| 2009-09-22 16:47:23 | |
| | |
| | |
| | ** DENIED ** |
| | |
| | ** NEW PLANS NOW SUBMITTED FOR THE FIRST TIME FOR |
| | REVIEW. PREVIOUS REVIEWS DID NOT CONTAIN ANY ELECTRICAL |
| | PLANS. THE PREVIOUS REVIEW NOTE BY PREVIOUS ELECTRICAL |
| | REVIEWER HAD TO DO WITH *ELECTRICAL SERVICE CHANGE* |
| | PERMIT ONLY. |
| | |
| | |
| | |
| | 1) NOTE: PLANS CONTAIN A NOTE ON COVER SHEET WHICH |
| | STATES ALL ELECTRICAL IS TO BE DONE UNDER THE 2008 NEC. |
| | HOWEVER ALL PERMIT APPLICATIONS SUBMITTED BEFORE |
| | OCTOBER 1ST, 2009 ARE UNDER THE 2005 NEC. |
| | |
| | 2) NOTE: PLEASE SEE 210.52D FOR GFI RECEPTACLE TO BE |
| | LOCATED WITHIN 3FT OF THE MASTER BEDROOM SINK. |
| | |
| | 3) NOTE: PLEASE SEE FBC R313.1,313.2, 313.2.1 FOR SMOKE |
| | ALARMS WHICH ARE REQUIRED TO BE BROUGHT UP TO CURRENT |
| | CODE. PLEASE SEE NFPA-72 11.5.1 AND 11.8.3 FOR REQUIRED |
| | LOCATIONS. |
| | PLEASE BE SURE TO SEE 11.8.3 AS ALL SMOKE ALARMS WITHIN |
| | 20FT OF COOKING APPLIANCES SHALL MEET SPECIFIC |
| | REQUIREMENTS. ( OUTSIDE MASTER BEDROOM) |
| | |
| | 4) NOTE: PLANS ONLY INDICATE ONE A/C SYSTEM YET THE |
| | PANEL SCHEDULE INDICATES TWO ADDITIONAL MINI-SPLIT |
| | SYSTEMS HOWEVER THE ELECTRICAL AND MECHANICAL PLANS DO |
| | SHOW EITHER OF THESE TWO SYSTEMS. |
| | PLEASE SHOW AND SHOW DISCONNECTS PER 440.11,440.12, AND |
| | COMPLIANCE WITH 210.63 |
| | |
| | 5) NOTE: PLEASE SEE 424.3B FOR MINIMUM OVER CURRENT |
| | PROTECTION FRO AHU. PANEL SCHEDULE INDICATES 50AMP FEED |
| | WITH #8 AWG. BOTH ARE TOO SMALL. |
| | MINIMUM IS 125%. |
| | |
| | 6) NOTE: PLANS INDICATE BOTH DISCONNECTS AND |
| | RECEPTACLES PER SYMBOL LEGEND NEXT TO THE DRYER, |
| | OVEN/RANGE AND OTHER LOCATIONS SUCH AS AHU, WATER |
| | HEATER, CU ETC. |
| | THERE IS EQUIPMENT AND APPLIANCES IN THE NEC WHICH DO |
| | REQUIRE DISCONNECTING MEANS HOWEVER OTHER LOCATIONS FOR |
| | CORD AND PLUG EQUIPMENT WHICH COMES THAT WAY FROM THE |
| | MANUFACTURE AND IS LISTED AS CORD AND PLUG CONNECTED |
| | DOES NOT REQUIRE AND ADDITIONAL DISCONNECTING MEANS. |
| | THERE IS NO VIOLATION TO HAVE A DISCONNECT AND |
| | RECEPTACLES HOWEVER IF SHOWN THEN THEY MUST BE |
| | INSTALLED. IN EITHER CASE THE DISCONNECT NOTED ON PLANS |
| | FOR AHU IS SHOWN TOO SMALL AS NOTED IN COMMENT #5 |
| | ABOVE. |
| | PLEASE ALSO SEE 110.26 FOR MINIMUM CLEARANCES. |
| | |
| | 7) NOTE: PLEASE SEE 210.52 FOR RECEPTACLE SPACING. |
| | BEDROOM #3 MISSING RECEPTACLE WITHIN 6FT OF DOOR. |
| | |
| | 8) NOTE: PLEASE SEE 210.52B1 AS ALL CIRCUITS FOR DINING |
| | ROOM RECEPTACLES SHALL BE 20AMP AND #12. PANEL SCHEDULE |
| | DOES NOT DELINEATE BETWEEN LIGHTS OR RECEPTACLES. PANEL |
| | SCHEDULE DOES STATE AFCI PROTECTION WHICH IS NOT |
| | REQUIRED HOWEVER MAY BE INSTALLED. |
| | PLEASE SEE 210.52B1, 210.11C1 AND 220.53 AS ALL |
| | ADDITIONAL DEDICATED CIRCUITS ABOVE THE TWO MINIMUM |
| | SMALL APPLIANCE CIRCUITS SHALL BE FIGURED AT 1500VA FOR |
| | EACH. LOAD CALCULATIONS ONLY INDICATE TWO SMALL |
| | APPLIANCES FOR LOADS. |
| | |
| | 9) NOTE: AS NOTED ABOVE IN COMMENTS #8, SEE 210.52B1, |
| | 210.11C1 AND 220.53 FOR ALL SMALL APPLIANCE LOADS AND |
| | ANY DEDICATED DINING ROOM RECEPTACLE CIRCUITS. THE |
| | PANEL SCHEDULE INDICATES 3-SMALL APPLIANCE CIRCUITS |
| | BEFORE ADDING ANY DINING ROOMS. |
| | |
| | 10) NOTE: PLEASE SEE 422.13 AS STORAGE TYPE WATER |
| | HEATERS ARE CONSIDERED CONTINUOUS LOADS. SEE NEC |
| | COMMENTARY AS THE LAST SENTENCE STATES WHEN SIZING FOR |
| | SERVICE AND FEEDERS ALSO. THIS MEANS THE WATER HEATER |
| | 4500VA SHALL BE FIGURED AT 125% INTO LOAD CALCULATIONS. |
| | |
| | 11) NOTE: PLEASE SHOW LOCATION AND ELECTRICAL FOR THE |
| | SPRINKLER PUMP/SYSTEM AS LISTED ON PANEL SCHEDULE. |
| | NO REVIEW FOR CODE COMPLIANCE CAN BE DONE AS THE |
| | LOCATION IS NOT SHOWN. PLEASE REMEMBER TO SEE 430.102 |
| | FOR REQUIRED DISCONNECTING MEANS. |
| | |
| | |
| | ** AS ELECTRICAL ON SHEET IS MISSING SOME INFORMATION, |
| | THERE MAY BE SOME ITEMS NOT YET SUBMITTED WHICH MAY |
| | CREATE CODE COMMENTS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |