| 2009-07-06 10:27:13 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. |
| | 2007 FL. RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION WAS UPDATED AS REQUIRED BY SEC. 108.3 OF |
| | CITY AMENDMENTS TO FBC. THEREFORE, OWES $52.47 FOR |
| | UPDATED PERMIT VALUATION. |
| | |
| | 2- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTES. |
| | |
| | 3- DADE COUNTY PRODUCT APPROVAL NOA 07-1203.01 |
| | SUBMITTED WAS SUPERSEDED BY MIAMI-DADE COUNTY. SEE |
| | ATTACHED COPY. PROVIDE NOA 09-0224.01 WHICH IS THE ONE |
| | THAT SUPERSEDES NOA SUBMITTED. |
| | |
| | 4- CLEARLY MARK ON NOA SPECIFIC APPROVED ASSEMBLY TO BE |
| | INSTALLED. |
| | |
| | 5- CLEARLY MARK ON NOA SPECIFIC BASE SHEET FASTENING |
| | OPTION ON SELECTED APPROVED ASSEMBLY. |
| | |
| | 6- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR |
| | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS |
| | REQUIRED BY GENERAL LIMITATION #7. SEE GENERAL |
| | LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED. APPROVED |
| | ASSEMBLIES WITH GENERAL LIMITATION #9 CAN'T BE USED |
| | BECAUSE THEY DON'T MEET THE UPLIFT PRESSURES OF THIS |
| | BUILDING AND NAIL ENHANCING IS NOT ALLOWED. |
| | ***NOTE: DESIGN PROFESSIONAL DOING THE CALCULATIONS TO |
| | HAVE IN CONSIDERATION THAT THIS BUILDING IS LOCATED ON |
| | EXPOSURE "C' AS REQUIRED BY 2009 REVISIONS TO THE 2007 |
| | FLORIDA RESIDENTIAL CODE. |
| | |