| 2009-06-12 14:29:56 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. |
| | 2007 FL. RESIDENTIAL CODE W/ 2009 REVISIONS. |
| | |
| | 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 2- ROOF TILE PRODUCT APPROVAL NOA 06-0526.08. MARK HOW |
| | IS THE TILE GOING TO BE FASTENED TO VERIFY COMPLIANCE |
| | WITH THE UPLIFT PRESSURES OF SEC. R301 OF 2007 FLORIDA |
| | RESIDENTIAL CODE. (NOTE: BUILDING IS LOCATED ON |
| | EXPOSURE "C"). |
| | IF USING POLYFOAM OR ANY OTHER ADHESIVE, THEN PROVIDE |
| | CORRESPONDING PRODUCT APPROVAL. AS REQUIRED BY DCA RULE |
| | 9B-72. |
| | |
| | |
| | 3- FLAT ROOF PRODUCT APPROVAL NOA 08-0410.09: |
| | A) PROVIDE PAGE SHOWING APPROVED ASSEMBLY THAT IS GOING |
| | TO BE INSTALLED. INFORMATION SUBMITTED IS MISSING THIS |
| | INFORMATION. |
| | |
| | B) MARK BASE SHEET SPECIFIC FASTENING OPTION ON |
| | SELECTED APPROVED ASSEMBLY TO VERIFY COMPLIANCE WITH |
| | DESIGN PRESSURES OF SECTION R301 OF 2007 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | C) PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT |
| | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL |
| | LIMITATION #7. (NOTE: ASSEMBLIES THAT ARE LIMITED BY |
| | GENERAL LIMITATION #9 MAY NO BE GOOD IN THIS AREA |
| | BECAUSE THEY DON'T MEET THE DESIGN PRESSURES FOR THIS |
| | AREA). |
| | NOTE: ACCORDING TO 2009 REVISIONS TO 2007 FLORIDA |
| | RESIDENTIAL CODE, THIS BUILDING IS LOCATED ON EXPOSURE |
| | "C". HAVE THIS IN CONSIDERATION WHEN PROVIDING THE RAS |
| | 117 CALCULATIONS. |
| | |
| | D) PRODUCT APPROVAL SUBMITTED IS MISSING PAGE 38, WHICH |
| | SHOWS ALL GENERAL LIMTATIONS. PROVIDE THIS SHEET. IF |
| | GENERAL LIMITATION #7 ON SHEET #38 OF NOA SUBMITTED |
| | REQUIRES THE RAS 117 CALCULATIONS TO BE SIGNED AND |
| | SEALED, THEN NEED TO PROVIDE SIGNED AND SEALED |
| | CALCULATIONS. IF THE CALCULATIONS ARE NOT REQUIRED TO |
| | BE SIGNED AND SEALED, THEN CONTRACTOR MAY SUBMIT |
| | CALCULATIONS OR PRESCRIPTIVE METHOD WITHOUT HAVING TO |
| | BE SIGNED AND SEALED. |
| | |
| | 4- PERMIT VALUATION DECLARED IN THE PERMIT APPLICATION |
| | IS TOO LOW. VALUATION WAS UPDATED AS REQUIRED BY SEC. |
| | 108.3 CITY AMENDMENTS TO FBC. OWES $147.07 FOR UPDATED |
| | VALUATION. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |
| | |
| | |