Plan Review Details - Permit 09060428
Plan Review Stops For Permit 09060428
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-11-05 Cont ID  
Sent By rmcdouga Date 2009-11-05 Time 13:51 Rev Time 0.00
Received By rmcdouga Date 2009-11-05 Time 13:51 Sent To  
Notes
2009-11-05 17:38:03REVISED ENERGY CALCULATIONS WITHOUT TAKING THE WHOLE
 HOUSE FAN CREDIT ARE REQUIRED. PER CONTRACTOR THERE IS
 NO EXISTING WHOLE HOUSE FAN, NOR WILL ONE BE INSTALLED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-09-16 Cont ID  
Sent By rmcdouga Date 2009-09-16 Time 15:30 Rev Time 0.00
Received By rmcdouga Date 2009-09-16 Time 15:30 Sent To  
Notes
2009-09-16 16:15:452007 FBC W/2009 REVISIONS
 LEVEL 2 ALTERATION
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE
 STRUCTURAL WINDOW MULLIONS AS REQUIRED BY DCA RULE
 9B-72.
  
 2) SUBMIT TWO SETS OF REVISED ENERGY CALCULATIONS, WITH
 47.9 K BTU COOLING SYSTEM AS SHOWN ON THE MECHANICAL
 PLANS AND LOAD CALCS.
  
 3) CLARIFY THE EXTERIOR DOOR THAT WILL BE USED AND
 SUBMIT TWO COMPLETE SETS OF PRODUCT APPROVALS. THE FL
 COVER SHEET SUBMITTED IS FOR A STEEL DOOR WITH WOOD
 FRAME AND THE NOA ATTACHED TO IT IS FOR A STEEL DOOR
 WITH A METAL FRAME.
  
 4) THE PROJECT IS A LEVEL 2 ALTERATION PER THE EXISTING
 BUILDING CODE. PLEASE REVISE SHEET 1.2.
  
 5) SPECIFY THE LOCATION OF THE SMOKE DETECTORS ON THE
 PLANS AS REQUIRED BY FBC R313.2.1.
  
 6) ON SHEET 2.2 THE EXPOSURE CATEGORY IS SPECIFIED AS B
 UNDER DESIGN PARAMETERS AND AS EXPOSURE C UNDER
 STRUCTURAL NOTES. PLEASE CORRECT AND COORDINATE THE
 COMPONENT AND CLADDING PRESSURES WITH THE APPROPRIATE
 EXPOSURE CATEGORY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-08-10 Cont ID  
Sent By rmcdouga Date 2009-08-10 Time 10:53 Rev Time 0.00
Received By rmcdouga Date 2009-08-10 Time 10:53 Sent To  
Notes
2009-08-10 11:00:262007 FBC
 RENOVATION
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF A KEY PLAN FOR THE ACCORDION
 SHUTTERS. THE NUMBERING OF THE OPENINGS ON THE KEY PLAN
 SHALL CORRESPOND TO THE THE OPENING NUMBERS ON THE
 INSTALLATION SCHEDULE. PREVIOUS COMMENT THAT HAS NOT
 BEEN ADDRESSED. THE OPENING NUMBER/LETTER
 IDENTIFICATION MARKS ON THE KEY PLAN, THAT WAS
 SUBMITTED, DOES NOT MATCH THE INSTALLATION SCHEDULE.
  
 2) SPECIFY WINDOW OPENING SIZES, CONFIGURATIONS, NUMBER
 OF ANCHORS, SILL TYPE, GLASS TYPE AND DESIGN PRESSURES
 FOR THE HORIZONTAL SLIDING WINDOWS THAT WILL BE
 INSTALLED. CIRCLE THE APPROPRIATE ITEMS ON THE TABLES
 GIVEN IN THE NOA. PREVIOUS COMMENT THAT HAS NOT BEEN
 ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-07-10 Cont ID  
Sent By rmcdouga Date 2009-07-10 Time 16:09 Rev Time 0.00
Received By rmcdouga Date 2009-07-10 Time 16:09 Sent To  
Notes
2009-07-10 16:25:452007 FBC
 RENOVATION
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO COPIES OF A KEY PLAN FOR THE ACCORDION
 SHUTTERS. THE NUMBERING OF THE OPENINGS ON THE KEY PLAN
 SHALL CORRESPOND TO THE THE OPENING NUMBERS ON THE
 INSTALLATION SCHEDULE.
  
 2) THE EDGE DISTANCE IS REQUIRED TO BE 3-1/2" IN ORDER
 TO USE THE ANCHOR SPACING IN THE TABLES OF THE
 ACCORDION SHUTTER NOA. SEE PAGE 11 OF THE DRAWINGS.
  
 3) SPECIFY WINDOW OPENING SIZES, CONFIGURATIONS, NUMBER
 OF ANCHORS, SILL TYPE, GLASS TYPE AND DESIGN PRESSURES
 FOR THE HORIZONTAL SLIDING WINDOWS THAT WILL BE
 INSTALLED. CIRCLE THE APPROPRIATE ITEMS ON THE TABLES
 GIVEN IN THE NOA.
  
 4) SHOW THAT THE SLEEPING ROOM WINDOWS WILL COMPLY WITH
 FBC R310 AND SECTION 604 OF THE EXISTING BUILDING CODE
 FOR EMERGENCY ESCAPE AND RESCUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-10-22 Cont ID  
Sent By btrobaug Date 2009-10-22 Time 16:55 Rev Time 0.00
Received By btrobaug Date 2009-10-22 Time 16:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-09-22 Cont ID  
Sent By dpalmer Date 2009-09-22 Time 16:47 Rev Time 0.00
Received By dpalmer Date 2009-09-22 Time 16:23 Sent To  
Notes
2009-09-22 16:47:23 
  
  
 ** DENIED **
  
 ** NEW PLANS NOW SUBMITTED FOR THE FIRST TIME FOR
 REVIEW. PREVIOUS REVIEWS DID NOT CONTAIN ANY ELECTRICAL
 PLANS. THE PREVIOUS REVIEW NOTE BY PREVIOUS ELECTRICAL
 REVIEWER HAD TO DO WITH *ELECTRICAL SERVICE CHANGE*
 PERMIT ONLY.
  
  
  
 1) NOTE: PLANS CONTAIN A NOTE ON COVER SHEET WHICH
 STATES ALL ELECTRICAL IS TO BE DONE UNDER THE 2008 NEC.
 HOWEVER ALL PERMIT APPLICATIONS SUBMITTED BEFORE
 OCTOBER 1ST, 2009 ARE UNDER THE 2005 NEC.
  
 2) NOTE: PLEASE SEE 210.52D FOR GFI RECEPTACLE TO BE
 LOCATED WITHIN 3FT OF THE MASTER BEDROOM SINK.
  
 3) NOTE: PLEASE SEE FBC R313.1,313.2, 313.2.1 FOR SMOKE
 ALARMS WHICH ARE REQUIRED TO BE BROUGHT UP TO CURRENT
 CODE. PLEASE SEE NFPA-72 11.5.1 AND 11.8.3 FOR REQUIRED
 LOCATIONS.
 PLEASE BE SURE TO SEE 11.8.3 AS ALL SMOKE ALARMS WITHIN
 20FT OF COOKING APPLIANCES SHALL MEET SPECIFIC
 REQUIREMENTS. ( OUTSIDE MASTER BEDROOM)
  
 4) NOTE: PLANS ONLY INDICATE ONE A/C SYSTEM YET THE
 PANEL SCHEDULE INDICATES TWO ADDITIONAL MINI-SPLIT
 SYSTEMS HOWEVER THE ELECTRICAL AND MECHANICAL PLANS DO
 SHOW EITHER OF THESE TWO SYSTEMS.
 PLEASE SHOW AND SHOW DISCONNECTS PER 440.11,440.12, AND
 COMPLIANCE WITH 210.63
  
 5) NOTE: PLEASE SEE 424.3B FOR MINIMUM OVER CURRENT
 PROTECTION FRO AHU. PANEL SCHEDULE INDICATES 50AMP FEED
 WITH #8 AWG. BOTH ARE TOO SMALL.
 MINIMUM IS 125%.
  
 6) NOTE: PLANS INDICATE BOTH DISCONNECTS AND
 RECEPTACLES PER SYMBOL LEGEND NEXT TO THE DRYER,
 OVEN/RANGE AND OTHER LOCATIONS SUCH AS AHU, WATER
 HEATER, CU ETC.
 THERE IS EQUIPMENT AND APPLIANCES IN THE NEC WHICH DO
 REQUIRE DISCONNECTING MEANS HOWEVER OTHER LOCATIONS FOR
 CORD AND PLUG EQUIPMENT WHICH COMES THAT WAY FROM THE
 MANUFACTURE AND IS LISTED AS CORD AND PLUG CONNECTED
 DOES NOT REQUIRE AND ADDITIONAL DISCONNECTING MEANS.
 THERE IS NO VIOLATION TO HAVE A DISCONNECT AND
 RECEPTACLES HOWEVER IF SHOWN THEN THEY MUST BE
 INSTALLED. IN EITHER CASE THE DISCONNECT NOTED ON PLANS
 FOR AHU IS SHOWN TOO SMALL AS NOTED IN COMMENT #5
 ABOVE.
 PLEASE ALSO SEE 110.26 FOR MINIMUM CLEARANCES.
  
 7) NOTE: PLEASE SEE 210.52 FOR RECEPTACLE SPACING.
 BEDROOM #3 MISSING RECEPTACLE WITHIN 6FT OF DOOR.
  
 8) NOTE: PLEASE SEE 210.52B1 AS ALL CIRCUITS FOR DINING
 ROOM RECEPTACLES SHALL BE 20AMP AND #12. PANEL SCHEDULE
 DOES NOT DELINEATE BETWEEN LIGHTS OR RECEPTACLES. PANEL
 SCHEDULE DOES STATE AFCI PROTECTION WHICH IS NOT
 REQUIRED HOWEVER MAY BE INSTALLED.
 PLEASE SEE 210.52B1, 210.11C1 AND 220.53 AS ALL
 ADDITIONAL DEDICATED CIRCUITS ABOVE THE TWO MINIMUM
 SMALL APPLIANCE CIRCUITS SHALL BE FIGURED AT 1500VA FOR
 EACH. LOAD CALCULATIONS ONLY INDICATE TWO SMALL
 APPLIANCES FOR LOADS.
  
 9) NOTE: AS NOTED ABOVE IN COMMENTS #8, SEE 210.52B1,
 210.11C1 AND 220.53 FOR ALL SMALL APPLIANCE LOADS AND
 ANY DEDICATED DINING ROOM RECEPTACLE CIRCUITS. THE
 PANEL SCHEDULE INDICATES 3-SMALL APPLIANCE CIRCUITS
 BEFORE ADDING ANY DINING ROOMS.
  
 10) NOTE: PLEASE SEE 422.13 AS STORAGE TYPE WATER
 HEATERS ARE CONSIDERED CONTINUOUS LOADS. SEE NEC
 COMMENTARY AS THE LAST SENTENCE STATES WHEN SIZING FOR
 SERVICE AND FEEDERS ALSO. THIS MEANS THE WATER HEATER
 4500VA SHALL BE FIGURED AT 125% INTO LOAD CALCULATIONS.
  
 11) NOTE: PLEASE SHOW LOCATION AND ELECTRICAL FOR THE
 SPRINKLER PUMP/SYSTEM AS LISTED ON PANEL SCHEDULE.
 NO REVIEW FOR CODE COMPLIANCE CAN BE DONE AS THE
 LOCATION IS NOT SHOWN. PLEASE REMEMBER TO SEE 430.102
 FOR REQUIRED DISCONNECTING MEANS.
  
  
 ** AS ELECTRICAL ON SHEET IS MISSING SOME INFORMATION,
 THERE MAY BE SOME ITEMS NOT YET SUBMITTED WHICH MAY
 CREATE CODE COMMENTS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2009-08-12 Cont ID  
Sent By btrobaug Date 2009-08-12 Time 14:42 Rev Time 0.00
Received By btrobaug Date 2009-08-12 Time 14:41 Sent To  
Notes
2009-08-12 14:42:24 
  
 ELECTRIC ON PERMIT #09070440./WRT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-07-07 Cont ID  
Sent By btrobaug Date 2009-07-07 Time 11:53 Rev Time 0.00
Received By btrobaug Date 2009-07-07 Time 11:44 Sent To  
Notes
2009-07-07 11:53:22 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2007 FLORIDA RESIDENTIAL BUILDING CODE, 2009
 REVISIONS, 2005 NEC, 2004 FBC AS AMENDED, CHAPTER 1.AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 PLEASE NOTE AN ELECTRICAL PERMIT IS REQUIRED FOR THE
 SCOPE OF WORK PURPOSED. 105.1 FBC AS AMENDED.
  
 1} PLEASE SUBMIT A FLOOR PLAN AND INDICATING THE
 LOCATION OF ALL EQUIPMENT AND DEVICES BEING INSTALLED
 UNDER THE SCOPE OF THIS APPLICATION.106.1.1 FBC.
  
 2} SMOKE ALARMS MUST BE INSTALLED TO COMPLY WITH R313.2
 RESIDENTIAL FLORIDA BUILDING CODE.INDICATE LOCATIONS ON
 THE ELECTRICAL PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-10-01 Cont ID  
Sent By lmartine Date 2009-10-01 Time 16:25 Rev Time 0.00
Received By shill Date 2009-10-01 Time 16:25 Sent To  
Notes
2009-10-15 09:46:56R 9
  
  
2009-10-01 16:33:33GAVE TO MARTINEZ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-09-15 Cont ID  
Sent By lmartine Date 2009-09-09 Time 18:32 Rev Time 0.00
Received By lmartine Date 2009-09-09 Time 18:32 Sent To  
Notes
2009-09-15 18:33:59R-6

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-24 Cont ID  
Sent By dpalmer Date 2009-07-24 Time 08:58 Rev Time 0.00
Received By dpalmer Date 2009-07-24 Time 08:58 Sent To  
Notes
2009-07-24 08:59:15R23

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-07-10 Cont ID  
Sent By rmcdouga Date 2009-07-10 Time 16:25 Rev Time 0.00
Received By rmcdouga Date 2009-06-18 Time 11:38 Sent To  
Notes
2009-06-18 11:46:43R-9

Review Stop L LANDSCAPING
Rev No 3 Status P Date 2009-09-23 Cont ID  
Sent By ajones Date 2009-09-23 Time 08:39 Rev Time 0.00
Received By ajones Date 2009-09-23 Time 08:39 Sent To B
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2009-07-29 Cont ID  
Sent By rkussner Date 2009-07-29 Time 18:21 Rev Time 0.00
Received By rkussner Date 2009-07-29 Time 18:21 Sent To  
Notes
2009-07-29 18:24:31***LANDSCAPE REVIEW FAILED***
  
 PLEASE PROVIDE A COST ESTIMATE OF WORK TO BE PERFORMED
 AND IF THE VALUE OF THE WORK EXCEEDS 50% OF THE VALUE
 OF THE STRUCTURE, THEN THE COMMENTS MADE ON 7/2/09
 SHALL BE ADDRESSED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-07-02 Cont ID  
Sent By rkussner Date 2009-07-02 Time 13:27 Rev Time 0.00
Received By rkussner Date 2009-07-02 Time 13:27 Sent To  
Notes
2009-07-02 13:41:07***LANDSCAPE REVIEW FAILED***
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 1 .PURSUANT TO SECTION 94-441(C)(2), WHEN RENOVATIONS,
 REPAIR, ALTERATION OR REDEVELOPMENT EXCEEDS 50 PERCENT
 OF THE VALUE OF THE STRUCTURE, THE ENTIRE LANDSCAPING
 ON SITE SHALL BE BROUGHT UP TO CURRENT STANDARDS.
  
 2. PLEASE SUBMIT A LANDSCAPE PLAN WITH ALL ALL
 TABULATION NECESARY FOR THE EVALUATION OF COMPLIANCE
 WITH ARTICLE XIV OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS, INCLUDING THE XERISCAPE DESIGN OPTIONS.
  
 3. SUBMIT A COST ESTIMATE THAT INCLUDES THE TOTAL COST
 OF ALL LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO
 UNIT COST.
  
 4. AN IRRIGATION PERMIT IS REQUIRED. THERE SHALL BE
 120% COVERAGE TO ALL AREAS INCLUDING THE RIGHT-OF-WAY.
 IN ADDITION, A RAIN SENSING DEVICE IS REQUIRED.
  
  
  
 IF YOU HAVE ANY QUESITONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-09-16 Cont ID  
Sent By rmcdouga Date 2009-09-16 Time 14:13 Rev Time 0.00
Received By rmcdouga Date 2009-09-16 Time 14:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-08-10 Cont ID  
Sent By rmcdouga Date 2009-08-10 Time 11:00 Rev Time 0.00
Received By rmcdouga Date 2009-08-10 Time 11:00 Sent To  
Notes
2009-08-10 11:36:202007 FBC W/2009 REVISIONS
 LEVEL 1 ALTERATION
  
 DENIED
  
 (1) SUBMIT TWO SETS OF HEATING AND COOLING EQUIPMENT
 SIZING CALCULATIONS IN ACCORDANCE WITH ACCA MANUAL J OR
 OTHER APPROVED METHODOLOGIES AS REQUIRED BY FBC R
 M1401.3. AND REQUESTED IN FIRST REVIEW COMMENTS.
  
 (2) THE TWO SETS OF MECHANICAL PLANS THAT WERE
 SUBMITTED ARE NOT ADEQUATE. IN ADDITION TO THE GRILL
 SIZES, SPECIFY THE DUCT SIZES AND CFM AT EACH SUPPLY
 GRILL ON THE PLANS. SPECIFY THE SIZE AND LOCATION OF
 THE RETURN AIR SYSTEM. PLEASE SPECIFY THE ADDRESS OF
 THE PROJECT AND THE PERSON RESPONSIBLE FOR THE DESIGN
 ON THE PLANS. SEE FBC R M1601 AND N1110.AB.1 OF THE
 2007 ENERGY GLITCH AMENDMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-07-10 Cont ID  
Sent By rmcdouga Date 2009-07-10 Time 14:44 Rev Time 0.00
Received By rmcdouga Date 2009-07-10 Time 14:44 Sent To  
Notes
2009-07-10 15:09:582007 FBC
 RENOVATION
  
 DENIED
 1) BASED ON THE SCOPE OF WORK THAT WAS SPECIFIED, A
 MECHANICAL PERMIT, TWO SETS OF PLANS AND TWO SETS OF
 EQUIPMENT SIZING CALCULATIONS ARE REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-07-06 Cont ID  
Sent By kstevens Date 2009-07-06 Time 11:47 Rev Time 0.00
Received By kstevens Date 2009-07-06 Time 11:47 Sent To  
Notes
2009-07-06 11:56:30NO PLUMBING PLANS SUBMITTED. FIXTURE CHANGEOUT IN THE
 EXACT LOCATION INDICATED. -- PLUMBING PERMIT REQUIRED.

Review Stop Z ZONING
Rev No 1 Status N Date 2009-07-10 Cont ID  
Sent By ajones Date 2009-07-10 Time 16:50 Rev Time 0.00
Received By ajones Date 2009-07-10 Time 16:42 Sent To  
Notes
2009-07-10 16:43:36FAILED MUST COMPLY WITH LANDSCAPING COMMENTS.