| 2009-07-03 15:22:45 | |
| | |
| | ** DENIED |
| | |
| | ** BASED ON THE COMMENTS BELOW. IF A PERMIT ONLY FOR |
| | UNDERGROUND CONDUIT INSTALLATIONS WOULD ALLEVIATE ANY |
| | DELAYS IN THE PROJECT START DATE THIS MAY BE DONE UNDER |
| | SEPARATE PERMIT APPLICATION(S). |
| | GAVE INFORMATION TO CONTRACTOR AS THIS MAY BE AN OPTION |
| | TO GET STARTED. |
| | |
| | |
| | 1) NOTE: TWO PERMIT APPLICATIONS WERE SUBMITTED FOR |
| | 09060658 AND 09060657. BOTH FOR THE SAME LOCATION |
| | ADDRESS OF * @151 S FLAGLER*. PER THE PLANS THERE ARE |
| | TWO SERVICE POINTS WHICH NEED TO CONTAIN SEPARATE |
| | ADDRESSES. |
| | AN E-MAIL WAS SENT TO ADDRESSING REVIEWER TO |
| | ADJUSTMENTS. PLEASE BE SURE ADDRESS IS NOTED ON PLANS. |
| | FOR ANY SHEETS WHICH DO NOT NEED TO BE REVISED FOR CODE |
| | COMMENTS MAY HAVE NEW ADDRESS PLACED NEATLY ON TITLE |
| | BLOCKS. |
| | FAC 61G15-23.002, FBC 106.5 FOR RECORD DOCUMENTS. |
| | |
| | 2) NOTE: PLEASE SEE RISER. THE NEW MAIN ON THE LOAD |
| | SIDE OF THE FPL METER INDICATES TWO SEPARATE CONDUITS |
| | TO THE TRANSFORMER. HOWEVER THE RISER ONLY INDICATES |
| | CONDUCTORS FOR ONE CONDUIT. |
| | WHAT IS THE SECOND CONDUIT? AS IT IS NOT KNOWN IT IS |
| | UNCLEAR TO REVIEW FOR SPECIFIC CODE REQUIREMENTS. |
| | 240.4, 310.16, 215.5 FBC 106.1.1 FOR COMPLETION, |
| | CLARITY, INFORMATION AND COORDINATION OF PLANS. |
| | |
| | 3) NOTE: THE RISER INDICATES TAPS FROM THE SECONDARY |
| | SIDE OF THE TRANSFORMER GOING INTO A GUTTER THEN BEING |
| | TAPPED AGAIN TO GO TO EACH OF THE PANELS. THIS WOULD BE |
| | TAPPING A TAP CONDUCTOR WHICH IS NOT PERMITTED. |
| | EACH SET OF TAPPED CONDUCTORS MAY GO TO EACH PANEL |
| | HENCE EACH TERMINATING IN OVER CURRENT PROTECTION AS |
| | REQUIRED. |
| | 240.21,310.16,240.4 |
| | |
| | 4) NOTE: RISER ONLY INDICATES ONE GROUND ROD. PLEASE |
| | SEE 250.56. PLEASE EXPLAIN HOW THE REQUIRED RESISTANCE |
| | WILL BE OBTAINED IN SPECIFIC SOIL CONDITIONS BASED ONLY |
| | ON THE ONE 10FT GROUND ROD. |
| | |
| | 5) NOTE: SPOKE TO CONTRACTOR. WIND LOAD CALCULATIONS |
| | ARE TO BE SUBMITTED. PLEASE BE SURE CALCULATIONS |
| | COORDINATE WITH BOTH TYPE OF POLES SUBMITTED AND SHOWN |
| | ON PLANS. |
| | |
| | 6) NOTE: PLEASE KNOW THAT PART OF A PROVISO WHICH MAY |
| | BE SET UP IS FOR THE PANEL SCHEDULE TO BE SPECIFIC TO |
| | LOCATIONS. STATING *RECEPTACLES*, UPPER/LOWER ETC IS |
| | NOT SPECIFIC. ALPHA/NUMERICAL DESIGNATIONS MAY USED AT |
| | LATER DATE. |
| | 408.4 |
| | |
| | 7) NOTE: PLEASE VERIFY WHY THE RISER DOES NOT INDICATE |
| | PANELS LC AND LD AS MCB WITH CONTACTOR AS LA AND LB. |
| | BASED ON PANEL SCHEDULES THESE ARE ALL 150AMP MCB |
| | PANELS WITH CONTACTORS. IS THIS THE CASE? |
| | |
| | 8) NOTE: PLEASE CLARIFY THE AIC RATING OF EACH PANEL. |
| | STATES 10K, HOWEVER IS THIS FOR MAIN, BRANCH BREAKERS |
| | OR BOTH? |
| | |
| | 9) NOTE: THE RISER INDICATES MAIN AS 2-POLE OCP WITH |
| | 300AMP FUSES TO THE 100K TRANSFORMER WITH 3-350MCM'S |
| | AND 1-#4 EQUIPMENT GROUND. PLEASE EXPLAIN A GROUNDED |
| | (NEUTRAL) CONDUCTOR BEING SHOWN TO A TRANSFORMER WHICH |
| | IS SEPARATELY DERIVED. |
| | 250.20,250.30,250.50,250.66 |
| | |
| | 10) NOTE: SERVICE EQUIPMENT SHALL BE ABOVE THE BASE |
| | FLOOD ELEVATION. PLEASE OBTAIN THE BFE BASED ON FEMA |
| | CHARTS. THIS IS FLOOD ZONE A. |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |