| 2009-06-24 08:38:55 | DENIED |
| | REFERENCE: |
| | FBC-2007 RESIDENTIAL |
| | FBC-2007 CHAPTER 1 |
| | |
| | A. THE FOLLOWING INFORMATION IS REQUIRED FOR A GAS |
| | PERMIT: |
| | |
| | 1. TYPE OF GAS, (LP OR NATURAL). |
| | |
| | 2. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2007 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | |
| | 3. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2007 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33) OR RESIDENTIAL CODE SECTIONS G2412.8 THRU |
| | G2413.6.1 AND TABLES G2413.4(1) THRU 2413.4(8). -- |
| | TOTAL NOT SHOWN. |
| | |
| | 4. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE |
| | SEC. G2413.2. |
| | |
| | 5. PER FBC-2007 FUEL GAS, SECTION 409.4 MP REGULATOR |
| | VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH MP REGULATOR. A UNION IS |
| | REQUIRED DOWNSTREAM OF THE SHUT OFF VALVE FOR THE HOUSE |
| | REGULATOR. |
| | |
| | 6. SUBMIT MANUF SPEC SHEETS FOR THE REGULATORS. |
| | INDICATE MODEL OF REGULATOR AS WELL AS THE OUTPUT |
| | CAPACITY OF THE REGULATORS. THE REGULATORS SHALL BE |
| | LISTED. SECTION 106.1.2 (MORE INFORMATION REQUIRED). |
| | |
| | B. THE FOLLOWING INFORMATION IS REQUIRED FOR THE POOL |
| | HEATER: |
| | |
| | 1. FBC-2007 SEC. 424.2.14.1, OR |
| | FBCR-2007 SEC. R4101.14.1 SWIMMING POOL |
| | WATER HEATERS SHALL BEAR THE LABEL OF A |
| | RECOGNIZED TESTING AGENCY. (MANUFACTURE |
| | SHEETS REQUIRED, PLEASE SUBMIT). |
| | |
| | 2. FBC-2007 SEC. 424.2.14.2, OR |
| | FBCR-2007 SEC. R4101.14.2 WATER |
| | RETENTION, PROVIDE A POSITIVE MEANS OF |
| | RETAINING WATER IN THE HEATER WHEN PUMP |
| | IS SHUT OFF. (MANUFACTURE SHEETS |
| | REQUIRED, PLEASE SUBMIT). |
| | |
| | C. 1. THE VALUE ON THE PERMIT APPLICATION APPEARS LOW. |
| | THE VALUE ON THE PERMIT APPLICATION MUST INCLUDE THE |
| | TOTAL COST OF LABOR, MATERIALS AND DESIGN. |
| | PER (W.P.B AS AMENDED) SECTION 108.3 BUILDING PERMIT |
| | VALUATION. IF, IN THE OPINION OF THE BUILDING OFFICIAL, |
| | THE CLAIMED VALUATION OF BUILDING, ALTERATION, |
| | STRUCTURAL, ELECTRICAL, GAS, MECHANICAL OR PLUMBING |
| | SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| | APPLICATION, THE PERMIT SHALL BE DENIED. -- MARSHALL & |
| | SWIFT INDICATES THE GAS POOL HEATER TO BE APPROX. |
| | $3000. SO WITH THE PIPING, VALVES, REGULATORS & LABOR |
| | THE JOB WILL BE ABOUT $4,000 TOTAL. A NOTICE OF |
| | COMMENCEMENT WILL BE REQUIRED PER FS 713.3. |
| | |
| | D. A MINIMUM OF TWO SETS OF PLANS IS REQUIRED WITH EACH |
| | APPLICATION FOR PERMIT. SECTION 106.1. ONLY ONE SET OF |
| | PLANS HAS BEEN SUBMITTED FOR REIVEW. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |