Plan Review Details - Permit 09060290
Plan Review Stops For Permit 09060290
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2009-07-14 Cont ID  
Sent By jgomez Date 2009-07-14 Time 08:46 Rev Time 0.00
Received By jgomez Date 2009-07-14 Time 08:46 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-09-21 Cont ID  
Sent By dpalmer Date 2009-09-21 Time 15:57 Rev Time 0.00
Received By dpalmer Date 2009-09-21 Time 15:57 Sent To PC
Notes
2009-09-21 15:59:40REDLINED PLANS FOR 22K AIC RATING ALSO GE TO BE CWP AND
 2GRND RODS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-09-21 Cont ID  
Sent By dpalmer Date 2009-09-21 Time 15:52 Rev Time 0.00
Received By dpalmer Date 2009-09-21 Time 15:52 Sent To  
Notes
2009-09-21 15:52:19** TEMP FAILED, CALLED AND LEFT MESSAGE ON CONTRACTOR
 VOICEMAIL. NEED AIC RATING OF NEW MAIN BREAKER PANEL.
 110.9
  
 ALSO WAS GOING TO REDLINE PLANS FOR METALLIC CWP AND
 2ND GRND ROD PER 250.50, 250.56
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-08-05 Cont ID  
Sent By dpalmer Date 2009-08-05 Time 13:52 Rev Time 0.00
Received By dpalmer Date 2009-08-05 Time 13:52 Sent To PC
Notes
2009-08-05 13:53:24REDLINED PLANS FOR 20AMP AND #12

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-06-19 Cont ID  
Sent By dpalmer Date 2009-06-19 Time 14:16 Rev Time 0.00
Received By dpalmer Date 2009-06-19 Time 14:13 Sent To  
Notes
2009-06-19 14:16:59** DENIED REVIEW **
  
 1) NOTE: PERMIT APPLICATION STATES ELECTRICAL SCOPE OF
 WORK INCLUDING A SIGNED ON ELECTRICAL CONTRACTOR.
 PACKAGE DOES NOT INCLUDE ANY ELECTRICAL PLANS .
 PLEASE SUBMIT ELECTRICAL PLANS FOR SCOPE OF WORK. NEC
 2005
 PLEASE ALSO SEE FBC R313.1 AND NFPA-72 FOR SMOKE ALARMS
 REQUIRED TO MEET CURRENT CODE. IF THE EXISTING DWELLING
 HAS ALL MEETING CURRENT CODE PLEASE UPDATED ELECTRICAL
 PLANS TO SHOW LOCATIONS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-15 Cont ID  
Sent By kstevens Date 2009-09-15 Time 15:57 Rev Time 0.00
Received By kstevens Date 2009-09-15 Time 15:57 Sent To  
Notes
2009-09-15 15:57:37SENT TO DVPALMER.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-07-14 Cont ID  
Sent By jgomez Date 2009-07-14 Time 08:58 Rev Time 0.00
Received By jgomez Date 2009-06-12 Time 10:12 Sent To  
Notes
2009-06-12 10:44:23SENT TO R20

Review Stop P PLUMBING
Rev No 1 Status N Date 2009-07-07 Cont ID  
Sent By kstevens Date 2009-07-07 Time 16:00 Rev Time 0.00
Received By kstevens Date 2009-07-07 Time 16:00 Sent To  
Notes
2009-07-07 16:02:18PLUMBING FIXTURE REPLACEMENT ONLY. -- KITCHEN SINK & 2
 VANITIES (LAVS).

Review Stop Z ZONING
Rev No 1 Status N Date 2009-06-25 Cont ID  
Sent By mcruz Date 2009-06-25 Time 15:57 Rev Time 0.00
Received By mcruz Date 2009-06-25 Time 15:57 Sent To  
Notes
2009-06-25 15:57:45*ZONING REVIEW NOT REQUIRED: INTERIOR WORK ONLY AND THE
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  
 PLACED IN R20