Plan Review Details - Permit 09060251
Plan Review Stops For Permit 09060251
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-08-18 Cont ID  
Sent By jwitmer Date 2009-08-18 Time 12:11 Rev Time 1.20
Received By jwitmer Date 2009-08-18 Time 11:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-07-07 Cont ID  
Sent By jwitmer Date 2009-07-07 Time 14:30 Rev Time 1.33
Received By jwitmer Date 2009-07-07 Time 13:19 Sent To  
Notes
2009-07-07 13:54:12BUILDING PLAN REVIEW
 PERMIT: 09060251
 ADD: 318 CLEMATIS ST
 CONT: HORGAN GENERAL CONTRACTING INC
 TEL: (561)744-0991
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS. PLEAS CORRECT THE COVER
 SHEET AND A2 ,THE STRUCTURAL NOTES, THERE ARE NO PALM
 BEAH COUNTY AMENDMENTS.
  
 2) PLANS WILL ALSO BE REVIEWED TO THE 2007 EXISTING
 BUILDING CODE W/ 2009 SUPPLEMENTS, PLEASE INDICATE TO
 WHAT LEVEL ALTERATION WILL BE COMPLETED UNDERTHIS
 PERMIT.
 401.4 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 403, 404 AND 405 OF THIS CODE.
  
 3) NEITHER SHEET A1 NOR A2 LIFE SAFETY INDICATE
 COMPLIANCE WITH :
 3A) 11-5.1 GENERAL. EXCEPT AS SPECIFIED OR MODIFIED IN
 THIS SECTION, RESTAURANTS AND CAFETERIAS SHALL COMPLY
 WITH THE REQUIREMENTS OF SECTION 11-4.1 TO SECTION
 11-4.35. WHERE FIXED TABLES (OR DINING COUNTERS WHERE
 FOOD IS CONSUMED BUT THERE IS NO SERVICE) ARE PROVIDED,
 AT LEAST 5 PERCENT, BUT NOT LESS THAN ONE, OF THE FIXED
 TABLES (OR A PORTION OF THE DINING COUNTER) SHALL BE
 ACCESSIBLE AND SHALL COMPLY WITH SECTION 11-4.32 AS
 REQUIRED IN SECTION 11-4.1.3(18). IN ESTABLISHMENTS
 WHERE SEPARATE AREAS ARE DESIGNATED FOR SMOKING AND
 NONSMOKING PATRONS, THE REQUIRED NUMBER OF ACCESSIBLE
 FIXED TABLES (OR COUNTERS) SHALL BE PROPORTIONALLY
 DISTRIBUTED BETWEEN THE SMOKING AND NONSMOKING AREAS.
 IN NEW CONSTRUCTION, AND WHERE PRACTICABLE IN
 ALTERATIONS, ACCESSIBLE FIXED TABLES (OR COUNTERS)
 SHALL BE DISTRIBUTED THROUGHOUT THE SPACE OR FACILITY.
  
 3B) 11-5.2 COUNTERS AND BARS. WHERE FOOD OR DRINK IS
 SERVED AT COUNTERS EXCEEDING 34 INCHES (865 MM) IN
 HEIGHT FOR CONSUMPTION BY CUSTOMERS SEATED ON STOOLS OR
 STANDING AT THE COUNTER, A PORTION OF THE MAIN COUNTER
 WHICH IS 60 INCHES (1525 MM) IN LENGTH MINIMUM SHALL BE
 PROVIDED IN COMPLIANCE WITH SECTION 11-4.32 OR SERVICE
 SHALL BE AVAILABLE AT ACCESSIBLE TABLES WITHIN THE SAME
 AREA.
  
 4) THE LEFT SIDE OF THE RESTAURANTTHE FIRST FIVE BOOTHS
 DO NOT MEET: 1014.4.3.3 TABLE AND SEATING AISLE
 ACCESSWAY LENGTH. THE LENGTH OF TRAVEL ALONG THE AISLE
 ACCESSWAY SHALL NOT EXCEED 30 FEET (9144 MM) FROM ANY
 SEAT TO THE POINT WHERE A PERSON HAS A CHOICE OF TWO OR
 MORE PATHS OF EGRESS TRAVEL TO SEPARATE EXITS.
  
 5) SHEET A-1 INDICATES NEW STAIRS TO THE RAISED DECK
 BAR AREA# 2, DETAIL 6 ON A3 INDICATES THE STAIR RAILING
 BUT NOT THE ACCESSIBLE EXTENSIONS REQUIRED.11-4.9.4(2)
 IF HANDRAILS ARE NOT CONTINUOUS, THEY SHALL EXTEND AT
 LEAST 12 INCHES (305 MM) BEYOND THE TOP RISER AND AT
 LEAST 12 INCHES (305 MM) PLUS THE WIDTH OF ONE TREAD
 BEYOND THE BOTTOM RISER. AT THE TOP, THE EXTENSION
 SHALL BE PARALLEL WITH THE FLOOR OR GROUND SURFACE. AT
 THE BOTTOM, THE HANDRAIL SHALL CONTINUE TO SLOPE FOR A
 DISTANCE OF THE WIDTH OF ONE TREAD FROM THE BOTTOM
 RISER; THE REMAINDER OF THE EXTENSION SHALL BE
 HORIZONTAL [SEE FIGURE 19(C) AND FIGURE 19(D)].
 HANDRAIL EXTENSIONS SHALL COMPLY WITH SECTION 11-4.4.
  
 6) SINCE THE BAR# 2 IS AN ALTERED AREA PLEASE PROVIDE
 VERTICAL ACCESSIBLITY11-4.1.6(1)(F).
  
 7) SHEET A3 INDICATES DECRATIVE COLUMNS AND ARCHES, NO
 FINISH INFORMATION HAS BEEN PROVIDED FOR WALLS NOR TRIM
 SECTION 803 AND TABLE 803.5.
  
 8) THE MECHANICAL PLANS INDICATE AN EXTERIOR WALL
 LOUVER, PLEASE PROVIDE PRODUCT APPROVAL FOR WALL
 LOUVER. RULE 9B-72 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED
 TO COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 9A) THE MECHANICAL PLANS INDICATE NEW EXHAUST FANS
 THROUGH THE ROOF DECK PLEASE PROVIDE COMPLIANCE WITH:
 301.13 FBC MECHANICAL. WIND RESISTANCE. MECHANICAL
 EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST WIND
 PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 9B) EXHAUST FANS 1509.7 MECHANICAL UNITS. ROOF MOUNTED
 MECHANICAL UNITS SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES (203 MM) ABOVE THE ROOF SURFACE, OR
 WHERE ROOFING MATERIALS EXTEND BENEATH THE UNIT, ON
 RAISED EQUIPMENT SUPPORTS PROVIDING A MINIMUM CLEARANCE
 HEIGHT IN ACCORDANCE WITH TABLE 1509.7.
  
  
 10) 1013.5 MECHANICAL EQUIPMENT. GUARDS SHALL BE
 PROVIDED WHERE APPLIANCES, EQUIPMENT, FANS, ROOF HATCH
 OPENINGS OR OTHER COMPONENTS THAT REQUIRE SERVICE ARE
 LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR OPEN
 SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS
 LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR,
 ROOF OR GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO
 AS TO PREVENT THE PASSAGE OF A 21-INCH-DIAMETER (533
 MM) SPHERE. THE GUARD SHALL EXTEND NOT LESS THAN 30
 INCHES (762 MM) BEYOND EACH END OF SUCH APPLIANCE,
 EQUIPMENT, FAN OR COMPONENT. SEE MECHANICAL COMMENTS
 FOR POSSIBLE ACCESS ISSUES.
  
 11) PLANS ARE NOT CLEAR AS IF THIS IS A SINGLE STORY
 BUILDING OR MULTIPLE STORIES THAT WOULD REQUIRE SHAFT
 ENCLOSURES FOR EXHAUST DUCTS.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-09-25 Cont ID  
Sent By dpalmer Date 2009-09-25 Time 20:25 Rev Time 0.00
Received By dpalmer Date 2009-09-25 Time 20:25 Sent To B
Notes
2009-09-25 20:26:40** PROVISO **
  
 1) NOTE: PLEASE SEE 13-415.AB.5, 13-415.B.1 AND
 APPENDIX B FOR LIGHTING PERFORMANCE CALCULATIONS.
 PLANS NEED TO INDICATE THE TOTAL ALLOWED WATTAGE AND
 THE TOTAL DESIGN. BASED ON THE AMOUNT SHOWN ON PLANS
 THE DESIGN AND ALLOWABLE IS NOT SHOWN AS NEEDED.
 PLEASE CALL TO GO OVER.
  
 ** SEPARATE PERMITS FOR LOW VOLTAGE SYSTEMS INCLUDING
 PLANS.
 ** SEPARATE PERMIT AND PLAN LAYOUT FOR ANY FIRE ALARM
 DEVICE RELOCATIONS OR INSTALLATIONS. ( PLEASE BE SURE
 TO SEE FBC CHAPTER 11 FOR ADA COMPLIANCE FOR ALL
 DEVICES. 11-4.28.1, .2 AND .3.
  
 ** ALL OTHER CHANGES ARE REQUIRED TO BE REVISED BEFORE
 ROUGH ALONG WITH COMMENTS ABOVE.
  
 ** IMPORTANT**
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2009-09-21 Cont ID  
Sent By dpalmer Date 2009-09-21 Time 14:54 Rev Time 0.00
Received By dpalmer Date 2009-09-21 Time 14:54 Sent To  
Notes
2009-09-21 14:54:29 
  
  
 ** DENIED **
  
  
 1) NOTE: IF NEW CONTROL IS INSTALLED FOR REAR EXTERIOR
 LIGHT IT MUST MEET 13-415.AB.1.4.
  
 2) NOTE: RISER DIAGRAM AND PANEL SCHEDULES INDICATE ALL
 EQUIPMENT AS EXISTING. HOWEVER SOME ITEMS ARE IN NEED
 OF MINIMUM CODE COMPLIANCE AS THEY ARE FIRE AND LIFE
 SAFETY HAZARDS.
 RISER INDICATES TAPPED CONDUCTORS FROM GUTTER TO EACH
 PANEL. PLEASE 240.21 AS ALL TAPPED CONDUCTORS SHALL
 TERMINATE IN OVER CURRENT PROTECTION. PLEASE ALSO SEE
 408.36 FOR ANY LIGHTING AND APPLIANCE PANEL BOARDS.
  
 THE PANELS ARE ALL SHOWN AS 225AMP MLO. EVEN IF 225AMP
 MAINS WERE INSTALLED, TWO OF THE PANELS SUCH AS *A* AND
 *C* HAVE 3/0 CONDUCTORS TAPPED FROM GUTTER WHICH ARE
 NOTE RATED FOR 225AMPS.
 310.16, 110.14.
  
 THE RISER ALMOST APPEARS TO INDICATE 2-POLE 225AMP
 BREAKERS FOR EACH, HOWEVER THIS DOES NOT SEEM POSSIBLE
 WHEN THE CONDUCTORS RUN TO PANELS ARE FOR 3-PHASE
 PANELS AND EACH OF THE PANEL SCHEDULES ALSO INDICATE
 THESE PANELS AS 3-PHASE.
  
 ** THERE ARE ITEMS ON THE ABOVE WHICH ARE NOT KNOWN. IN
 BOTH CASES 3/0 AWG IS ONLY FOR 200AMP IN COMMERCIAL
 INSTALLATIONS.
  
 3) NOTE: THERE ARE LIGHT FIXTURES WHICH ARE NOTED AS
 250W PAR -38 FIXTURES FOR TRACKS. PLEASE EXPAND ON
 LIGHTING CALCULATIONS ON THE AMOUNT OF WHICH TYPE OF
 FIXTURES ARE GOING TO BE INSTALLED.
  
 4) NOTE: PLEASE SHOW WHERE LOADS IN CALCULATIONS ARE
 SHOWN PER 220.43 A AND B.
  
 5) NOTE: PLEASE SEE 210.8B2 AS ALL 15/20AMP 120V
 RECEPTACLES IN KITCHEN ARE REQUIRED TO BE GFI/GFI
 PROTECTED.
  
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2009-08-26 Cont ID  
Sent By dpalmer Date 2009-08-26 Time 13:21 Rev Time 0.00
Received By dpalmer Date 2009-08-26 Time 13:21 Sent To  
Notes
2009-08-26 13:25:00NO REVIEW DONE PER GC AND CHRIS TYSON. ELECTRICLA HAS
 BEEN REMOVED FROM REVIEW PER LETTER OF REQUEST.
 ELECTRICAL TO BE SUBMITTED AS REVISION AFTER MAIN
 PERMIT IS ISSUED. THE ELECTRICAL PERMIT WHICH WAS
 SIGNED ON IS ISSUED AS AN ELECTRICAL FOR SLAB WORK
 ONLY. ONCE ELECTRICAL REVISIONS ARE OK THEN THE EC MAY
 COME IN PAY THE SUB PERMIT FEE, REFERENCE MAIN AND TURN
 AROUND PERMIT WILL BE ISSUED.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-07-05 Cont ID  
Sent By dpalmer Date 2009-07-05 Time 13:06 Rev Time 0.00
Received By dpalmer Date 2009-07-05 Time 12:37 Sent To  
Notes
2009-07-05 13:06:12 
 ** DENIED PLANS REVIEW **
  
 1) NOTE: PLEASE SEE COVER SHEET WHICH REFLECTS THE
 CONTRACTOR AS CBT CONSTRUCTION HOWEVER THE PERMIT
 APPLICATION STATES HORGAN GENERAL CONTR.
 THE CONTRACTOR IS NOT REQUIRED TO BE NOTED ON PLANS.;
 THIS IS NOT A CODE REQUIRED ITEM ONLY FOR COORDINATION
 OF RECORD PLANS.
  
 2) NOTE: PLANS NEED TO STATE THE FOLLOWING CODES
 SUBMITTED AFTER MARCH 1ST, 2009
 AT THIS TIME THERE ARE REFERENCES TO CODES WHICH ARE NO
 LONGER APPLICABLE. PLEASE ALSO KNOW THAT STATING *THE
 LATEST EDITION* IS NOT ACCEPTABLE. THERE ARE MANY
 INSTANCES WHERE THE LATEST EDITION IN PUBLICATION IS
 NOT ADOPTED OR IS NEVER ADOPTED.
 ALL RECORD SET OF PLANS IS REQUIRED BY LAW AND FBC TO
 STATE THE CODES RELEVANT TO THE SPECIFIC PROJECT AND
 DESIGN.
 PLEASE LIST AND DESIGN PER THE FOLLOWING ADOPTED CODES
 AT THIS TIME FOR THIS REVIEWER. THERE MAY BE OTHER
 CODES REQUESTED BY OTHER TRADES.
  
 2007 FBC WITH 2009 SUPPLEMENTS.
 2005 NFPA_70
 2006 NFPA-101
 2002 NFPA-72
  
 PER FS 633,553.73,FAC 69A-60.004, 69A-3.0125 ETC
  
 3) NOTE: ONE COMPLETE SET OF PLANS FOR MEP DESIGNERS
 ARE *PHOTO-COPIES* OF SIGNED, DATED AND SEALED PLANS.
 PLEASE SEE FAC 61G15-23.002 AS THIS IS NOT PERMITTED.
 BOTH SETS FOR THE MEP DESIGN PROFESSIONAL SHALL BE
 ORIGINAL.
 FS 471.025
 PLEASE BE SURE TO ADDRESS FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER TRADES.
  
 4) NOTE: SCOPE OF WORK IS NOT CLEAR. SOME AREAS ARE
 INDICATING NO WORK HOWEVER OTHER DETAILS ON PLANS SEEM
 TO INDICATE WORK IN THOSE SAME AREAS.
 SOME OF WHAT IS SHOWN AS EXISTING TO REMAIN IS NOT AT
 LOCATION OR DIFFERENT.
 MANY ITEMS ON PLANS ARE SO LIGHT THAT EXISTING CODE
 COMPLIANCE CAN NOT BE VERIFIED AS SAFE FOR NEW
 OCCUPANCY. THE FIRE ALARM DEVICE LOCATIONS FOR EXAMPLE
 ARE ONE EXAMPLE OF THIS.
 PLEASE SEE FBC FOR REQUIRED SYSTEMS AND NFPA72 FOR
 MINIMUM INSTALLATIONS.
 PLEASE SEE FBC 11-4.28.1,2 AND .3.
  
 5) NOTE: PLEASE SUBMIT PLANS SHOWING COMPLETE EGRESS
 LIGHTING AND EXIT LIGHTING REQUIREMENTS PER NFPA-101
 2006 EDITION, 7.8, 7.9, FBC 1016, NEC 700.16,700.12F.
 BATHROOMS DO NOT SHOW ANY LIGHTING FOR EMERGENCY
 EGRESS. IS IT NEW OR EXISTING?
  
 6) NOTE: PLEASE COORDINATE RISER AND PANELS.
 PANEL B SHOWN AS 250AMP YET RISER INDICATES 225AMP.
 215.5,230,240,310 GIVEN IN GENERAL.
 FBC 106.1.1, 106.1.2, 106.5 FOR CLARITY, COORDINATION
 OF RECORD PLANS.
  
 7) NOTE: PLEASE SEE NEC 220.43 FOR TRACK LIGHTING AND
 SHOW WINDOW LOADS WHICH ARE REQUIRED TO BE SHOWN.
  
 8) NOTE: THE PLANS STATES THAT THE CONTRACTOR SHALL
 REMOVE ALL OLD WIRING WHICH IS NO LONGER IN USE WHEN
 ACCESSIBILITY IS IMPAIRED. PLEASE SEE NEC CHAPTER 8,
 800.3C,
  
 *** ALL LOW VOLTAGE WORK SHALL BE UNDER SEPARATE
 PERMITS.
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-08-24 Cont ID  
Sent By mcarsill Date 2009-08-24 Time 08:10 Rev Time 0.00
Received By mcarsill Date 2009-08-24 Time 08:10 Sent To  
Notes
2009-08-24 09:10:39*****FIRE-STAMPED*****
  
 BASED UPON THE PLANS BEING REVIEWED AND APPROVED BY
 BATTALION CHIEF/FIRE MARSHAL MIKE CARSILLO, PLAN SHEETS
 A-1, A-2, E-1, AND THE THREE HOOD SYSTEM DRAWINGS WERE
 STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-07-27 Cont ID  
Sent By mcarsill Date 2009-07-27 Time 16:16 Rev Time 0.00
Received By mcarsill Date 2009-07-27 Time 16:07 Sent To  
Notes
2009-07-27 16:16:29308 CLEMATIS STREET
 DEMOLITION AND INTERIOR RENOVATIONS. NEW KITCHEN AND
 DINING ROOM
  
 1. DEMOLITION, CONSTRUCTION, AND RENOVATION TO COMPLY
 WITH NFPA 241.
  
 2. DEBRIS IS TO BE REMOVED FROM THE SITE DAILY.
  
 3. EXITS ARE TO REMAIN CLEAR AND ACCESSIBLE.
  
 4. WALK-IN COOLERS AND FREEEZERS TO BE FIRE SPRINKLER
 PROTECTED.
  
 5. THE ELECTRICAL ROOM DOOR APPEARS TO DECREASE THE
 EXIT CORRIDOR BY HALF WHEN OPENED.
  
 6. NEW INTERIOR WALLS SHALL NOT INTERFERE WITH THE
 OPERATION OF ANY FIRE SPRINKLER HEADS.
  
 7. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 8. PLEASE INDICATE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR HANDRAILS AT TYPICAL STEP DETAIL.
  
 9. NO FIRE ALARM STROBES SHOWN IN RESTROOMS.
  
 10. SEPARATE PLANS AND PERMITS REQUIRED FOR ANY HOOD,
 DUCT, AND FIRE SUPPRESSION SYSTEM.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2009-08-17 Cont ID  
Sent By kstevens Date 2009-08-17 Time 16:11 Rev Time 0.00
Received By kstevens Date 2009-08-14 Time 17:11 Sent To  
Notes
2009-08-17 16:13:01SEPARATE GAS PERMIT REQUIRED.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2009-07-02 Cont ID  
Sent By kstevens Date 2009-07-02 Time 14:07 Rev Time 0.00
Received By kstevens Date 2009-07-02 Time 14:07 Sent To  
Notes
2009-07-02 14:09:52DENIED
 REFERENCE:
 FBC-2007 FUEL GAS
  
 A. A SEPARATE GAS PERMIT IS REQUIRED. PLEASE SUBMIT THE
 REQUIRED INFORMATION FOR THE PERMIT:
  
 1. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2007 FUEL
 GAS CODE SECTION 304 & RESIDENTIAL CODE SECTION G2407.
 -- REQUIRED FOR THE WATER HEATER.
  
 2. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2007 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2007 FUEL GAS CODE SEC 402.2 & RESIDENTIAL CODE
 SEC. G2413.2.
  
 B. SHT P-2 NATURAL GAS RISER DIAGRAM. PIPE SIZE TO ITEM
 10 SHALL BE 1-1/2" (FOR 455,000 BTU'S AT 80') AND THE
 STUB OUT FOR ITEM 10 IS REQUIRED TO BE 1-1/4" UP TO AND
 INCLUDING THE SHUT OFF VALVE. TABLE 402.4(2).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-09-15 Cont ID  
Sent By kstevens Date 2009-09-15 Time 15:53 Rev Time 0.00
Received By kstevens Date 2009-09-15 Time 15:53 Sent To  
Notes
2009-09-15 15:53:23SENT TO DVPALMER.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-07-29 Cont ID  
Sent By rregueir Date 2009-07-29 Time 09:23 Rev Time 0.00
Received By rregueir Date 2009-06-11 Time 09:23 Sent To  
Notes
2009-06-11 13:45:46TO C-24

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-08-14 Cont ID  
Sent By rregueir Date 2009-08-14 Time 15:54 Rev Time 0.00
Received By rregueir Date 2009-08-14 Time 15:53 Sent To  
Notes
2009-08-14 15:53:59PROVIDE TRUSS CALCS TO DEMONSTRATE GRAVITY LOADS FOR
 REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-07-29 Cont ID  
Sent By rregueir Date 2009-07-29 Time 09:21 Rev Time 0.00
Received By rregueir Date 2009-07-29 Time 08:56 Sent To  
Notes
2009-07-29 09:21:54REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. NEED PERMIT APPLICATION FROM APPROPRIATELY LICENSED
 CONTRACTOR FOR THE PROPOSED SCOPE OF WORK (KITCHEN HOOD
 AND VENTILATION SYSTEM). ALSO, SEPARATE PLANS AND
 PERMIT APPLICATION REQUIRED FOR HOOD SUPPRESSION SYSTEM
 IN ACCORDANCE WITH FBC-M 509.1.
  
 2. EXHAUST OUTLETS SHALL BE LOCATED NOT LESS THAN 10
 FEET HORIZONTALLY FROM PARTS OF THE SAME OR CONTIGUOUS
 BUILDINGS, ADJACENT BUILDINGS, ADJACENT PROPERTY LINES
 AND AIR INTAKE OPENINGS INTO ANY BUILDING IN ACCORDANCE
 WITH FBC-M 506.3.12.3. PROVIDE PLAN VIEW OF ROOF
 SHOWING LOCATION OF ADJACENT BUILDINGS, OPENINGS AND
 PROPERTY LINES.
  
 3. MAKEUP AIR FAN INTAKE IS SHOWN TO BE LOCATED AT THE
 REAR OF THE BUILDING WHICH DIRECTLY ABUTS AN ALLEY.
 MAKEUP AIR INTAKE OPENING LOCATION SHALL COMPLY WITH
 SECTIONS 401.4 AND 401.4.1 OF THE FBC-M (MINIMUM 10'
 FROM ALLEYS, STREETS OR PARKING LOTS) IN ACCORDANCE
 WITH FBC-M 508.1.
  
 4. DWG #3 SHOWS EXHAUST FAN ON A 7/12 PITCHED ROOF. A
 LEVEL PLATFORM SHALL BE PROVIDED ON EACH SIDE OF THE
 APPLIANCE TO WHICH ACCESS IS REQUIRED FOR SERVICE,
 REPAIR OR MAINTENANCE. THE PLATFORM SHALL BE NOT LESS
 THAN 30 INCHES IN ANY DIMENSION AND SHALL BE PROVIDED
 WITH GUARDS. THE GUARDS SHALL EXTEND NOT LESS THAN 42
 INCHES ABOVE THE PLATFORM, SHALL BE CONSTRUCTED SO AS
 TO PREVENT THE PASSAGE OF A 21-INCH-DIAMETER SPHERE AND
 SHALL COMPLY WITH THE LOADING REQUIREMENTS FOR GUARDS
 SPECIFIED IN THE FLORIDA BUILDING CODE, BUILDING IN
 ACCORDANCE WITH FBC-M 306.5.1.
  
 5. A RECEPTACLE OUTLET SHALL BE PROVIDED AT OR NEAR THE
 EQUIPMENT LOCATION IN ACCORDANCE WITH THE CHAPTER 27 OF
 THE FLORIDA BUILDING CODE, BUILDING AND FBC-M 306.5.2.
  
 6. PROVIDE CERTIFICATION FROM STRUCTURAL ENGINEER THAT
 EXISTING ROOF TRUSSES ARE CAPABLE OF SUPPORTING THE
 ADDITIONAL GRAVITY LOADS OF THE HOOD, SUPPRESSION
 SYSTEM, SUPPLY AND EXHAUST DUCTWORK, SUPPLY AND EXHAUST
 FANS, FIRE WRAP AND OTHER RELATED COMPONENTS IN
 ACCORDANCE WITH FBC-EB 707.4.1.
  
 7. PLEASE PROVIDE PRODUCT APPROVAL FOR WALL LOUVER.
 RULE 9B-72 PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-08-17 Cont ID  
Sent By kstevens Date 2009-08-17 Time 16:11 Rev Time 0.00
Received By kstevens Date 2009-08-14 Time 17:11 Sent To  
Notes
2009-08-17 16:12:42SEPARATE GREASE INTERCEPTOR PERMIT REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2009-07-02 Cont ID  
Sent By kstevens Date 2009-07-02 Time 13:40 Rev Time 0.00
Received By kstevens Date 2009-07-02 Time 13:40 Sent To  
Notes
2009-07-02 14:06:49DENIED
 REFERENCE:
 FBC-2007 W/2009 SUPPLEMENTS
 FBC-2007 PLUMBING
 FBC-2007 FUEL GAS
 FBC-2007 CHAPTER 1 ADMIN
 CITY WPB MUNICIPAL CODE
  
 1. SHT C-1 PROJECT DATA INDICATES FBC-2004 W/2006
 AMENDMENTS. ALL APPLICATIONS FOR PERMIT SUBMITTED ON OR
 AFTER MARCH 1, 2009 SHALL BE DESIGNED TO THE FBC-2007
 WITH 2009 SUPPLEMENTS. PLEASE CORRECT TO THE CORRECT
 CODE CYCLE. SECTION 110.1.2(7).
  
 2. SHT A-1 INDICATES 3 "WHS" TO BE ADDED. THESE ARE NOT
 SHOWN ON OTHER SHEETS. PLEASE CLARIFY. HAND WRITTEN
 INFORMATION IS NOT APPROVED ON SIGNED, SEALED, DATED
 PLANS. A REVISION IS REQUIRED FOR NEW INFORMATION ADDED
 TO THE PLANS. SECTION 106.1.3. THE EXISTING SHEET A-1
 WITH THE FOOD SERVICE APPROVAL STAMP CAN BE RESUBMITTED
 IN THE PLANS AS A REFERENCE SHEET ONLY. -- IF THE WHS'S
 ARE TO BE INSTALLED, THEN THE PLUMBING PLANS SHALL
 REFLECT THE INSTALLATION.
  
 3. A GREASE INTERCEPTOR IS INDICATED. THE GREASE
 INTERCEPTOR SHALL BE APPROVED BY THE UTILITY DEPT.
 INDUSTRIAL PRETREATMENT, ENVIRONMENTAL COMPLIANCE.
 PLEASE CONTACT HOLLY MCGRATH, LABORATORY SUPERVISOR,
 (561) 822-2271, (FAX) (561) 822-2279, OR E-MAIL
 [email protected]. A WRITTEN DETERMINATION OR E-MAIL OF
 APPROVAL IS REQUIRED FOR OUR FILES. ARTICLE III SECTION
 90-124(7) & SECTION 1003.2.
  
 4. SHTS P-1 & P-2. THE JANITOR SINK SHALL DISCHARGE
 THROUGH THE GREASE INTERCEPTOR. SECTION 1003.1.
  
 5. THE DISHWASHER IS PROHIBITED FROM DRAINING INTO THE
 GREASE LINE AND SHALL CONNECT TO THE SANITARY LINE.
 ARTICLE III SECTION 90-124(7)(B).
  
 6. IF THERE IS A FOOD WASTE GRINDER CONNECTING TO THE
 GREASE INTERCEPTOR, THEN A SOLIDS INTERCEPTOR IS
 REQUIRED. SECTION 1003.3.2.
  
 7. GREASE INTERCEPTORS SHALL BE EQUIPPED WITH DEVICES
 TO CONTROL THE RATE OF WATER FLOW SO THAT THE WATER
 FLOW DOES NOT EXCEED THE RATED FLOW. SECTION
 1003.3.4.2.
  
 8. INFORMATIONAL: A SEPARATE GREASE INTERCEPTOR PERMIT
 IS REQUIRED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2009-06-18 Cont ID  
Sent By aaponte Date 2009-06-18 Time 15:49 Rev Time 0.00
Received By aaponte Date 2009-06-18 Time 15:49 Sent To  
Notes
2009-06-18 15:50:07INTERIOR WORK ONLY NOT AFFECTING FACADE.