Plan Review Details - Permit 09060429
Plan Review Stops For Permit 09060429
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-09-24 Cont ID  
Sent By rmcdouga Date 2009-09-24 Time 15:58 Rev Time 0.00
Received By rmcdouga Date 2009-09-24 Time 15:58 Sent To  
Notes
2009-09-24 16:02:00SUBMIT TWO CLARIFICATION LETTERS FROM THE ENGINEER FOR
 THE MINIMUM EMBED DEPTH OF THE TAPCONS IN THE DOOR
 ANCHOR DETAIL ON SHEET 1.3. THE NUMBER IS ILLEGIBLE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-08-10 Cont ID  
Sent By rmcdouga Date 2009-08-10 Time 15:29 Rev Time 0.00
Received By rmcdouga Date 2009-08-10 Time 15:29 Sent To  
Notes
2009-08-10 15:41:262007 FBC W/2009 REVISIONS
 LEVEL 1 ALTERATION
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF PLANS DETAILING THE WORK THAT
 WILL BE DONE TO THE PORCH. THE DETAIL THAT WAS
 SUBMITTED IS NOT ADEQUATE. IT ONLY STATES REMOVE AND
 REPLACE COLUMNS. SPECIFY THE SIZE, TYPE AND NUMBER OF
 COLUMNS BEING REPLACED. SPECIFY HOW THE NEW COLUMNS
 WILL BE ANCHORED AT THE TOP AND BOTTOM (SPECIFY
 CONNECTORS) IN ORDER TO PROVIDE A CONTINUOUS LOAD PATH
 TO RESIST WIND-LOADS. PROVIDE DRAWINGS SHOWING THE
 DIMENSIONS OF THE PORCH, SPANS, ETC.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-07-13 Cont ID  
Sent By rmcdouga Date 2009-07-13 Time 08:06 Rev Time 0.00
Received By rmcdouga Date 2009-07-13 Time 08:05 Sent To  
Notes
2009-07-13 08:43:232007 FBC
 RENOVATION
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF A PLANS, SHOWING COMPLIANCE
 WITH THE 2007 FBC, FOR THE PORCH THAT WILL BE BUILT TO
 REPLACE THE EXISTING ONE THAT WILL BE DEMOLISHED.
 SPECIFY DIMENSIONS,
  
 2) SPECIFY WINDOW OPENING SIZES, CONFIGURATIONS, NUMBER
 OF ANCHORS, SILL TYPE, GLASS TYPE AND DESIGN PRESSURES
 FOR THE HORIZONTAL SLIDING WINDOWS THAT WILL BE
 INSTALLED. CIRCLE THE APPROPRIATE ITEMS ON THE TABLES
 GIVEN IN THE NOA.
  
 3) SHOW THAT THE SLEEPING ROOM WINDOWS WILL COMPLY WITH
 FBC R310 AND SECTION 604 OF THE EXISTING BUILDING CODE
 FOR EMERGENCY ESCAPE AND RESCUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-10-08 Cont ID  
Sent By dpalmer Date 2009-10-08 Time 17:56 Rev Time 0.00
Received By dpalmer Date 2009-10-08 Time 17:56 Sent To PC
Notes
2009-10-08 17:56:15 
  
 ** PROVISO **
  
 1) NOTE: AS NOTED ON PREVIOUS REVIEW STORAGE TYPE OF
 WATER HEATER LOADS SHALL BE FIGURED AT 125%. LOAD
 CALCULATIONS SHOW 125% HOWEVER IT WAS NOT FIGURED INTO
 CALCULATIONS AT THAT RATE.
 4500VA @ 125% IS 5625VA,
  
 2) NOTE: PANEL SCHEDULE SHALL BE SPECIFIC. THE USE OF
 GENERAL LIGHTING/GENERAL RECEPTACLES IS NOT ACCEPTABLE.
 PLEASE SEE NEC 2005 408.4 AND COMMENTARY IN NEC
 HANDBOOK.
  
 ** PLEASE REVISE THE ABOVE ITEMS BEFORE FINAL. IF THERE
 ARE OTHER REVISIONS THEN THEY MUST BE REVISED BEFORE
 ROUGH.
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-09-28 Cont ID  
Sent By dpalmer Date 2009-09-28 Time 09:24 Rev Time 0.00
Received By dpalmer Date 2009-09-28 Time 09:24 Sent To  
Notes
2009-09-28 09:24:48 
 ** DENIED **
  
 ** COMPLETE NEW PLANS SUBMITTED WHICH HAVE NOT BEEN
 PREVIOUSLY SUBMITTED OR REVIEWED.
  
 1) NOTE: PLANS CONTAIN A NOTE WHICH STATES ALL
 ELECTRICAL IS TO BE DONE UNDER THE 2008 NEC. HOWEVER
 ALL PERMIT APPLICATIONS SUBMITTED BEFORE OCTOBER 1ST,
 2009 IS UNDER THE 2005 NEC.
  
 2) NOTE: PLEASE SEE FBC R313.1, 313.2, 313.2.1 FOR
 SMOKE ALARMS WHICH ARE REQUIRED TO BE BROUGHT UP TO
 CURRENT CODE. PLEASE SEE NFPA-72 11.5.1 AND 11.8.3 FOR
 REQUIRED LOCATIONS.
 PLANS ARE MISSING DEVICES.
 PLEASE BE SURE TO SEE 11.8.3 AS ALL SMOKE ALARMS WITHIN
 20FT OF COOKING APPLIANCES SHALL MEET SPECIFIC
 REQUIREMENTS. ( OUTSIDE MASTER BEDROOM)
  
 3) NOTE: PLANS/RISER INDICATES A 150AMP SERVICE YET THE
 FEEDERS FROM THE MAIN TO THE PANEL ARE TOO SMALL.
 PLEASE SEE 310.16,310.15B6 AS #2 IS NOT RATED FOR
 150AMPS.
  
 4) NOTE: PLANS INDICATE ONE A/C SYSTEM WITH 60AMP OVER
 CURRENT PROTECTION. HOWEVER THE MECHANICAL PLANS
 INDICATE A SYSTEM WITH 8KW HEAT. THIS 60AMP OCP IS TOO
 HIGH. 422.13E(3)
 ** ELECTRICAL PLANS INDICATE 10KW FOR AHU. PLEASE
 CORRELATE BOTH THE ELECTRICAL AND MECHANICAL PLANS.
  
 5) NOTE: PLANS ARE MISSING THE REQUIRED SWITCH AND
 LIGHTING OUTLET AT FRONT DOOR ENTRANCE/EXIT.
 210.70
  
 6) NOTE: PLANS ARE MISSING DISCONNECTS FOR BOTH THE
 CONDENSING UNIT AND AIR HANDLING UNIT PER 440.11,
 440.12.
  
 PLEASE BE SURE TO SEE 110.26 FOR CLEARANCES.
 THE SYMBOL SHOWN ON PLANS IS FOR A 220V OUTLET ONLY.
  
 7) NOTE: PLEASE SEE PLANS AS THE DISCONNECT SHOWN ON
 RISER IS NOT SHOWN ON PLANS. PLEASE SEE 110.26 FOR
 LOCATION.
 PANEL SCHEDULE ALSO CONTAINS A NOTE WHICH STATES THE
 PANEL ALREADY EXISTS, YET THE PLANS STATE THE PANEL AND
 THE MAIN SERVICE IS NEW.
 WHICH IS ACCURATE?
  
  
 8) NOTE: PLEASE SEE 210.52B1 AS ALL CIRCUITS FOR DINING
 ROOM RECEPTACLES SHALL BE 20AMP AND #12. PANEL SCHEDULE
 DOES NOT DELINEATE BETWEEN LIGHTS OR RECEPTACLES. PANEL
 SCHEDULE DOES STATE AFCI PROTECTION WHICH IS NOT
 REQUIRED HOWEVER MAY BE INSTALLED.
 PLEASE SEE 210.52B1, 210.11C1 AND 220.53 AS ALL
 ADDITIONAL DEDICATED CIRCUITS ABOVE THE TWO MINIMUM
 SMALL APPLIANCE CIRCUITS SHALL BE FIGURED AT 1500VA FOR
 EACH. LOAD CALCULATIONS ONLY INDICATE TWO SMALL
 APPLIANCES FOR LOADS.
  
 9) NOTE: AS NOTED ABOVE IN COMMENTS #8, SEE 210.52B1,
 210.11C1 AND 220.53 FOR ALL SMALL APPLIANCE LOADS AND
 ANY DEDICATED DINING ROOM RECEPTACLE CIRCUITS. THE
 PANEL SCHEDULE INDICATES 3-SMALL APPLIANCE CIRCUITS
 BEFORE ADDING ANY DINING ROOMS.
  
 10) NOTE: PLEASE SEE 422.13 AS STORAGE TYPE WATER
 HEATERS ARE CONSIDERED CONTINUOUS LOADS. SEE NEC
 COMMENTARY AS THE LAST SENTENCE STATES WHEN SIZING FOR
 SERVICE AND FEEDERS ALSO. THIS MEANS THE WATER HEATER
 4500VA SHALL BE FIGURED AT 125% INTO LOAD CALCULATIONS.
  
 11) NOTE: PLEASE INDICATE AIC RATING FOR MAIN AND PANEL
 PER 110.9.
  
  
 **IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-08-04 Cont ID  
Sent By btrobaug Date 2009-08-04 Time 15:45 Rev Time 0.00
Received By btrobaug Date 2009-08-04 Time 15:16 Sent To  
Notes
2009-08-04 15:45:26 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 SAME COMMENTS AS THE PREVIOUS REVIEW, NO ELECTRICAL
 PLANS HAVE BEN SUBMITTED.
 PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED.
  
 1} PLEASE SUBMIT A FLOOR PLAN AND INDICATING THE
 LOCATION OF ALL EQUIPMENT AND DEVICES BEING INSTALLED
 UNDER THE SCOPE OF THIS APPLICATION.106.1.1 FBC.
  
 2} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.2
 RESIDENTIAL FLORIDA BUILDING CODE.INDICATE LOCATIONS ON
 THE ELECTRICAL PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-07-07 Cont ID  
Sent By btrobaug Date 2009-07-07 Time 12:05 Rev Time 0.00
Received By btrobaug Date 2009-07-07 Time 12:04 Sent To  
Notes
2009-07-07 12:05:00 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED.
  
 1} PLEASE SUBMIT A FLOOR PLAN AND INDICATING THE
 LOCATION OF ALL EQUIPMENT AND DEVICES BEING INSTALLED
 UNDER THE SCOPE OF THIS APPLICATION.106.1.1 FBC.
  
 2} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.2
 RESIDENTIAL FLORIDA BUILDING CODE.INDICATE LOCATIONS ON
 THE ELECTRICAL PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-10-01 Cont ID  
Sent By lmartine Date 2009-10-01 Time 16:24 Rev Time 0.00
Received By shill Date 2009-10-01 Time 16:24 Sent To  
Notes
2009-10-07 15:07:48RESUB SUBMITTED ON 10/1 ROUTED TO DP DESK
  
2009-10-01 16:24:19IN ZONING

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-09-15 Cont ID  
Sent By lmartine Date 2009-09-09 Time 18:23 Rev Time 0.00
Received By lmartine Date 2009-09-09 Time 18:27 Sent To  
Notes
2009-09-15 18:27:57R-5

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-23 Cont ID  
Sent By dpalmer Date 2009-07-23 Time 16:39 Rev Time 0.00
Received By dpalmer Date 2009-07-23 Time 16:39 Sent To  
Notes
2009-07-23 16:40:08R-28

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-07-13 Cont ID  
Sent By rmcdouga Date 2009-07-13 Time 09:21 Rev Time 0.00
Received By rmcdouga Date 2009-06-18 Time 10:08 Sent To  
Notes
2009-06-30 10:07:54R-19

Review Stop L LANDSCAPING
Rev No 3 Status P Date 2009-09-14 Cont ID  
Sent By rkussner Date 2009-09-14 Time 11:52 Rev Time 0.00
Received By rkussner Date 2009-09-14 Time 11:52 Sent To  
Notes
2009-09-14 11:53:31***LANDSCAPE REVIEW PASSED PER ANGELLA***
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2009-08-03 Cont ID  
Sent By rkussner Date 2009-08-03 Time 09:28 Rev Time 0.00
Received By rkussner Date 2009-08-03 Time 09:28 Sent To  
Notes
2009-08-03 10:49:23***LANDSCAPE REVIEW FAILED***
  
 1. COMMENTS MADE ON 7/2 HAVE NOT BEEN ADDRESSED.
  
 2. THE LOCATION OF ALL PLANT MATERIAL, NEW AND
 EXISTING, SHALL BE IDENTIFIED ON THE PLAN AND A PLANT
 LIST WITH THE PLANT NAMES, QUANTITY, SIZE AND SPACING
 SHALL BE PART OF THE PLAN. PROPOSED PLANT MATIERIAL
 SHALL BE SUITABLE FOR THIS ZONE. XERISCAPE POINTS SHALL
 BE DETERMINED BY USING THE XERISCAPE DESIGN OPTIONS
 FOUND IN SECTION 94-442 (G) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.
  
 3. THE LANDSCAPE PLAN SHALL CONTAIN EACH OF THE
 ELEMENTS IDENTIFIED IN SECTION 94-448 (D). THE PLAN
 SHALL IDENTIFY THE ADDRESS AND SHOW THE STREET AND
 RIGHT-OF-WAY.
  
 4. THE LANDSCAPE CALCULATIONS PROVIDED WERE NOT
 COMPLETE. PLEASE INDICATE HOW THE OPEN SPACE SQUARE
 FOOTAGE WAS DETERMINED AND AND HOW MANY TREES AND
 PLANTS WERE PROPOSED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-07-02 Cont ID  
Sent By rkussner Date 2009-07-02 Time 13:46 Rev Time 0.00
Received By rkussner Date 2009-07-02 Time 13:46 Sent To  
Notes
2009-07-02 13:47:05***LANDSCAPE REVIEW FAILED***
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 1 .PURSUANT TO SECTION 94-441(C)(2), WHEN RENOVATIONS,
 REPAIR, ALTERATION OR REDEVELOPMENT EXCEEDS 50 PERCENT
 OF THE VALUE OF THE STRUCTURE, THE ENTIRE LANDSCAPING
 ON SITE SHALL BE BROUGHT UP TO CURRENT STANDARDS.
  
 2. PLEASE SUBMIT A LANDSCAPE PLAN WITH ALL ALL
 TABULATION NECESARY FOR THE EVALUATION OF COMPLIANCE
 WITH ARTICLE XIV OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS, INCLUDING THE XERISCAPE DESIGN OPTIONS.
  
 3. SUBMIT A COST ESTIMATE THAT INCLUDES THE TOTAL COST
 OF ALL LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO
 UNIT COST.
  
 4. AN IRRIGATION PERMIT IS REQUIRED. THERE SHALL BE
 120% COVERAGE TO ALL AREAS INCLUDING THE RIGHT-OF-WAY.
 IN ADDITION, A RAIN SENSING DEVICE IS REQUIRED.
  
  
  
 IF YOU HAVE ANY QUESITONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-09-24 Cont ID  
Sent By rmcdouga Date 2009-09-24 Time 16:04 Rev Time 0.00
Received By rmcdouga Date 2009-09-24 Time 16:04 Sent To  
Notes
2009-09-24 16:37:391) SUBMIT REVISED MECHANICAL PLANS INDICATING THE SIZES
 OF THE TRANSFER DUCT AND GRILLS BETWEEN THE DINING ROOM
 AND BEDROOM #1.
  
 2) THE WHOLE HOUSE FAN CREDIT HAS BEEN TAKEN ON THE
 ENERGY CALCULATIONS. SUBMIT REVISED PLANS SHOWING THE
 LOCATION OF THE WHOLE HOUSE FAN AND PROVIDE
 DOCUMENTATION SHOWING HOW THE THREE REQUIREMENTS OF
 2007 FBC RESIDENTIAL ENERGY GLITCH AMENDMENTS B4.1.4
 WILL BE MET.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-08-10 Cont ID  
Sent By rmcdouga Date 2009-08-10 Time 15:41 Rev Time 0.00
Received By rmcdouga Date 2009-08-10 Time 15:41 Sent To  
Notes
2009-08-10 15:42:282007 FBC W/2009 REVISIONS
 LEVEL 1 ALTERATION
  
 DENIED
  
 (1) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT
 SIZING CALCULATIONS IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED METHODOLOGIES AS REQUIRED BY FBC R
 M1401.3. AND REQUESTED IN FIRST REVIEW COMMENTS.
  
 (2) THE TWO SETS OF MECHANICAL PLANS THAT WERE
 SUBMITTED ARE NOT ADEQUATE. IN ADDITION TO THE GRILL
 SIZES, SPECIFY THE DUCT SIZES AND CFM AT EACH SUPPLY
 GRILL ON THE PLANS. SPECIFY THE SIZE AND LOCATION OF
 THE RETURN AIR SYSTEM. PLEASE SPECIFY THE ADDRESS OF
 THE PROJECT AND THE PERSON RESPONSIBLE FOR THE DESIGN
 ON THE PLANS. SEE FBC R M1601 AND N1110.AB.1 OF THE
 2007 ENERGY GLITCH AMENDMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-07-13 Cont ID  
Sent By rmcdouga Date 2009-07-13 Time 09:20 Rev Time 0.00
Received By rmcdouga Date 2009-07-13 Time 09:20 Sent To  
Notes
2009-07-13 09:25:392007 FBC
 RENOVATION
  
 DENIED
 1) THE SCOPE OF WORK STATES " A/C EVALUATE AND
 INSTALL". IF THIS MEANS THAT A NEW A/C SYSTEM WITH NEW
 DUCT WORK IS TO BE INSTALLED, THEN A MECHANICAL PERMIT,
 TWO SETS OF PLANS AND TWO SETS OF EQUIPMENT SIZING
 CALCULATIONS ARE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-07-06 Cont ID  
Sent By kstevens Date 2009-07-06 Time 12:07 Rev Time 0.00
Received By kstevens Date 2009-07-06 Time 12:07 Sent To  
Notes
2009-07-06 12:09:26NO PLUMBING PLANS SUBMITTED. -- CHANGE OUT OF FIXTURES
 IN SAME LOCATION -- PLUMBING PERMIT REQUIRED.

Review Stop Z ZONING
Rev No 4 Status P Date 2009-10-05 Cont ID  
Sent By astelly Date 2009-10-05 Time 12:09 Rev Time 0.00
Received By astelly Date 2009-10-05 Time 12:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 2009-09-21 Cont ID  
Sent By astelly Date 2009-09-21 Time 18:02 Rev Time 0.00
Received By astelly Date 2009-09-21 Time 18:17 Sent To E
Notes
2009-09-21 18:14:35AMY STELLY
 PLANNING AND ZONING
 561-822-1442
  
 PLEASE RESPOND TO THE REPEAT COMMENTS BELOW:
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 3. INDICATE SETBACK DIMENSIONS FROM PROPOSED/RELOCATED
 A/C EQUIPMENT TO ALL PROPERTY LINES. PURSUANT THE ZLDR:
 SECTION 94-305(B) (4): MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2009-08-03 Cont ID  
Sent By mcruz Date 2009-08-03 Time 15:09 Rev Time 0.00
Received By mcruz Date 2009-08-02 Time 21:33 Sent To B
Notes
2009-08-03 15:09:21PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PLEASE ADDRESS LANDSCAPE PLANNER COMMENTS.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  
 PLACED IN R28

Review Stop Z ZONING
Rev No 1 Status F Date 2009-07-01 Cont ID  
Sent By mcruz Date 2009-07-01 Time 14:13 Rev Time 0.00
Received By mcruz Date 2009-07-01 Time 14:08 Sent To  
Notes
2009-07-01 14:13:05PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PROVIDE TWO (2) COPIES OF A CURRENT SURVEY, WHICH
 INCLUDES THE PROPERTY'S ADDRESS AND LEGAL DESCRIPTION.
  
 3. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-441(C)(2) OF: AS THE VALUE OF THE PROPOSED WORK
 EXCEEDS 50% OF THE STRUCTURE'S VALUE (LISTED AS
 "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 4. INDICATE ON THE SURVEY THE SETBACK DIMENSIONS FROM
 ANY EXTERIOR IMPROVEMENTS TO ALL ADJACENT PROPERTY
 LINES. PURSUANT TO THE ZLDR, SECTION 94-73(B)(2):
 SINGLE-FAMILY/SMALL LOT (SF11) HIGH DENSITY RESIDENTIAL
 DISTRICT. - MINIMUM SETBACKS FOR PRINCIPAL BUILDING ARE
 AS FOLLOWS:
  
 A. FRONT: 20 FEET OR 20 PERCENT OF LOT DEPTH, WHICHEVER
 IS LESS;
  
 B. CORNER: TEN FEET OR TEN PERCENT OF LOT DEPTH,
 WHICHEVER IS LESS;
  
 C. REAR: TEN FEET OR TEN PERCENT OF LOT DEPTH,
 WHICHEVER IS LESS;
  
 D. SIDE: FIVE FEET MINIMUM, TEN FEET TOTAL.
  
 5. INDICATE SETBACK DIMENSIONS FROM PROPOSED/RELOCATED
 A/C EQUIPMENT TO ALL PROPERTY LINES. PURSUANT THE ZLDR,
 SECTION 94-305(B)(4): MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  
 PLACED ON SF RACK R19
  