Plan Review Details - Permit 09060284
Plan Review Stops For Permit 09060284
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-28 Cont ID  
Sent By jwitmer Date 2009-07-28 Time 14:45 Rev Time 0.33
Received By jwitmer Date 2009-07-28 Time 14:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-07-08 Cont ID  
Sent By jwitmer Date 2009-07-08 Time 08:50 Rev Time 0.50
Received By jwitmer Date 2009-07-08 Time 08:20 Sent To  
Notes
2009-07-08 08:38:15BUILDING PLAN REVIEW
 PERMIT: 09060285
 ADD: 650 BELVEDERE RD
 CONT: CORE STATES CONSTRUCTION
 TEL: (561)997-6273
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTI
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-07-30 Cont ID  
Sent By dpalmer Date 2009-07-30 Time 16:06 Rev Time 0.00
Received By dpalmer Date 2009-07-30 Time 16:06 Sent To  
Notes
2009-07-30 16:07:09ELEC SUB PERMIT AND LV SUB PERMITS REQUIRED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-07-05 Cont ID  
Sent By dpalmer Date 2009-07-05 Time 12:22 Rev Time 0.00
Received By dpalmer Date 2009-07-05 Time 12:10 Sent To  
Notes
2009-07-05 12:22:33 
 ** DENIED PLANS REVIEW **
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING MINIMUM CODES ARE
 STATED ON PLANS AS THEY ARE RELEVANT FOR THE MINIMUM
 DESIGNS.
 2007 FBC W/ 2009 SUPPLEMENTS
 2005 NFPA-70
 2006 NFPA-101
  
 2) NOTE: THE ENGINEERING FIRM SHALL INCLUDE ALL
 REQUIRED INFORMATION ON TITLE BLOCKS PER FAC
 61G15-23.002. PLEASE ALSO SEE THE SAME SECTION OF THE
 FLORIDA ADMINISTRATIVE CODE REQUIRES THE CERTIFICATE OF
 AUTHORIZATION NUMBER. THIS IS AN REQUIRED LICENSE
 NUMBER PER FLORIDA STATUTES 471.023
 IF THERE ARE ANY QUESTIONS ON HOW TO PROCEED PLEASE
 CALL.
  
 3) NOTE: PLEASE SEE 13-415.AB.5. PLEASE PROVIDE SPACE
 OF NEW WORK SHOWING NEW LIGHTING TO EXISTING. THE
 ADDITION OF NEW LIGHTING TO EXISTING MAY OR MAY NOT
 EXCEED LIGHTING LEVELS PERMITTED.
 PLEASE CALL TO GO OVER AS ALLOWANCES IN THE FBC AS THEY
 HAVE CHANGED SUBSTANTIALLY. THE LIGHTING LAYOUT ON
 PLANS DOES NOT SEEM TO COORDINATE WITH THE ACTUAL
 LOCATION FOR ALL LIGHTS.
  
 *** ALL LOW VOLTAGE WORK SHALL BE UNDER SEPARATE
 PERMITS.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-08-05 Cont ID  
Sent By mawillia Date 2009-08-05 Time 11:24 Rev Time 0.00
Received By mawillia Date 2009-08-05 Time 11:14 Sent To  
Notes
2009-08-05 11:24:46*****APPROVED*****
  
  
 PLAN SHEET A1.0 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2009-07-14 Cont ID  
Sent By mawillia Date 2009-07-14 Time 14:32 Rev Time 0.00
Received By mawillia Date 2009-07-14 Time 14:21 Sent To  
Notes
2009-07-14 14:25:35*****FIRE STAMPING NEEDED*****
  
 THE APPROPIATE PLAN SHEET(S) TO BE FIRE-STAMPED WHEN
 THE OTHER PLAN REVIEWERS' COMMENTS HAVE BEEN ADDRESSED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-17 Cont ID  
Sent By kstevens Date 2009-07-17 Time 12:54 Rev Time 0.00
Received By kstevens Date 2009-07-17 Time 12:55 Sent To  
Notes
2009-07-17 13:02:40SENT TO C-2.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-07-14 Cont ID  
Sent By mawillia Date 2009-07-14 Time 14:21 Rev Time 0.00
Received By mawillia Date 2009-06-12 Time 09:42 Sent To  
Notes
2009-06-12 13:30:20SENT TO COMMERCIAL C28

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-08-06 Cont ID  
Sent By kstevens Date 2009-08-06 Time 16:23 Rev Time 0.00
Received By kstevens Date 2009-08-06 Time 16:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-07-02 Cont ID  
Sent By kstevens Date 2009-07-02 Time 16:08 Rev Time 0.00
Received By kstevens Date 2009-07-02 Time 16:08 Sent To  
Notes
2009-07-02 16:09:51DENIED
 REFERENCE:
 FBC-2007 PLUMBING
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHT P1.0 THE FIRM LICENSE NUMBER, (CERTIFICATE OF
 AUTHROIZATION), IS REQUIRED IN THE TITLE BLOCK OF EACH
 SHEET. FAC 61G1-16.004(2) & FS 481.2055.
  
 2, SHT P1.0 THE PRINTED NAME OF THE PERSON SEALING THE
 PLANS IS REQUIRED ON EACH SHEET. FAC 61G1-16.004(6) &
 FS 481.2055.
  
 3. SHT P1.0 THE REVERSE OSMOSIS SHALL MEET THE
 REQUIREMENTS OF NFS 58. OTHER WATER FILTERS SHALL MEET
 THE REQUIREMENTS OF NSF 42. PLEASE SUBMIT MANUF.
 SPECIFICATION SHEETS SHOWING COMPLIANCE. SECTION 611.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2009-06-15 Cont ID  
Sent By eschneid Date 2009-06-15 Time 09:40 Rev Time 0.25
Received By eschneid Date 2009-06-15 Time 09:39 Sent To  
Notes
2009-06-15 09:42:15VALUE OF PERMIT IS $50,000 WHICH IS LESS THAN 50% OF
 THE VALUE OF THE STRUCTURE.
  
 NOTE THAT IMPROVEMENTS WITHIN ANY ONE YEAR PERIOD
 EXCEEDING 50% OF THE VALUE OF THE STRUCTURE WILL
 REQUIRE VERIFICATION THAT THE LANDSCAPE ON SITE MEETS
 THE ORIGINALLY APPROVED PLAN OR THE CURRENT CITY
 LANDSCAPE REQUIREMENTS.