Plan Review Details - Permit 09060501
Plan Review Stops For Permit 09060501
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-08 Cont ID  
Sent By shill Date 2009-07-08 Time 08:57 Rev Time 0.00
Received By shill Date 2009-07-08 Time 08:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-06-18 Cont ID  
Sent By shill Date 2009-06-18 Time 18:10 Rev Time 0.00
Received By shill Date 2009-06-18 Time 18:10 Sent To  
Notes
2009-06-18 18:16:00****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. THE PRODUCT REQUIRES 3000PSI CONCRETE, SEE PAGE 1.
 FOR OPENINGS WITH A FLOOR MOUNT, PLEASE NOTE THAT
 RESIDENTIAL SLABS ARE TYPICALLY POURED AT 2500PSI; HOW
 HAVE YOU DETERMINED THAT THE CONCRETE MEETS THE MINIMUM
 STRENGTH? YOU MAY USE ANCHOR SPACING FOR MASONRY/BLOCK
 IN LIEU OF PROVIDING EVIDENCE THAT THE CONCRETE MEETS
 3000PSI REQUIREMENT.
  
 **UPON REQUEST (TELEPHONE CALL), PLAN WILL BE REDLINED
 TO REVISE ANCHOR SPACING FOR OPENING #7 TO BE 3"
 BOTTOM**
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-18 Cont ID  
Sent By shill Date 2009-06-18 Time 18:17 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
***NONE***