Plan Review Details - Permit 09060212
Plan Review Stops For Permit 09060212
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-06-17 Cont ID  
Sent By jgomez Date 2009-06-17 Time 16:55 Rev Time 0.00
Received By jgomez Date 2009-06-17 Time 16:55 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-06-12 Cont ID  
Sent By jgomez Date 2009-06-12 Time 10:10 Rev Time 0.00
Received By jgomez Date 2009-06-12 Time 10:10 Sent To PC
Notes
2009-06-12 10:18:51RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW 2ND
 CHECKLIST.
 REVIEW UNDER 2007 FL. RESIDENTIAL CODE W/ 2009
 REVISIONS.
  
 1- CLEARLY MARK ON FLAT ROOF NOA 07-0730.03 SUBMITTED
 WHICH BASE SHEET FASTENING OPTION IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH DESIGN PRESSURES OF
 SEC. R301. (REPEAT COMMENT. NOA SUBMITTED DOESN'T
 IDENTIFY FASTENING OPTION).
  
 2- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7. (REPEAT COMMENT. CALCULATIONS WERE NOT
 SUBMITTED).
  
 ***NOTE: I EXPLAINED TO MARK ON 6/10/09 THAT RAS 117
 CALCULATIONS ARE ALWAYS REQUIRED. ONLY WHEN NOA
 REQUIRES RAS 117 CALCULATIONS TO BE SIGNED AND SEALED,
 THEN THEY NEED TO BE SIGNED AND SEALED. OTHERWISE,
 CALCULATIONS OR PRESCRIPTIVE METHOD ON CONTRACTOR'S
 LETTERHEAD ARE ACCEPTABLE. I DIDN'T TELL MARK THAT HE
 HAS TO USE A TAMKO PRODUCT APPROVAL AS COMMENTED ON THE
 RE-SUBMITTAL FORM. CONTRACTOR IS FREE TO SELECT ANY
 PRODUCT HE/SHE WANTS TO USE. WE DON'T REQUEST ANY
 SPECIFIC PRODUCT APPROVAL. WE ONLY ENFORCE WHAT THE
 PRODUCT APPROVAL REQUIRES.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-06-10 Cont ID  
Sent By jgomez Date 2009-06-10 Time 09:55 Rev Time 0.00
Received By jgomez Date 2009-06-10 Time 09:55 Sent To PC
Notes
2009-06-10 10:01:39RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER 2007 FLORIDA RESIDENTIAL CODE WITH 2009
 REVISIONS.
  
 1- CLEARLY MARK ON NOA 09-0224.01 SUBMITTED WHICH BASE
 SHEET FASTENING OPTION ON SELECTED APPROVED ASSEMBLY IS
 GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 CALCULATED DESIGN PRESSURES OF SEC. R301 OF 2007
 FLORIDA RESIDENTIAL CODE.
  
 2- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT
 PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL
 LIMITATION #7. SEE NOA SUBMITTED.
  
 3- RAS 117 CALCULATIONS NEED TO BE SIGNED AND SEALED AS
 REQUIRED BY GENERAL LIMITATION #7 ON SHEET 31 OF NOA
 09-0224.01 SUBMITTED.
 ***NOTE: DESIGN PROFESSIONAL DOING THE CALCULATIONS TO
 TAKE INTO CONSIDERATION THAT ACCORDING TO THE 2009
 REVISIONS TO SEC. R301 OF 2007 FLORIDA RESIDENTIAL CODE
 THIS BUILDING IS LOCATED ON EXPOSURE "C".
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-06-10 Cont ID  
Sent By jgomez Date 2009-06-10 Time 10:01 Rev Time 0.00
Received By jgomez Date 2009-06-10 Time 09:55 Sent To  
Notes
***NONE***