| Plan Review Stops For Permit 09060575 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2009-07-16 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-07-16 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-07-16 |
Time |
11:40 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2009-07-08 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-07-08 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-07-08 |
Time |
15:16 |
Sent To |
PC |
|
| Notes |
| 2009-07-08 15:22:38 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. IF THE MECHANICAL CONTRACTOR IS ACTING AS THE | | | DESIGNER UNDER FS 471.003, THE QUALIFIER SHALL SIGN THE | | | PLANS AS THE DESIGNER OF RECORD. | | | | | | 2. THERE IS NO DETERMINATION AS TO WHICH BUILDING OR | | | LOCATIONS WITHIN A BUILDING WHERE THESE DAMPERS ARE TO | | | BE LOCATED. THE SPECIFIC LOCATION AND INSTALLATION | | | DETAILS OF EACH SMOKE DAMPER SHALL BE SHOWN AND | | | PROPERLY IDENTIFIED ON THE BUILDING PLANS BY THE | | | DESIGNER IN ACCORDANCE WITH FBC-M 607.8. | | | | | | 3. SHOW HOW THESE DAMPERS ARE TO BE ACTUATED IN | | | ACCORDANCE WITH FBC-M 607.3.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
|