Plan Review Details - Permit 09060502
Plan Review Stops For Permit 09060502
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-25 Cont ID  
Sent By mcruz Date 2009-06-25 Time 15:45 Rev Time 0.00
Received By mcruz Date 2009-06-05 Time 15:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-06-22 Cont ID  
Sent By rregueir Date 2009-06-22 Time 15:30 Rev Time 0.00
Received By rregueir Date 2009-06-22 Time 15:21 Sent To Z
Notes
2009-06-22 15:30:19REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE FORM N1100-B TO DEMONSTRATE ENERGY CODE
 COMPLIANCE IN ACCORDANCE WITH FBC-R SECTION
 N1100.0.8.1.
  
 2. PROVIDE COOLING LOAD CALCULATIONS ATTACHED TO THE
 METHOD B FORM 1100 IN ACCORDANCE WITH FBC-R SECTION
 N1100.7.AB.1.
  
 3. ONE OF THE 3 BEDROOMS DOES NOT SHOW ANY PROVISIONS
 FOR BALANCED RETURN. SHOW HOW BALANCED RETURN IS TO BE
 ACHIEVED IN ACCORDANCE WITH FBC-R SECTION M1602.4.
  
 4. HOW WILL THE A/C SYSTEM BE POWERED? THERE IS NO
 ELECTRICAL PERMIT APPLICATION TO INSTALL THE POWER
 SUPPLY AND DISCONNECTS FOR THIS SYSTEM.
  
 5. A NOTICE OF COMMENCEMENT WILL BE REQUIRED FOR THIS
 WORK TO BE FILED WITH THE COUNTY CLERK'S OFFICE PRIOR
 TO FIRST INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2009-06-25 Cont ID  
Sent By mcruz Date 2009-06-25 Time 15:45 Rev Time 0.00
Received By mcruz Date 2009-06-25 Time 15:29 Sent To  
Notes
2009-06-25 15:44:57PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 3. INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES. PURSUANT TO THE CITY
 OF WEST PALM BEACH ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDR), SECTION 94-305(B)(4): MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET INTO A
 REQUIRED SETBACK.
  
 PURSUANT TO THE ZLDR, SECTION 94-72(A)(2):
 SINGLE-FAMILY LOW DENSITY (SF7) RESIDENTIAL DISTRICT -
 MINIMUM SETBACKS FOR PRINCIPAL BUILDING ARE AS FOLLOWS:
  
 A. FRONT: 25 FEET;
  
 B. CORNER: 12.5 FEET;
  
 C. REAR: 15 FEET OR TEN PERCENT OF LOT DEPTH, WHICHEVER
 IS LESS;
  
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  