Plan Review Details - Permit 09070076
Plan Review Stops For Permit 09070076
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-11-16 Cont ID  
Sent By jgomez Date 2009-11-16 Time 13:14 Rev Time 0.00
Received By jgomez Date 2009-11-16 Time 13:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-10-26 Cont ID  
Sent By jgomez Date 2009-10-26 Time 13:50 Rev Time 0.00
Received By jgomez Date 2009-10-26 Time 13:50 Sent To PC
Notes
2009-10-26 13:53:52ROOF A/C DUCTWORK INSTALLATION, BUILDING REVIEW
 CHECKLIST.
 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ENGINEER DETAIL NEEDS TO CLARIFY IF TAPCONS ARE TO
 BE ANCHORED TO THE ROOF TRUSSES OR JUST TO ROOF
 SHEATHING. IF TAPCONS ARE TO BE ATTACHED TO THE ROOF
 SHEATHING, THEN PROVIDE CALCULATIONS SHOWING HOW THE
 ROOF SHEATHING ALONE WILL SUPPORT THE DUCTWORK FOR THE
 SPECIFIED WIND LOADS AS REQUIRED BY SEC. R301 OF 2007
 FLORIDA RESIDENTIAL CODE.
  
 2- ENGINEER TO SPECIFY DESIGN CRITERIA, INCLUDING
 CURRENT BUILDING CODE AND REVISIONS, BUILDING EXPOSURE,
 WIND LOADING, ETC.
 ***NOTE: ENGINEER TO TAKE INTO CONSIDERATION THAT
 ACCORDING TO SEC. R301.2.1.4.3 OF 2009 REVISIONS TO THE
 2007 FLORIDA RESIDENTIAL CODE, THIS BUILDING IS LOCATED
 ON EXPOSURE "C".
  
 3- ENGINEER TO PROVIDE COMPLETE SPECIFICATIONS FOR TYPE
 OF ANGLE OR STRAP TO BE USED. DRAWING ONLY SPECIFY
 ANGLE OR STRAP. THIS IS NO ENOUGH INFORMATION TO VERIFY
 IF PROPOSED ANCHORING IS ADEQUATE TO RESIST THE
 CALCULATED LOADS AS REQUIRED BY SEC. R301 OF 2007
 FLORIDA RESIDENTIAL CODE.
  
 4- PROVIDE SPECIFICATIONS FOR TYPE OF DUCTWORK TO BE
 USED TO RESIST THE CALCULATED DESIGN LOADS OF SEC. R301
 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2009-08-17 Cont ID  
Sent By jgomez Date 2009-08-17 Time 10:33 Rev Time 0.00
Received By jgomez Date 2009-08-17 Time 10:33 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-08-17 Cont ID  
Sent By jgomez Date 2009-08-17 Time 10:38 Rev Time 0.00
Received By jgomez Date 2009-08-17 Time 10:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-07-20 Cont ID  
Sent By jgomez Date 2009-07-20 Time 10:20 Rev Time 0.00
Received By jgomez Date 2009-07-20 Time 10:20 Sent To PC
Notes
2009-07-20 11:29:44RESIDENTIAL (R3) NEW A/C SYSTEM MECHANICAL REVIEW
 CHECKLIST.
 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE COMPLETE ENERGY CALCULATIONS. ONLY THE FIRST
 PAGE OF THE CALCULATIONS WERE SUBMITTED.
 ***NOTE: FORM 1100A-08 SUBMITTED IS THE METHOD A AND
 REQUIRES ENTIRE HOUSE TO COMPLY WITH CURRENT CODE. FOR
 NEW A/C SYSTEM ON EXISTING HOUSE THE REQUIRED FORM IS
 1100B-08 FOR THE METHOD B AND IT ONLY APPLIES TO THE
 SPECIFIC SYSTEM TO BE INSTALLED. SEE SEC. N1100.0.8.1
 OF 2007 FLORIDA RESIDENTIAL CODE.
  
 2- PROVIDE A/C SYSTEM COOLING LOAD CALCULATIONS AS
 REQUIRED BY SEC. N1107.AB.1 OF 2007 FLORIDA RESIDENTIAL
 CODE.
  
 3- SHOWN ON PLANS LOCATION OF CONDENSER UNIT FOR ZONING
 REVIEW OF THE SETBACKS. CONTACT ZONING AT 822-1435 OR
 805-6720 FOR REQUIREMENTS.
  
 4- CONTRACTOR/INSTALLER TO PROVIDE HIS NAME AND SIGN
 HIS PLANS AS REQUIRED BY FLORIDA STATUTE SEC. 471.003.
  
 5- PLANS TO SHOW COMPLETE INFORMATION (SEC. 106.1.1 OF
 CITY AMENDMENTS TO FBC):
 A) SIZE OF ROOMS AND CFM'S ON EACH ROOM.
 B) DUCT TYPE AND INSULATION.
 C) BALANCE RETURN (SEC. M1602.4 OF 2007 FL. RESIDENTIAL
 CODE).
 D) BATHROOM EXHAUST FAN.
 E) CONDENSATE LINES.
  
 JULIO GOMEZ
 PLANS EXAMINER
 (561)805-6712

Review Stop Z ZONING
Rev No 1 Status P Date 2009-08-13 Cont ID  
Sent By mcruz Date 2009-08-13 Time 15:53 Rev Time 0.00
Received By mcruz Date 2009-08-13 Time 15:48 Sent To B
Notes
2009-08-13 15:53:20AS NOTED ON PLANS, THE A/C EQUIMENT SHALL BE NO LESS
 THAN SIX FEET FROM THE SIDE PROPERTY LINE.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  
 ROUTED TO JG