2009-07-17 14:46:30BUILDING PLAN REVIEW
 PERMIT: 09060612
 ADD: 5501 GEORGIA AV.
 CONT: SULLIVAN
 TEL: (561)310-1899
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS, PLEASE UPDATE SHEET
 A-1.
  
 2) PLEASE UPDATE SHEET A-1. 2007 FBC 1609.1.1 & CHAPTER
 35 REFERENECED STANDARDS RECOGNIZES ASCE 7-05 . ALSO
 1603.1.4 WIND DESIGN DATA.
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 2.1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2.2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 2.3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 2.4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
  
 2.5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 3) PLEASE PROVIDE A SITE PLAN INDICATING THE LOCATION
 OF THE ADDITION TO THE STRUCTURE. ADMINISTATIVE CODE
 106.3.5.1.1.(1) THE SURVEY SUBMITTED APPEARS TO BE FOR
 620 BUNKER RD.
 NOTE THIS ADDITION MAY HAVE ISSUES ONCE THE LOCATION IS
 PROVIDED ON THE SITE PLAN.
  
 4) PLEASE PROVIDE THE TYPE OF BUILDING CONSTRUCTION OF
 THE EXISTING BUILDING AND NEW ADDITION. ADMINISTRATIVE
 CODE 106.3.1.1(3).
  
 5) SHEET A-2 INDICATES THE USE OF 12 INCH DEEP BAR
 JOIST THE PLAN IS NOT CLEAR AS TO HOW THE BAR JOIST ARE
 TO BE ANCHORED TO THE CBS WALL ON THE ONE SIDE NOR THE
 DOUBLE 2X10'S, SECTION A INDICATES THE TRUSS BEARING
 PLATE TO BE DESIGNED BY TRUSS MANUFACTURER.
  
 6) SHEET A-22 DETAIL-B INDICATES THE THICKNESS OF THE
 METAL DECK TO BE 22 GAUGE GAL METAL BUT NO MENTION OF
 THE DECK CONNECTION TO BAR JOIST. THE DECK IS PART OF
 THE MAIN WIND FORCE RESISTING SYSTEM, PLEASE INDICATE
 TYPE OF FASTENING AND FREQUENCY. 106.3.5.1.1(8)
 BUILDING ENVELOPE/ ROOF SYSTEMS.
  
 7) PRODUCT APPROVALS: SUBMITTED WAS A POLYGLASS OVER
 WOOD DECKS 07-0822.10, PLEASE SUBMIT THE CORRECT
 PRODUCT APPROVAL FOR METAL DECK WITH INSULATION. RULE
 9B-72. WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 THIS ROOF IS MISSING OR NOT IN COMPLIANCE WITH THE
 FOLLOW ITEMS:
 _XX__ CONTRACTOR FAILED TO INDICATE WHICH SYSTEM TO BE
 USED.
  
 _XX__ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE
 _2& 3__(NOT KNOWN AT THIS TIME) .
  
 NOT KNOWN___ THE SYSTEM PROVIDED STATES LIMITATION# 7,
 SHOULD THE FASTENER RESISTANCE BE LESS THAN THAT
 REQUIRED, AS DETERMINED BY THE BUILDING OFFICIAL, A
 REVISED
 FASTENER SPACING, PREPARED , SIGNED AND SEALED BY A
 FLORIDA REGISTERED PROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOF CONSULTANT MAY BE
 SUBMITTED.
  
 _NOT KNOWN__ THE SYSTEM PROVIDED INDICATES LIMITATION#
 9, NO ENHANCED FASTENING ALLOWED.
  
 8) FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING,
 PROVIDE 2 COPIESR OF PRODUCT TESTING REPORTS, MISSING
 REPORTS ARE AS FOLLOWS:
 8A) FIXED WINDOWS.
  
 9) FEES DUE OF $3.98 STATE RADON FEES.
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-07-24 Cont ID  
Sent By dpalmer Date 2009-07-24 Time 09:35 Rev Time 0.00
Received By dpalmer Date 2009-07-24 Time 09:35 Sent To  
Notes
2009-07-24 09:35:29 
 ** DENIED REVIEW. **
  
 1) NOTE: PLEASE SEE FS 553.73. ALL PLANS SUBMITTED FOR
 PERMIT ON OR AFTER MARCH 1ST 2009 SHALL BE UNDER THE
 FOLLOWING CODES.
 2007 FBC W/ 2009 REVISIONS.
 2005 NFPA-70
 2006 NFPA-101
  
 THESE ARE CODES FOR THIS TRADE REVIEWER.
  
 2) NOTE: LIGHTING CONTROLS PER FBC 13-415.AB.1,.1.1,
 .1.2 ARE NOT MET BY THE USE OF TWO SINGLE POLE
 SWITCHES. MUST MEET PRESCRIPTIVE FOR NEW BEING
 INSTALLED IN BUILDINGS OVER 5K SQ FT.
  
 3) NOTE: PLEASE INDICATE THE LIGHTING PERFORMANCE
 LEVELS FOR NEW SPACE. PLEASE SEE 13-415.AB.5. THE
 LIGHTING FIXTURES NEED TO BE SPECIFIC HOWEVER BASED ON
 THE FIXTURES SHOWN THE PERMITTED LIGHTING ENERGY USE IS
 EXCEEDED.
  
 4) NOTE: PLEASE INDICATE THE LOAD CALCULATIONS PER THE
 NATIONAL ELECTRICAL CODE. THE CALCULATION METHOD SHOWN
 INDICATES A *.3* WATTS PER SQFT. NO LOCATION IN 220.12
 FOR LIGHTING ALONE STATES A .3. PLEASE ALSO KNOW THAT
 WHEN A LIGHTING LOAD EXCEEDS THE WATTS PER SQ FT BASED
 ON ACTUAL FIXTURE WATTAGE THEN THE FIXTURE WATTAGE MUST
 BE USED.
 PLEASE SEE 220.44 FOR RECEPTACLE LOADS WHICH MAY NOT BE
 FIGURED IN WITH THE LIGHTING LOAD IN OTHER THAT
 DWELLING UNITS.
  
 ** THE LOAD WILL INCREASE. THE PLANS SHOW A TOTAL OF
 11.9WATTS WHICH IS NOT POSSIBLE WHEN THE LAMP IN ONE OF
 THE FIXTURES ALONE FAR EXCEEDS 11.9 WATTS.
 PLEASE INDICATE CIRCUITING FOR NEW. BRANCH CIRCUIT
 SIZE, CONDUCTOR SIZE AND TO THE LOCATION.
 240.4,310.16,408.4 ETC
  
 FBC 106.1.1,106.1.2, FOR CLARITY AND ADDITIONAL
 INFORMATION.
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-07-28 Cont ID  
Sent By mcarsill Date 2009-07-28 Time 07:33 Rev Time 0.00
Received By mcarsill Date 2009-07-28 Time 07:30 Sent To  
Notes
2009-07-28 07:33:385501 GEORGIA AVENUE
 ADDITION OF 398 SQUARE FEET OF STORAGE SPACE
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. WHAT IS TO BE STORED IN THE NEW STORAGE ADDITION.
 ARE ANY FLAMMABLE, COMBUSTIBLE, TOXIC, CORROSIVE, OR
 OTHER TYPES OF MATERIALS EXPECTED.
  
 3. NO FIRE SAFETY EQUIPMENT ILLUSTRATED ON THE PLANS.
  
 4. PLEASE INDICATE THE LOCATIONS OF EXISTING EXITS,
 MAXIMUM TRAVEL DISTANCES TO REACH EXITS, ANY DEAD-END
 CORRIDORS OR CONDITIONS, ETC.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jwitmer Date 2009-06-25 Time 08:40 Sent To  
Notes
2009-06-25 08:48:49INCOMING : RESIDENTIAL TO R-27

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-07-08 Cont ID  
Sent By kdfreema Date 2009-07-08 Time 14:03 Rev Time 0.00
Received By kdfreema Date 2009-07-08 Time 14:02 Sent To  
Notes
2009-07-08 14:25:38***FAILED***
  
 1. THE SURVEY PROVIDED IS FOR 620 BUNKER RD. WHILE THE
 PROJECT LOCATION ON THE PERMIT APPLICATION STATES 5501
 GEORGIA AVENUE. PLEASE ENSURE THAT ALL INFORMATION
 REFERS BACK TO THE PROPERTY WHERE THE WORK IS PROPOSED
 TO TAKE PLACE.
  
 2. TWO COPIES OF A SURVEY NOT LESS THAN ONE YEAR OLD
 ARE REQUIRED TO BE SUBMITTED, THE PROVIDED SURVEY IS
 OVER 5 YEARS OLD AND ONLY ONE COPY WAS PROVIDED.
  
 3. THE ARCHITECTURAL DRAWINGS TO NOT CLEARLY SHOW WHERE
 ON THE STRUCTURE THE ADDITION IS GOING. PLEASE SHOW A
 TOTAL OVERVIEW OF THE PROPERTY INCLUDING THE LOCATION
 OF THE PROPOSED ADDITION.
  
 4. THE TENANT IS SHOWN AS KOFSKI ANTIQUES, BUT THE
 APPLICATION TYPE IS LISTED AS A RESIDENTIAL ADDITION,
 PLEASE CLARIFY.
  
 5. NOTE THAT ONCE THE COMMENTS ABOVE ARE ADDRESSED, NEW
 COMMENTS ARE LIKELY TO BE GENERATED BASED UPON THE FACT
 THAT IS ITS UNCLEAR AT THIS TIME WHERE THE WORK IS
 TAKING PLACE.
  