Plan Review Details - Permit 09060420
Plan Review Stops For Permit 09060420
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-08-19 Cont ID  
Sent By shill Date 2009-08-19 Time 11:32 Rev Time 0.00
Received By shill Date 2009-08-19 Time 11:32 Sent To  
Notes
2009-08-19 11:33:20***PROVISO***
 1. VALUE TO BE ADJUSTED PRIOR TO ISSUANCE
 2. REVISION REQUIRED - PLANS TO INCLUDE WIND DESIGN
 CRITERIA FBC1603.1.4.
 AN INSPECTION HOLD HAS BEEN PLACED ON THIS PERMIT
 SUBJECT TO REVISION OF PLANS.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-07-16 Cont ID  
Sent By shill Date 2009-07-16 Time 17:24 Rev Time 0.00
Received By shill Date 2009-07-16 Time 17:24 Sent To  
Notes
2009-07-16 17:26:44***PROVISO***
 1. VALUE TO BE ADJUSTED PRIOR TO ISSUANCE
 2. REVISION REQUIRED - PLANS TO INCLUDE WIND DESIGN
 CRITERIA FBC1603.1.4.
 AN INSPECTION HOLD HAS BEEN PLACED ON THIS PERMIT
 SUBJECT TO REVISION OF PLANS.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-09-01 Cont ID  
Sent By dpalmer Date 2009-09-01 Time 15:11 Rev Time 0.00
Received By dpalmer Date 2009-09-01 Time 15:11 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-08-18 Cont ID  
Sent By dpalmer Date 2009-08-18 Time 13:13 Rev Time 0.00
Received By dpalmer Date 2009-08-18 Time 13:13 Sent To B
Notes
2009-08-18 13:14:09** DENIED PLANS REVIEW **
 NOTE FROM PREVIOUS REVIEW STILL THE SAME. NO
 INFORMATION PROVIDED.
  
 2) NOTE: THE VALUE FOR THE APPLIED SCOPE OF WORK NEEDS
 TO BE UPDATED. THE APPLIED VALUE FOR THE SIGN IS
 EXTREMELY LOW. IF AN APPROPRIATE VALUE IS NOT ADJUSTED
 ONE WILL BE ADJUSTED USING THE ADOPTED GUIDES UNDER FBC
 108.3.
 LED LIGHTING KITS FOR SIGNS IS SUBSTANTIAL.
 IT IS NOT POSSIBLE TO DESIGN, BUILD, INSTALL AND WIRE
 THE SIGNS SHOWN ON PLANS FOR THE APPLIED VALUE OF
 $1500.00. THE VALUE IS TO INCLUDE ANY ITEMS EVEN IF
 OWNER SUPPLIED.
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-07-04 Cont ID  
Sent By eschneid Date 2009-07-04 Time 14:26 Rev Time 0.00
Received By dpalmer Date 2009-07-04 Time 15:05 Sent To B
Notes
2009-07-04 15:05:25 
 ** DENIED PLANS REVIEW **
  
 1) NOTE: PLANS SUBMITTED NEED TO SHOW MINIMUM
 SUFFICIENT CODES AND ELECTRICAL DETAILS PER FBC 2007
 AND NEC 2005.
 PLANS SUBMITTED ARE NOT SUFFICIENT FOR CLARITY,
 INFORMATION OR MINIMUM DESIGNS.
 PLEASE SEE NEC 250,600 FOR SOME OF THE MINIMUMS. FBC
 106.1.1,106.1.2,106.5 FOR CLARITY, COORDINATION,
 DETAILS OF RECORD PLANS.
 PLANS NEED TO STATE THE FOLLOWING CODES FOR THE
 RELEVANT SCOPE OF WORK.
 2005 NFPA-70
 ** PLANS STATE THE 2008 NEC, HOWEVER THE STATE OF
 FLORIDA TO DATE HAS NOT ADOPTED THE NEW VERSION OF THE
 NEC.
  
 2) NOTE: THE VALUE FOR THE APPLIED SCOPE OF WORK NEEDS
 TO BE UPDATED. THE APPLIED VALUE FOR THE SIGN IS
 EXTREMELY LOW. IF AN APPROPRIATE VALUE IS NOT ADJUSTED
 ONE WILL BE ADJUSTED USING THE ADOPTED GUIDES UNDER FBC
 108.3.
 LED LIGHTING KITS FOR SIGNS IS SUBSTANTIAL.
 IT IS NOT POSSIBLE TO DESIGN, BUILD, INSTALL AND WIRE
 THE SIGNS SHOWN ON PLANS FOR THE APPLIED VALUE OF
 $1500.00. THE VALUE IS TO INCLUDE ANY ITEMS EVEN IF
 OWNER SUPPLIED.
  
 3) NOTE: PLEASE SHOW DISCONNECTS PER 600.5.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-09-01 Cont ID  
Sent By kstevens Date 2009-09-01 Time 11:05 Rev Time 0.00
Received By kstevens Date 2009-09-01 Time 11:05 Sent To  
Notes
2009-09-01 11:06:24SENT TO DVPALMER.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-08-04 Cont ID  
Sent By rmcdouga Date 2009-08-04 Time 10:00 Rev Time 0.00
Received By rmcdouga Date 2009-08-04 Time 10:00 Sent To  
Notes
2009-08-04 10:01:02SENT TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-07-16 Cont ID  
Sent By shill Date 2009-07-16 Time 17:27 Rev Time 0.00
Received By shill Date 2009-06-17 Time 14:51 Sent To  
Notes
2009-06-17 14:51:27TO ZONING
  

Review Stop Z ZONING
Rev No 2 Status P Date 2009-08-11 Cont ID  
Sent By eschneid Date 2009-08-11 Time 10:33 Rev Time 0.30
Received By eschneid Date 2009-08-11 Time 10:33 Sent To E
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2009-06-22 Cont ID  
Sent By eschneid Date 2009-06-22 Time 14:24 Rev Time 1.00
Received By eschneid Date 2009-06-22 Time 14:24 Sent To E
Notes
2009-06-22 14:25:31FAILED
  
 1) THE CITYPLACE MANAGEMENT APPROVAL STAMP IS REQUIRED
 ON THE DRAWINGS.
  
 2) THE CITYPLACE MASTER SIGN PLAN LIMITS FACADE SIGN
 TEXT TO BE SIZED BETWEEN 8 AND 12 INCHES IN HEIGHT.
 PROVIDE THE MINIMUM AND MAXIMUM HEIGHT OF THE LETTERS
 FOR THE FACADE SIGNS.
  
 3) THE CITYPLACE MASTER SIGN PLAN ALLOWS ONE SQUARE
 FOOT OF FACADE SIGNAGE PER ONE LINEAR FOOT OF STORE
 FRONTAGE. PROVIDE THE LINEAR FRONTAGE OF THE ROSEMARY
 FACADE AND THE SIDE FACADE. NOTE: THE ARCADE DOES NOT
 COUNT AS FACADE ON THE SIDE, JUST THE SPACE THE STORE
 OCCUPIES. ALSO PROVIDE THE DIMENSIONS OF THE FACADE
 SIGNS.
  
 4) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT SIGNS
 BE INSTALLED WITHIN SPECIFIC SIGN ZONES. THE SIDE
 FACADE SIGN IS NOT IN A DESIGNATED SIGN ZONE.
  
 5) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT BLADE
 SIGNS BE A MAXIMUM OF 18 INCHES BY 18 INCHES. PROVIDE
 THE SIZE OF THE BLADE SIGN.
  
 6) THE SUBMITTED PLANS STATE THE BLADE SIGN IS A CHANGE
 OUT ON AN EXISTING BRACKET. THE RENDERING PROVIDED
 SHOWS THE SIGN IN A DIFFERENT LOCATION THAN THE CURRENT
 SIGN FRAME.
  
 7) THE CITYPLACE MASTER SIGN PLAN REQUIRES THAT BLADE
 SIGNS (INCLUDING MOUNTING FRAMES) PROVIDE A MINIMUM OF
 8 FEET OF CLEARANCE. PROVIDE THE BLADE SIGN CLEARANCE.
  
 8) THE CITYPLACE MASTER SIGN PLAN ALLOWS CITYPLACE TO
 GRANT VARIANCES FROM THE NUMERICAL AND LOCATIONAL
 PROVISIONS OF 2 THROUGH 5 ABOVE. PROVIDE A NOTARIZED
 LETTER FROM CITYPLACE THAT THEY HAVE GRANTED THE
 SPECIFIC VARIANCES BEING REQUESTED FOR THE PROPOSED
 SIGNS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.