| Plan Review Stops For Permit 09060703 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2009-07-29 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-07-29 |
Time |
09:55 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-07-29 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2009-07-29 09:55:50 | RESTAMPED D1 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2009-07-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-07-08 |
Time |
10:20 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2009-07-08 |
Time |
9:25 |
Sent To |
|
|
| Notes |
| 2009-07-08 10:21:22 | INTERIOR DEMO 15 FLOOR SPACES A & B |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2009-07-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-07-30 |
Time |
14:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-07-30 |
Time |
14:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-07-04 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-07-29 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-07-04 |
Time |
10:57 |
Sent To |
|
|
| Notes |
| 2009-07-04 10:57:38 | ** DENIED PLANS** | | | | | | 1) NOTE: THE APPLIED SCOPE OF WORK IS NOT CLEAR. THE | | | APPLICATION STATES INTERIOR DEMOLITION ONLY YET THE | | | PLANS SUBMITTED ARE FOR DEMO WORK AND REMODEL WORK. | | | | | | 2) NOTE: PLEASE SHOW LIGHTING FOR EGRESS PER NFPA-101 | | | 7.8, 7.9.2.1,.2.2. NO BATTERY BACK UP FIXTURES SHOWN | | | FOR MINIMUM EGRESS LIGHTING. THIS IS SHOWN FROM AN | | | EXISTING EMERGENCY CIRCUIT WHICH IS OK AS LONG AS THE | | | BUILDING IS NOT OCCUPIED UNDER EMERGENCY POWER. | | | ** PLEASE KEEP IN MIND THE BUILDING SHALL NOT BE | | | OCCUPIED UNDER EMERGENCY POWER. IF OCCUPIED UNDER | | | EMERGENCY POWER AND THE GENERATOR BREAKER IS TRIPPED OR | | | LOST THEN NO EGRESS LIGHTING WOULD BE PROVIDED. THIS | | | COULD LEAVE LIFE SAFETY EGRESS AREAS IN TOTAL DARKNESS. | | | PLEASE BE SURE TO GO OVER THIS WITH BUILDING | | | OWNER/MANAGEMENT. | | | OBTAIN IN WRITING THAT BUILDING SHALL NOT BE OCCUPIED | | | UNDER EMERGENCY POWER. | | | | | | | | | ** SOME ITEMS MAY BE REDLINED AS PROVISO HOWEVER SCOPE | | | IF NOT CLEAR AT THIS TIME. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2009-07-29 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-07-29 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-07-29 |
Time |
13:30 |
Sent To |
E |
|
| Notes |
| 2009-07-29 13:43:31 | ***** APPROVED***** | | | | | | PLAN SHEETS D1.1 AND E1 WERE STAMPED, INITIALED, AND | | | DATED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2009-07-15 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-07-15 |
Time |
13:44 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-07-15 |
Time |
13:16 |
Sent To |
|
|
| Notes |
| 2009-07-15 13:43:45 | ******PARTIAL APPROVAL***** | | | | | | | | | THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN | | | THE ELECTRICAL EXAMINER'S COMMENTS AS WELL AS THE | | | FOLLOWING HAVE BEEN ADDRESSED: | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241- 2004 | | | EDITION. ON SHEET "T" , ADD COMMENT TO THE GENERAL | | | NOTES OR NFPA 241 (2004 EDITION) UNDER CODES. | | | | | | 2. ON SHEET D1.1, CLARIFY GENERAL NOTE #5 "SPRINKLERS | | | TO BE TURNED UP" . | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2009-07-15 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-07-15 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-07-01 |
Time |
09:18 |
Sent To |
|
|
| Notes |
| 2009-07-01 09:32:45 | WAITING FOR THE BOB BOARD IN THE INCOMMING CUBICLE |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2009-07-13 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-07-13 |
Time |
16:13 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-07-13 |
Time |
16:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2009-07-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-07-10 |
Time |
16:25 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-07-10 |
Time |
16:25 |
Sent To |
|
|
| Notes |
| 2009-07-10 16:26:00 | DEAD ENDS PROHIBITED. SECTION 704.5. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2009-07-06 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2009-07-06 |
Time |
10:30 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2009-07-06 |
Time |
10:30 |
Sent To |
|
|
| Notes |
| 2009-07-06 10:30:35 | BUILDING VALUE IN EXCESS OF $57 MIL. |
|
|