| 2009-07-03 15:48:43 | |
| | ** DENIED |
| | |
| | ** BASED ON THE COMMENTS BELOW. IF A PERMIT ONLY FOR |
| | UNDERGROUND CONDUIT INSTALLATIONS WOULD ALLEVIATE ANY |
| | DELAYS IN THE PROJECT START DATE THIS MAY BE DONE UNDER |
| | SEPARATE PERMIT APPLICATION(S). |
| | GAVE INFORMATION TO CONTRACTOR AS THIS MAY BE AN OPTION |
| | TO GET STARTED. |
| | |
| | |
| | 1) NOTE: TWO PERMIT APPLICATIONS WERE SUBMITTED FOR |
| | 09060658 AND 09060657. BOTH FOR THE SAME LOCATION |
| | ADDRESS OF * @151 S FLAGLER*. PER THE PLANS THERE ARE |
| | TWO SERVICE POINTS WHICH NEED TO CONTAIN SEPARATE |
| | ADDRESSES. |
| | AN E-MAIL WAS SENT TO ADDRESSING REVIEWER TO |
| | ADJUSTMENTS. PLEASE BE SURE ADDRESS IS NOTED ON PLANS. |
| | FOR ANY SHEETS WHICH DO NOT NEED TO BE REVISED FOR CODE |
| | COMMENTS MAY HAVE NEW ADDRESS PLACED NEATLY ON TITLE |
| | BLOCKS. |
| | FAC 61G15-23.002, FBC 106.5 FOR RECORD DOCUMENTS. |
| | |
| | 2) NOTE: PLEASE SEE RISER. THERE IS AN EQUIPMENT |
| | GROUNDING CONDUCTOR SHOWN FROM FPL METER TO THE FIRST |
| | MEANS OF DISCONNECT. AS THE NEC REQUIRES THE FIRST |
| | MEANS OF DISCONNECT TO BE BONDED IF AN EQUIPMENT |
| | GROUNDING CONDUCTOR IS INSTALLED THIS WOULD CREATE A |
| | PARALLEL PATH WITH THE GROUNDED/NEUTRAL CONDUCTOR. THIS |
| | COULD CREATE OBJECTIONABLE CURRENT WHICH IS NOT |
| | PERMITTED. |
| | PLEASE SEE 250.24, 250.6. |
| | |
| | 3) NOTE: THE RISER INDICATES TAPS FROM THE SECONDARY |
| | SIDE OF THE TRANSFORMER GOING INTO A GUTTER THEN BEING |
| | TAPPED AGAIN TO GO TO EACH OF THE PANELS. THIS WOULD BE |
| | TAPPING A TAP CONDUCTOR WHICH IS NOT PERMITTED. |
| | EACH SET OF TAPPED CONDUCTORS MAY GO TO EACH PANEL |
| | HENCE EACH TERMINATING IN OVER CURRENT PROTECTION AS |
| | REQUIRED. |
| | 240.21,310.16,240.4 |
| | |
| | 4) NOTE: RISER ONLY INDICATES ONE GROUND ROD. PLEASE |
| | SEE 250.56. PLEASE EXPLAIN HOW THE REQUIRED RESISTANCE |
| | WILL BE OBTAINED IN SPECIFIC SOIL CONDITIONS BASED ONLY |
| | ON THE ONE 10FT GROUND ROD. |
| | |
| | 5) NOTE: SPOKE TO CONTRACTOR. WIND LOAD CALCULATIONS |
| | ARE TO BE SUBMITTED. PLEASE BE SURE CALCULATIONS |
| | COORDINATE WITH BOTH TYPE OF POLE SUBMITTED AND SHOWN |
| | ON PLANS. |
| | |
| | 6) NOTE: PLEASE KNOW THAT PART OF A PROVISO WHICH MAY |
| | BE SET UP IS FOR THE PANEL SCHEDULE TO BE SPECIFIC TO |
| | LOCATIONS. STATING *RECEPTACLES*, UPPER/LOWER ETC IS |
| | NOT SPECIFIC. ALPHA/NUMERICAL DESIGNATIONS MAY USED AT |
| | LATER DATE. |
| | 408.4 |
| | |
| | 7) NOTE: PLEASE VERIFY THE RISER WHICH INDICATE 4 |
| | PANELS YET ONLY THREE PANEL SCHEDULES WERE SUBMITTED |
| | AND SHOWN. 215.5,408.4, 240.4, 240.21, 310.16. |
| | CAN NOT VERIFY CODE COMPLIANCE IF THERE IS GOING TO BE |
| | ANOTHER PANEL. |
| | |
| | 8) NOTE: PLEASE CLARIFY THE AIC RATING OF EACH PANEL. |
| | STATES 10K, HOWEVER IS THIS FOR MAIN, BRANCH BREAKERS |
| | OR BOTH? |
| | |
| | 9) NOTE: SERVICE EQUIPMENT SHALL BE ABOVE THE BASE |
| | FLOOD ELEVATION. PLEASE OBTAIN THE BFE BASED ON FEMA |
| | CHARTS. THIS IS FLOOD ZONE A. |
| | |
| | 10) NOTE: RISER SHOWS A 2-POLE SINGLE PHASE |
| | INSTALLATION TO THE TRANSFORMER AND THE SAME TO THE |
| | PANELS. ( GUTTER AS SHOWN). PLEASE EXPLAIN THE |
| | GROUNDED/NEUTRAL CONDUCTORS BEING INSTALLED FROM THE |
| | MAIN TO THE TRANSFORMER IF THIS IS A SEPARATELY DERIVED |
| | SYSTEM? |
| | 250.20,250.30,250.50,250.66 ETC |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |