-13 |
Time |
15:48 |
Sent To |
B |
|
| Notes |
| 2009-08-13 15:53:20 | AS NOTED ON PLANS, THE A/C EQUIMENT SHALL BE NO LESS | | | THAN SIX FEET FROM THE SIDE PROPERTY LINE. | | | | | | MAGGIE CRUZ, ASSOCIATE PLANNER | | | PLANNING AND ZONING DEPARTMENT | | | TEL: (561) 822-1444 OR (561) 805-6720 | | | E-MAIL: [email protected] | | | | | | ROUTED TO JG |
|
|
|