Plan Review Details - Permit 09070062
Plan Review Stops For Permit 09070062
Review Stop G GAS REVIEW
Rev No 3 Status P Date 2009-08-18 Cont ID  
Sent By kstevens Date 2009-08-18 Time 09:38 Rev Time 0.00
Received By kstevens Date 2009-08-18 Time 09:38 Sent To  
Notes
2009-08-18 09:39:06REVISION TO GAS ISOMETRIC RISER DIAGRAM OK (REMOVED
 REGULATOR FROM FUTURE BBQ)

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2009-07-20 Cont ID  
Sent By kstevens Date 2009-07-20 Time 10:03 Rev Time 0.00
Received By kstevens Date 2009-07-20 Time 10:03 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-07-07 Cont ID  
Sent By kstevens Date 2009-07-07 Time 10:35 Rev Time 0.00
Received By kstevens Date 2009-07-07 Time 10:35 Sent To  
Notes
2009-07-07 10:53:39DENIED
 REFERENCE:
 FBC-2007 RESIDENTIAL
  
 A. THE FOLLOWING INFORMATION IS REQUIRED FOR THE GAS
 PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2007 RESIDENTIAL OR
 2007 FUEL GAS CODE. -- THE RISER DIAGRAM SUBMITTED IS
 NOT IN ISOMETRIC FORM. (SEE EXAMPLE DRAWN FOR
 EXPLAINATION).
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED. -- PIPING
 MATERIAL FROM METER AND AFTER THE WATER HEATER NOT
 INDICATED.
  
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE
 SEC. G2413.2.
  
 B. THE VALUE ON THE PERMIT APPLICATION APPEARS LOW. THE
 VALUE ON THE PERMIT APPLICATION MUST INCLUDE THE TOTAL
 COST OF LABOR, MATERIALS AND DESIGN.
 PER (W.P.B AS AMENDED) SECTION 108.3 BUILDING PERMIT
 VALUATION. IF, IN THE OPINION OF THE BUILDING OFFICIAL,
 THE CLAIMED VALUATION OF BUILDING, ALTERATION,
 STRUCTURAL, ELECTRICAL, GAS, MECHANICAL OR PLUMBING
 SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE
 APPLICATION, THE PERMIT SHALL BE DENIED. -- THE COST OF
 THE GAS APPLIANCES SHALL BE INCLUDED IN THE VALUATION
 OF THE PERMIT.
  
 C. A LISTED SHUT OFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR. SECTION
 G2420.4.
  
 D. DRIPS/SEDIMENT TRAPS REQUIRED DOWNSTREAM OF THE
 EQUIPMENT SHUT OFF VALVE. SECTION G2419.2/G2419.4.
  
 E. MANUF. SPEC SHEETS REQUIRED FOR THE REGULATORS.
 REGULATORS SHALL BE LISTED AND THE OUTLET BTU CAPACITY
 OF THE REGULATOR SHALL BE INDICATED. PLEASE SHOW MODEL
 OF REGULATOR BEING INSTALLED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS