Plan Review Details - Permit 09060575
Plan Review Stops For Permit 09060575
Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-07-16 Cont ID  
Sent By rregueir Date 2009-07-16 Time 11:40 Rev Time 0.00
Received By rregueir Date 2009-07-16 Time 11:40 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-07-08 Cont ID  
Sent By rregueir Date 2009-07-08 Time 15:22 Rev Time 0.00
Received By rregueir Date 2009-07-08 Time 15:16 Sent To PC
Notes
2009-07-08 15:22:38REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. IF THE MECHANICAL CONTRACTOR IS ACTING AS THE
 DESIGNER UNDER FS 471.003, THE QUALIFIER SHALL SIGN THE
 PLANS AS THE DESIGNER OF RECORD.
  
 2. THERE IS NO DETERMINATION AS TO WHICH BUILDING OR
 LOCATIONS WITHIN A BUILDING WHERE THESE DAMPERS ARE TO
 BE LOCATED. THE SPECIFIC LOCATION AND INSTALLATION
 DETAILS OF EACH SMOKE DAMPER SHALL BE SHOWN AND
 PROPERLY IDENTIFIED ON THE BUILDING PLANS BY THE
 DESIGNER IN ACCORDANCE WITH FBC-M 607.8.
  
 3. SHOW HOW THESE DAMPERS ARE TO BE ACTUATED IN
 ACCORDANCE WITH FBC-M 607.3.2.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved