Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-07-14 Cont ID  
Sent By dpalmer Date 2009-07-14 Time 11:55 Rev Time 0.00
Received By dpalmer Date 2009-07-14 Time 11:55 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-06-29 Cont ID  
Sent By dpalmer Date 2009-06-29 Time 10:00 Rev Time 0.00
Received By dpalmer Date 2009-06-29 Time 10:00 Sent To FIRE
Notes
2009-06-29 10:00:49 
 ** DENIED PLANS **
  
 ** SUBMITTED REVISIONS TO CHANGE SCOPE OF WORK TO
 ACCESS CONTROLS NOT A SECURITY SYSTEM.
  
  
 1) NOTE: PLANS NEED TO STATE THE MINIMUM ADOPTED CODES
 FOR DESIGN AND INSTALLATION.
 PLEASE BE SURE THE FOLLOWING MINIMUM ADOPTED CODES ARE
 STATED ON PLANS.
 FBC 2007W/2009 REVISIONS.
 2006 NFPA-101
 2005 NFPA-70
 2002 NFPA-72
  
 FBC CHAPTER 35, FAC 69A-60.003,.004. FAC 69A-3.012, FS
 553.73
  
 2) NOTE: PLEASE INCLUDE NOTES AND INFORMATION ON ACCESS
 CONTROLS UNDER NORMAL AND EMERGENCY PER NFPA-101
 CHAPTER 7. PLEASE BE SURE TO SEE ANY COMMENTS FROM FIRE
 MARSHAL REVIEW.
  
 3) NOTE: PLEASE INCLUDE WIRING METHODS AS THE SCOPE OF
 WORK IN A TYPE I BUILDING. PLEASE PROVIDE DETAILS PER
 NEC 300.21.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-06-19 Cont ID  
Sent By dpalmer Date 2009-06-19 Time 13:59 Rev Time 0.00
Received By dpalmer Date 2009-06-19 Time 13:59 Sent To  
Notes
2009-06-19 14:00:59SPOKE TO QUALIFIER, THIS IS FOR SECURITY ONLY WHICH
 DOES NOT INCLUDE ANY CARD ACCESS OR CONTROLS, CAMERAS
 OR SYSTEMS UNDER NFPA-101.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-07-10 Cont ID  
Sent By mawillia Date 2009-07-10 Time 13:33 Rev Time 0.00
Received By mawillia Date 2009-07-10 Time 13:15 Sent To E
Notes
2009-07-10 13:33:19*****APPROVED*****
  
  
 THE PROVISO COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW
 HAVE BEEEN ADDRESSED; PLAN SHEET S-2 (OF 2) WAS
 STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-06-29 Cont ID  
Sent By mawillia Date 2009-06-29 Time 14:42 Rev Time 0.00
Received By mawillia Date 2009-06-29 Time 13:59 Sent To  
Notes
2009-06-29 14:33:15*****PROVISO*****
  
  
 1. DOORS IN THE MEANS OF EGRESS SHALL BE PERMITTED TO
 BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS
 CONTROL SYSTEM PROVIDED THAT ALL THE CRITERIA OF
 7.2.1.6.2 , NFPA 101 (LIFE SAFETY CODE) - 2006 EDITION,
 ARE MET. ADD THIS CODE REFERENCE TO AN APPROPIATE PLAN
 SHEET.
  
 2. PROVIDE SPEC SHEETS ON THE ACCESS CONTROL SYSTEM
 DEVICES.
  
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE ABOVE AS WELL AS ALL OTHER PLAN EXAMINER'S COMMENTS
 HAVE BEEN ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2009-07-14 Time   Rev Time 0.00
Received By jwitmer Date 2009-07-06 Time 08:52 Sent To  
Notes
2009-07-06 08:53:14FIRE

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-24 Cont ID  
Sent By jgomez Date 2009-06-24 Time 10:00 Rev Time 0.00
Received By jgomez Date 2009-06-24 Time 10:00 Sent To  
Notes
2009-06-24 10:00:53SENT TO DEWEY PALMER'S DESK.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved