Plan Review Details - Permit 09060569
Plan Review Stops For Permit 09060569
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-20 Cont ID  
Sent By jgomez Date 2009-07-20 Time 09:45 Rev Time 0.00
Received By jgomez Date 2009-07-20 Time 09:45 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-06-24 Cont ID  
Sent By jgomez Date 2009-06-24 Time 14:20 Rev Time 0.00
Received By jgomez Date 2009-06-24 Time 14:20 Sent To PC
Notes
2009-06-24 14:20:59RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FL RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- ACCORDING TO THE 2009 REVISIONS TO THE 2007 FLORIDA
 RESIDENTIAL CODE THIS BUILDING IS LOCATED ON EXPOSURE
 "C" (SEC. R301.2.1.4.3). FLAT ROOF PRODUCT APPROVAL
 FL1654-R4 AND SPECIFIC SYSTEM SELECTED W-32 INDICATES
 THAT THE MAX. DESIGN PRESSURES FOR THIS SYSTEM IS
 -90PSF. IF BUILDING IS LOCATED ON EXPOSURE "C" THE
 DESIGN PRESSURES ARE HIGHER THAN -90PSF AT CORNER
 AREAS. NOTE # 7 ON SHEET 2 OF 33 OF PRODUCT APPROVAL
 SUBMITTED STATES THAT NO RATIONAL ANALYSIS IS PERMITTED
 TO INCREASE THE DESIGN PRESSURES.
 NEED TO SPECIFY FULLY BONDED ASSEMBLY WITH DESIGN
 PRESSURES THAT MEETS THE CALCULATED DESIGN PRESSURES
 FOR EXPOSURE 'C" OR SELECT ASSEMBLY WITH MECHANICALLY
 ATTACHED BASE SHEET. THIS SECOND OPTION REQUIRES SIGNED
 AND SEALED CALCULATIONS DONE BY A DESIGN PROFESSIONAL.
 SEE NOTE #6 ON SHEET 2 OF 33.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-24 Cont ID  
Sent By jgomez Date 2009-06-24 Time 14:21 Rev Time 0.00
Received By jgomez Date 2009-06-24 Time 14:20 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved