Plan Review Details - Permit 09060193
Plan Review Stops For Permit 09060193
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-10-13 Cont ID  
Sent By rmcdouga Date 2009-10-13 Time 16:42 Rev Time 0.00
Received By rmcdouga Date 2009-10-13 Time 16:41 Sent To  
Notes
2009-10-13 16:45:03REVISED RAS 117 CALCULATIONS AND PRODUCT APPROVAL
 DRAWING NO. 08-160 FOR THE COLONIAL SHUTTERS WERE
 SUBMITTED AS REQUESTED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2009-09-15 Cont ID  
Sent By rmcdouga Date 2009-09-15 Time 16:32 Rev Time 0.00
Received By rmcdouga Date 2009-09-15 Time 16:31 Sent To  
Notes
2009-09-15 16:37:20REVISIONS REQUIRED TO BE SUBMITTED AND APPROVED PRIOR
 TO INSTALLATION
  
 1) THE RAS 117 CALCULATIONS FROM THE ARCHITECT THAT
 WERE SUBMITTED ARE NOT CORRECT. SUBMIT TWO SETS OF
 CORRECTED RAS 117 CALCULATIONS THAT HAVE BEEN SIGNED
 AND SEALED BY THE ARCHITECT.
  
 2) SUBMIT TWO COPIES OF THE INSTALLATION DRAWING NO.
 08-160 FOR THE STORM SHUTTERS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2009-08-12 Cont ID  
Sent By rmcdouga Date 2009-08-12 Time 11:47 Rev Time 0.00
Received By rmcdouga Date 2009-08-12 Time 11:47 Sent To  
Notes
2009-08-12 13:09:222007 FBC W/2009 SUPPLEMENTS
 ADDITION
  
 DENIED BY BUILDING
  
 1) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION. 233-5025
  
 2) PLEASE REVISE THE CODE INFORMATION ON THE PLANS TO
 THE 2007 FBC W/2009 SUPPLEMENT. THIS IS THE CODE
 EDITION THAT APPLIES TO THIS PROJECT. SEE UNDER SCOPE
 OF WORK ON SHEET A01.
  
 3) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE ROOF
 COVERING MATERIALS ( SLOPED AND FLAT), SINGLE GLAZED
 OUTSWING DOOR AND FRENCH DOORS AS REQUIRED BY DCA RULE
 9B-72.
 NOTE: ON THE FLAT ROOF PRODUCT APPROVAL SPECIFY THE
 APPROVED SYSTEM AND FASTENING OPTION THAT WILL BE USED
 AND ENHANCED FASTENING REQUIREMENTS IF REQUIRED BY
 LIMITATION #7 ON THE NOA.
  
 4) THE PRODUCT APPROVALS SUBMITTED FOR THE GAF ROOF
 SHINGLES ARE FOR THE 2004 CODE AND ONLY THE FLORIDA
 COVER SHEETS WERE SUBMITTED. SUBMIT 2 COPIES OF PRODUCT
 APPROVALS FOR THE 2007 FBC INCLUDE THE EVALUATIONS OR
 NOAS. SEE FL 10124-R1.
  
 5) THE PRODUCT APPROVALS SUBMITTED FOR THE FIRESTONE
 MODIFIED ROOF SYSTEM IS FOR THE 2004 FBC. SUBMIT TWO
 COPIES FOR THE 2007 FBC INCLUDING TWO COPIES OF THE
 NOA. ONLY ONE COPY OF THE NOA WAS SUBMITTED AND IT HAS
 BEEN REVISED BY NOA 08-0118.07. SPECIFY THE ASSEMBLY
 THAT WILL BE INSTALLED AND PROVIDE RAS117 CALCULATIONS
 FOR ENHANCED FASTENING.
  
 6) THE PLANS SPECIFY RECONDITIONED DOORS AND WINDOWS
 INSTALLED INTO NEW OPENINGS. ALL EXTERIOR WINDOWS AND
 DOORS ARE CONSIDERED COMPONENTS AND CLADDING AND ARE
 REQUIRED TO HAVE PRODUCT APPROVALS OR SITE SPECIFIC
 ENGINEERING BY DCA RULE 9B-72.
  
 7) SUBMIT TWO COPIES OF PRODUCT APPROVALS, KEY PLANS
 AND INSTALLATION SCHEDULES FOR THE STORM PANELS.
 SPECIFY THE MOUNTING TYPE, THE FASTENER TYPE, FASTENER
 SPACING, GLASS SEPARATION, EDGE DISTANCE, ETC. RULE
 9B-72
  
 8) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE
 ADDITION. FBC 13-101.2.2 THE ONES SUBMITTED ARE ON 2004
 FBC FORMS AND ARE NO LONGER ACCEPTABLE. SUBMIT FORMS
 REQUIRED BY THE 2007 FBC ENERGY GLITCH AMENDMENTS.
  
 9) THE ENGINEERING SUBMITTED FOR THE EXISTING STORM
 PANELS IS NOT ACCEPTABLE. SEE DCA RULE 9B-72.
  
 NOTE: A SEPARATE PERMIT IS REQUIRED FOR THE FENCE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-07-08 Cont ID  
Sent By rmcdouga Date 2009-07-08 Time 16:57 Rev Time 0.00
Received By rmcdouga Date 2009-07-08 Time 16:57 Sent To  
Notes
2009-07-08 15:20:202007 FBC W/2009 SUPPLEMENTS
 ADDITION
  
 DENIED BY BUILDING
  
 1) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION. 233-5025
  
 2) PLEASE REVISE THE CODE INFORMATION ON THE PLANS TO
 THE 2007 FBC W/2009 SUPPLEMENT. THIS IS THE CODE
 EDITION THAT APPLIES TO THIS PROJECT.
  
 3) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE ROOF
 COVERING MATERIALS ( SLOPED AND FLAT), SKYLIGHTS AND
 FRENCH DOORS AS REQUIRED BY DCA RULE 9B-72.
 NOTE: ON THE FLAT ROOF PRODUCT APPROVAL SPECIFY THE
 APPROVED SYSTEM AND FASTENING OPTION THAT WILL BE USED
 AND ENHANCED FASTENING REQUIREMENTS IF REQUIRED BY
 LIMITATION #7 ON THE NOA.
  
 4) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR ALL WOOD
 CONNECTORS, STRAPS AND ANCHORS OR SPECIFY THE FL#S ON
 THE PLANS. DCA RULE 9B-72
  
 5) THE PLANS SPECIFY RECONDITIONED DOORS AND WINDOWS
 INSTALLED INTO NEW OPENINGS. ALL EXTERIOR WINDOWS AND
 DOORS ARE CONSIDERED COMPONENTS AND CLADDING AND ARE
 REQUIRED TO HAVE PRODUCT APPROVALS OR SITE SPECIFIC
 ENGINEERING BY DCA RULE 9B-72.
  
 6) PLEASE INDICATE IF THE NEW SHUTTERS ARE DECORATIVE
 OR INTENDED TO PROVIDE IMPACT PROTECTION. IF THEY ARE
 FOR IMPACT PROTECTION, SUBMIT TWO COPIES OF PRODUCT
 APPROVALS, KEY PLANS AND INSTALLATION SCHEDULES.
 SPECIFY THE MOUNTING TYPE, THE FASTENER TYPE, FASTENER
 SPACING, GLASS SEPARATION, EDGE DISTANCE, ETC. RULE
 9B-72
  
 7) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE
 ADDITION. FBC 13-101.2.2
  
 8) SPECIFY THE TYPE OF TERMITE PROTECTION THAT WILL BE
 PROVIDED AS REQUIRED BY FBC R320.
  
 9) SHOW COMPLIANCE WITH FBC R704 INSPECTION FOR
 TERMITES, WHICH REQUIRES NOT LESS THAN 6" CLEARANCE
 BETWEEN EXTERIOR WALL COVERINGS AND FINAL EARTH GRADE
 AND A 4" SPACE ABOVE PATIO AND GARAGE SLABS AND ENTRY
 AREAS. NOTE: R 403.1.4 REQUIRES THE BOTTOM OF FOOTINGS
 TO BE A MINIMUM OF 12" BELOW GRADE. THEREFORE, AN 18"
 DEEP FOOTING IS REQUIRED TO ACHIEVE THE 6" CLEARANCE
 SITED ABOVE.
  
 10) SPECIFY THE TRUSS TO WALL CONNECTORS AND THE WALL
 STUD TO TOP PLATE CONNECTORS. R601.2 A CONTINUOUS LOAD
 PATH IS REQUIRED.
  
 11) THE ROOF NOTES ON A05 AND A06 SPECIFY THE SHEATHING
 FASTENER SPACING AS 4" O.C. AND THE SPACING IS GIVEN AS
 6" O.C. ON A07. PLEASE COORDINATE THE NOTES.
  
 12) SPECIFY THE SIZE AND TYPE OF WOOD THAT WILL BE USED
 FOR THE PORCH COLUMNS ON A08.
  
 13) ON A08 A CB66 CONNECTOR FOR A 6 X 6 WOOD POST IS
 SPECIFIED AT THE COLUMN BASE AND A CC 5-1/4 - 8 FOR A 8
 X 8 WOOD POST IS SPECIFIED FOR THE COLUMN CAP. PLEASE
 CLARIFY.
  
 14) ON A06 THE WOOD BEAM IS SPECIFIED AS (3) 3 X 12. IS
 THIS CORRECT OR SHOULD IT BE (3) 2 X 12 ?
  
 15) ON THE WALL SECTIONS ON A07 AND A08, THE INSULATION
 IS SPECIFIED AS R-11. THE MINIMUM INSULATION FOR 2 X 6
 FRAME WALLS IS R-13. FBC N1102
  
 NOTE: A SEPARATE PERMIT IS REQUIRED FOR THE FENCE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-10-10 Cont ID  
Sent By dpalmer Date 2009-10-10 Time 08:05 Rev Time 0.00
Received By dpalmer Date 2009-10-10 Time 07:55 Sent To  
Notes
2009-10-10 08:06:59REDLINED PLANS AS SHEET WAS SUBMITTED FOR REVISED
 ELECTRICAL ONLY. PREVIOUS SHEETS WHICH CONTAIN PLUMBING
 AND MECHANICAL STAMPS ARE TO BE USED FOR THOSE TRADES.
 NEW SHEET SHOULD BE USED FOR ELECTRICAL ONLY AS THEY
 WERE NOT ROUTED TO M AND P REVIEWS.
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-09-10 Cont ID  
Sent By dpalmer Date 2009-09-10 Time 10:30 Rev Time 0.00
Received By dpalmer Date 2009-09-10 Time 10:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2009-08-10 Cont ID  
Sent By dpalmer Date 2009-08-10 Time 14:58 Rev Time 0.00
Received By dpalmer Date 2009-08-10 Time 14:58 Sent To  
Notes
2009-08-10 14:59:04 
  
 ** DENIED REVIEW **
 2ND REVIEW
  
  
 PLEASE SEE THAT SOME NOTES FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
 SOME NEW NOTES ARE ALSO NOW CREATED BASED ON SOME
 REVISIONS MADE NOT PART OF PREVIOUS PLANS.
 ** PLANS ARE COMING BACK FOR COMMENTS FROM OTHER
 TRADES. PLEASE REVISE AT THIS TIME.
  
 1) NOTE: PLEASE INDICATE THE AIC RATING OF SERVICE
 EQUIPMENT. 110.9
 ALL EQUIPMENT MUST BE RATED FOR THE AVAILABLE FAULT
 CURRENT.
 PREVIOUS NOTES
  
 2) NOTE: PLEASE INDICATE THE REQUIRED ARC FAULT
 PROTECTION FOR ALL OUTLETS. THE PANEL SCHEDULE WAS
 REVISED HOWEVER ONLY INDICATES THE AFCI PROTECTION FOR
 RECEPTACLES. 210.12
 PREVIOUS NOTES
  
 3) NOTE: PLEASE SEE MISSING *EQUIPMENT GROUNDING
 CONDUCTOR* FROM MAIN TO PANEL.
 250.122
  
 4) NOTE: THE GROUNDING ELECTRODE INDICATES ATTACHMENT
 TO GAS LING AS PART OF THE GROUNDING ELECTRODE. THIS IS
 NOT PERMITTED. THE GAS LINE IS BONDED PER 250.104
 HOWEVER NOT PART OF THE GROUNDING ELECTRODE SYSTEM. THE
 NOTE ON THE SAME STATES *OR* FOOTER STEEL. PLEASE SEE
 250.50 AS THE NEW FOOTER STEEL IS REQUIRED. PLEASE CALL
 TO ADJUST NOTES ON RISER.
  
 5) NOTE: PLEASE CIRCUITS 4,6 AND 8,10 ARE
 REVERSED.408.4
  
 6) NOTE: PLANS SHOW SMOKE DETECTORS, PLEASE VERIFY THIS
 AS THESE WOULD BE SMOKE ALARMS. PLEASE ALSO SEE PLANS
 ARE MISSING CARBON MONOXIDE DETECTORS. FS 553.885
  
 7) NOTE: PANEL SHOWN ON PLANS IS SHOWN NOT MEETING
 110.26. COVER IS SHOWN IN THE DIRECTION FACING THE
 COUNTER SPACE IN KITCHEN AREA.
 MUST HAVE CLEAR FLOOR SPACE AND WORKING CLEARANCES.
  
 8) NOTE: PLEASE SEE 210.11C2, 220. 52 AS THE MINIMUM
 LOAD FOR WASHER/LAUNDRY NEEDS TO BE 1500VA.
  
  
 ** PLANS ARE NO LONGER RELEASED PER BUILDING DIRECTOR.
 A TIME WILL NEED TO BE SET UP TO BRING IN NEW REVISIONS
 AND CHANGE OUT SHEETS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-06-19 Cont ID  
Sent By dpalmer Date 2009-06-19 Time 10:54 Rev Time 0.00
Received By dpalmer Date 2009-06-19 Time 10:54 Sent To  
Notes
2009-06-19 10:54:50 
 ** DENIED PLANS *
  
 1) NOTE: PLANS SUBMITTED STATE THE 2004 FBC W/ 2006
 REVISIONS. PLEASE KNOW THAT ALL PLANS SUBMITTED ON OR
 AFTER MARCH 1ST 2009 SHALL BE UNDER THE DESIGN OF THE
 2007 FBC W/ 2009 AMENDMENTS.
 THE PLANS NEED TO STATE THE FOLLOWING CODES AT A
 MINIMUM FOR THIS REVIEWER AS APPLICABLE TO ELECTRICAL
 PLANS.
 2007 FBC W/2009 REVISION
 2005 NFPA-70 ( NEC)
 2002 NFPA-72
  
  
 2) NOTE: PLEASE SEE FBC R313.1, NFPA-72 2002. PROVIDE A
 COMPLETE LAYOUT OF NEW OR EXISTING SMOKE ALARMS MEETING
 THE CURRENT NFPA-72 11.5.1.1, 11.8.3.
 THE PLANS DO NOT SHOW ANY NEW OR EXISTING FOR ADDITION
 OR REMODEL.
 PLEASE BE SURE TO ALSO SEE NEC 210.12 FOR ARC FAULT
 PROTECTION REQUIRED. 210.12 SEE OTHER NOTES.
  
 3) NOTE: PLEASE CORRELATE ALL CIRCUITING ON PLANS WITH
 THE SUBMITTED PANEL SCHEDULE. THERE ARE NUMEROUS
 INCONSISTENCIES ON PLANS WITH THE SUBMITTED PANEL
 SCHEDULE. BELOW WILL BE SOME EXAMPLES.
  
 FOR EXAMPLE: ALL CIRCUITS ARE NOTES AS *C* WHEN THE
 PANEL IS PANEL *A*.
 FOR EXAMPLE: THE OUTSIDE CONDENSING UNIT IS SHOWN AS AN
 AIR HANDLER AND THE CIRCUIT WHICH IS SHOWN AS C 12-14.
 FOR EXAMPLE: PLEASE SEE THE UNIDENTIFIED EQUIPMENT IN
 THE UTILITY CLOSET WHICH IS LABELED CIRCUIT C-5,7
 HOWEVER IF YOU LOOK AT THE PANEL SCHEDULE FOR THIS SAME
 ITEM IT IS THE SMALL APPLIANCE AND DISHWASHER/DISPOSAL
 CIRCUIT. THIS IS NOT PERMITTED OR POSSIBLE. SMALL
 APPLIANCE CIRCUITS ARE NOT PERMITTED TO FEED ANY OTHER
 AREAS. 210.52B1
 THIS SAME CIRCUIT C 5.7 IS ALSO SHOWN IN MORE THAN ONE
 LOCATION.
 FOR EXAMPLE: CIRCUIT C-32 IS SHOWN AS FEEDING LANDSCAPE
 LIGHTING HOWEVER PER THE PLANS THIS IS LIGHTING LOCATED
 INSIDE THE HOUSE.
  
 ** THIS IS ONLY A FEW EXAMPLES; PLEASE BE SURE TO SEE
 THE REST OF THE COMMENTS AND COORDINATE ALL.
 408..4,250.52,240.4,310.16 ETC
  
 4) NOTE: PLEASE SUBMIT LOAD CALCULATIONS IN ACCORDANCE
 WITH THE MINIMUM CODE FROM THE NEC. THERE ARE ITEMS
 WHICH ARE MISSING COMPLETELY.
 FOR EXAMPLE: THE DRYER IS SHOWN ON THE PANEL SCHEDULE
 IS NOT IN THE LOAD CALCULATIONS. PLEASE SEE 220.54 FOR
 MINIMUM LOAD REQUIRED TO BE FIGURED.
 FOR EXAMPLE: AS THERE APPEARS TO BE A WATER HEATER ON
 PLANS IT IS NOT CLEAR IF IT IS GAS OR ELECTRICAL.
 PLEASE SEE 4220.13 OF THE 2005 NEC AS THE WATER HEATER
 IS NOW CONSIDERED A CONTINUOUS IF ELECTRICAL. PLEASE
 ADJUST LOAD CALCULATIONS ACCORDINGLY. 422.13
 FOR EXAMPLE; THE AHU HEAT NEEDS TO BE COORDINATED. SEE
 NOTE #11 BELOW.
 * PLEASE SEE NEC 220. THERE ARE OTHER ITEMS SUCH AS THE
 ONE OR MORE *SMALL APPLIANCE CIRCUITS*, DEDICATED
 CIRCUITS ETC.
 220.53, 220.52 ETC
  
 5) NOTE: PLEASE SEE FS 553.885 FOR REQUIRED CARBON
 MONOXIDE DETECTOR WHICH IS REQUIRED FOR ANY HOUSE WITH
 ATTACHED GARAGE OR GAS APPLIANCES. IT IS NOT KNOWN AT
 THIS TIME IF THERE ARE ANY GAS APPLIANCES AT THIS
 LOCATION.
 BASED ON THE FACT THE PANEL SCHEDULE DOES NOT SHOW ANY
 STOVE, RANGE, OR WATER HEATER IT COULD BE ASSUMED THERE
 IS GAS APPLIANCES FOR THESE????
  
 6) NOTE: PLEASE SEE 210.52F, 210.11C2 AND 220.52 FOR
 MISSING REQUIRED WASHER/LAUNDRY CIRCUIT AND LOADS.
  
 7) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.53 FOR
 MISSING DINING ROOM CIRCUIT, LOAD ETC.
  
 8) NOTE: PLEASE LIST ALL OF THE REQUIRED ARC FAULT
 CIRCUITS PER 210.12, 408.4
  
 9) NOTE: PLEASE PROVIDE MORE INFORMATION ON THE
 LOCATION OF THE ELECTRICAL PANEL. THIS SEEMS TO BE SOME
 KIND OF STORAGE AREA. PLEASE SEE 240.24D, 110.26 FOR
 LOCATION IN STORAGE AREAS NOT PERMITTED AND WORKING
 CLEARANCES REQUIRED.
  
 10) NOTE: PLEASE IDENTIFY ALL EQUIPMENT AND APPLIANCES
 ON PLANS. AS NOTED ABOVE THE CIRCUIT #5,7 GOES TO
 SOMETHING HOWEVER IT CAN NOT BE DETERMINED WHAT IT IS.
 ALSO THE AHU NEEDS TO BE SHOWN. THERE ARE TWO SQUARE
 BOXES ON PLANS BOTH SHOWING CIRCUITS C-5,7??
 BASED ON THE PLANS THERE IS A SQUARE INSIDE THE CLOSET
 WHICH MAY OR MAY NOT BE THE AHU? PLEASE SEE
 440.11,440.12, 440.14 FOR REQUIRED DISCONNECT TO BE
 SHOWN.
  
 11) NOTE: PLEASE COORDINATE THE AHU WITH THE LOAD,
 CONDUCTORS AND OVER CURRENT PROTECTION. PLEASE SEE
 424.3B, 240.4,310.16, 408.4 ETC
 THE LOAD CALCULATIONS INDICATES THE UNIT AS 7.5 KW
 HOWEVER THE PANEL SCHEDULE SHOWS #10 AWG AND A 25AMP
 BREAKER WHICH DOES NOT MEET THE MINIMUM FOR CODE
 COMPLIANCE. THE OTHER AHU IS SHOWN WITH A 2-POLE 20AMP
 BREAKER AND #12 AWG WHICH IS ALSO NOT PERMITTED FOR
 WHAT APPEARS TO BE A 5KW UNIT.
 THERE ARE SEVERAL ITEMS WHICH NEED TO BE IDENTIFIED AND
 CORRECTED FOR MINIMUM CODE COMPLIANCE.
  
 12) NOTE: PLEASE SEE 110.9 FOR THE AIC RATING WHICH
 NEEDS TO BE SHOWN FOR ALL SERVICE EQUIPMENT.
  
 13) NOTE: PLEASE SEE 250.66 FOR THE MINIMUM SIZE OF THE
 GROUNDING ELECTRODE CONDUCTOR. THE RISER SHOWS #6 WHICH
 DOES NOT MEET MINIMUM CODE.
  
 14) NOTE: PLEASE INCLUDE THE NEW FOOTER STEEL AS
 REQUIRED PER 250.50
  
 15) NOTE: PLEASE SEE 250.104 FOR OTHER METAL PIPING
 WHICH IS REQUIRED TO BE BONDED. ( GAS PIPING??)
  
 16) NOTE: PLEASE SEE PANEL SCHEDULE AS BOTH THE GARBAGE
 DISPOSAL AND THE DISHWASHER IS SHOWN ON THE SAME 1-POLE
 20AMP CIRCUIT WHICH IS NOT PERMITTED. PLEASE SEE
 220.50,430.148, 220.82,220.53 ETC AS THE LOADS ON A
 DISHWASHER IS TYPICALLY AT LEAST 1200VA AND LOADS ON
 DISPOSAL IS GREATER THAN 1/4 HP. BASED ON MINIMUM CODE
 SECTIONS, THESE WOULD BE REQUIRED TO BE ON DEDICATED
 CIRCUITS. PLEASE CONFIRM THAT THESE ARE NOT ACTUALLY ON
 THE SAME CIRCUIT AS THIS IS A SAFETY AND FIRE HAZARD.
 PLEASE ALSO SEE 210.4B FOR DISCONNECTION OF ALL DEVICES
 WITH MULTI-WIRE BRANCH CIRCUITS ON THE SAME YOKE.
  
 17) NOTE: PLEASE SEE 240.4, 310.16 AS THE PANEL
 INDICATES A 30AMP BREAKER ON #12 AWG FOR DRYER.
  
 18) NOTE: PLEASE SEE FBC 13-606 AB .1.2.4 AS ALL NEW
 RECESSED LIGHTING FIXTURES SHALL MEET MINIMUM ENERGY
 CODE REQUIREMENTS PLEASE PLACE NOTE ON PLANS.
  
 19) NOTE: PLEASE SEE 210.52 AS TWO OF THE WALLS IN
 MASTER BEDROOM WILL REQUIRE AN ADDITIONAL RECEPTACLE
 BASED ON THE 3/16 SCALE PROVIDED. IF OVER 12FT THEN
 MORE THAN THE TWO SHOWN WILL BE REQUIRED.
  
 20) NOTE: PLEASE COMPLETE RISER. THERE ARE NO
 CONDUCTORS SHOWN FROM METER TO THE REST OF THE SERVICE.
 215.5, 310.16,310.15B6, 250.110,250.6,250.122 ETC
 FBC 106.1.1,106.1.2 FOR ADDITIONAL INFORMATION AND
 CLARITY.
  
 21) NOTE: PLEASE GO OVER THE CIRCUITING FOR THE MASTER
 BEDROOM. AS ALL RECEPTACLES, FANS, RECESSED LIGHTS ETC
 ARE SHOWN ON THE SAME CIRCUIT?
 PLEASE SEE 220.12 FOR LIGHTING LOADS. THERE IS OVER 11
 AMPS OF LOAD JUST WITH THE FAN/FAN LTS AND RECESSED
 LIGHTS ALONE.
  
 22) NOTE: PLEASE SEE 210.8A2 AS ALL RECEPTACLES IN
 UTILITY ROOMS ARE REQUIRED TO BE GFI OR GFI PROTECTED.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2009-07-21 Cont ID  
Sent By ssherman Date 2009-07-21 Time 17:07 Rev Time 0.00
Received By ssherman Date 2009-07-21 Time 17:07 Sent To  
Notes
2009-07-21 17:07:39HISTORICAL APPROVAL PER JILLIAN PAPA

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2009-06-09 Cont ID  
Sent By mmiller Date 2009-06-09 Time 11:14 Rev Time 0.00
Received By mmiller Date 2009-06-09 Time 11:14 Sent To  
Notes
2009-06-09 11:14:22OK PER JILLAIN PAPA MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-09-30 Cont ID  
Sent By rmcdouga Date 2009-09-29 Time 09:34 Rev Time 0.00
Received By rmcdouga Date 2009-09-29 Time 09:34 Sent To  
Notes
2009-09-30 09:34:20SENT TO R2

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-09-02 Cont ID  
Sent By kstevens Date 2009-09-02 Time 15:16 Rev Time 0.00
Received By kstevens Date 2009-09-02 Time 15:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-07-22 Cont ID  
Sent By shill Date 2009-07-22 Time 17:33 Rev Time 0.00
Received By shill Date 2009-07-22 Time 17:33 Sent To  
Notes
2009-07-22 17:33:27R 22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2009-07-08 Cont ID  
Sent By rmcdouga Date 2009-07-08 Time 16:57 Rev Time 0.00
Received By rmcdouga Date 2009-06-11 Time 13:13 Sent To  
Notes
2009-06-11 13:13:45TO R-3

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2009-09-21 Cont ID  
Sent By rmcdouga Date 2009-09-21 Time 16:47 Rev Time 0.00
Received By rmcdouga Date 2009-09-21 Time 16:47 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2009-09-15 Cont ID  
Sent By rmcdouga Date 2009-09-15 Time 14:51 Rev Time 0.00
Received By rmcdouga Date 2009-09-15 Time 14:51 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 2 Status P Date 2009-09-08 Cont ID  
Sent By rkussner Date 2009-09-08 Time 12:11 Rev Time 0.00
Received By rkussner Date 2009-09-08 Time 12:11 Sent To  
Notes
2009-09-08 12:12:42***LANDSCAPE REVIEW PASSED WITH PROVISO***
  
 1. PROVIDE SOD AND IRRIGQTION IN RIGHTS-OF-WAY.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2009-08-03 Cont ID  
Sent By rkussner Date 2009-08-03 Time 12:48 Rev Time 0.00
Received By rkussner Date 2009-08-03 Time 12:48 Sent To  
Notes
2009-08-03 12:55:46***LANDSCAPE REVIEW FAILED***
  
 PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT.
  
 1. SUBMIT A LANDSCAPE PLAN WITH THE TABULATION
 NECESSARY FOR THE EVALUATION OF COMPLIANCE WITH ARTICLE
 XIV OF THE ZONING AND LAND DEVELOPMENT REGULATIONS,
 INCLUDING THE XERISCAPE DESIGN OPTIONS.
  
 2. ALL OF THE ELEMENTS LISTED IN SECTION 94-448 (D)
 SHALL BE PART OF THE LANDSCAPE PLAN.
  
 3, SUBMIT A COST ESTIMATE THAT INCLUDES THE TOTAL COST
 OF ALL LANDSCAPE MATERIALS AND LABOR, BROKEN DOWN INTO
 UNIT COST.
  
 4. SUBMIT AN IRRGATION PLAN WITH THE IRRIGATION PERMIT
 APPLICATION. THERE SHALL BE 120% IRRIGATION COVERAGE TO
 ALL LANDSCAPED AREAS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (5651) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-09-15 Cont ID  
Sent By rmcdouga Date 2009-09-15 Time 08:24 Rev Time 0.00
Received By rmcdouga Date 2009-09-15 Time 08:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2009-08-12 Cont ID  
Sent By rmcdouga Date 2009-08-12 Time 14:45 Rev Time 0.00
Received By rmcdouga Date 2009-08-12 Time 14:45 Sent To  
Notes
2009-08-12 15:16:452007 FBC W/2009 REVISIONS
 MECHANICAL
  
 DENIED
  
 1) SHEET A09 OF THE NEW PLANS INDICATE A GAS APPLIANCE
 IN THE CLOSET OFF THE MASTER BATHROOM THAT WAS NOT
 SHOWN ON THE FIRST PLANS. PLEASE SHOW HOW THIS WILL
 COMPLY WITH FBC R M1701.4, M1702 AND M1703.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-07-08 Cont ID  
Sent By rmcdouga Date 2009-07-08 Time 11:52 Rev Time 0.00
Received By rmcdouga Date 2009-07-08 Time 11:52 Sent To  
Notes
2009-07-08 13:53:182007 FBC W/2009 AMENDMENTS
 ADDITION
  
 DENIED BY MECHANICAL
  
 1) RETURN AIR SHALL NOT BE TAKEN FROM A BATHROOM. FBC
 RESIDENTIAL M1602.2.
  
 2) THE PLAN SHOWS A SUPPLY DUCT FROM A GRILL IN THE
 MASTER BEDROOM TO THE SUPPLY DUCT IN THE NEW BATHROOM.
 IS THE GRILL IN THE BEDROOM EXISTING. IF SO, PLEASE
 LABEL THE GRILL AS EXISTING. ALSO THERE IS NO NEED TO
 SHOW THE DUCT RUNNING FROM THE BEDROOM GRILL TO THE
 BATHROOM GRILL. JUST SHOW THE NEW SUPPLY GRILL IN THE
 BATHROOM WITH THE NOTE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2009-09-15 Cont ID  
Sent By rmcdouga Date 2009-09-15 Time 08:25 Rev Time 0.00
Received By rmcdouga Date 2009-09-15 Time 08:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-08-12 Cont ID  
Sent By rmcdouga Date 2009-08-12 Time 14:46 Rev Time 0.00
Received By rmcdouga Date 2009-08-12 Time 14:46 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-07-08 Cont ID  
Sent By rmcdouga Date 2009-07-08 Time 07:56 Rev Time 0.00
Received By rmcdouga Date 2009-07-08 Time 07:56 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2009-09-04 Cont ID  
Sent By mcruz Date 2009-09-04 Time 17:07 Rev Time 0.00
Received By mcruz Date 2009-09-04 Time 17:01 Sent To L
Notes
2009-09-04 17:02:31PASSED W/PROVISO: LANDSCAPE COMMENTS SHALL BE ADDRESSED
 PRIOR TO FINAL CO.
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2009-08-03 Cont ID  
Sent By mcruz Date 2009-08-03 Time 14:53 Rev Time 0.00
Received By mcruz Date 2009-08-02 Time 21:25 Sent To  
Notes
2009-08-03 14:53:00PLANNING AND ZONING DEPT: ***ZONING FAILED - 1ST
 RESUB***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PLEASE ADDRESS LANDSCAPE PLANNER COMMENTS.
  
 3. REPEAT COMMENT: INDICATE SETBACK DIMENSIONS FROM
 PROPOSED A/C EQUIPMENT TO ALL PROPERTY LINES. PURSUANT
 THE ZLDR, SECTION 94-305(B)(4): MECHANICAL EQUIPMENT
 MAY NOT PROJECT MORE THAN 4 FEET INTO A REQUIRED
 SETBACK.
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  
 PLACED IN R22

Review Stop Z ZONING
Rev No 1 Status F Date 2009-06-23 Cont ID  
Sent By mcruz Date 2009-06-23 Time 13:34 Rev Time 0.00
Received By mcruz Date 2009-06-23 Time 12:23 Sent To  
Notes
2009-06-23 12:49:28PLANNING AND ZONING DEPT: ***ZONING FAILED***
  
 1. PLEASE PROVIDE ALL RESPONSES IN WRITING.
  
 2. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION
 94-441(C)(2) OF: AS THE VALUE OF THE PROPOSED WORK
 EXCEEDS 50% OF THE STRUCTURE'S VALUE (LISTED AS
 "IMPROVEMENT VALUE" WITH THE P.B.C. PROPERTY
 APPRAISER'S OFFICE), LANDSCAPING SHALL BE IN COMPLIANCE
 WITH ALL APPLICABLE REGULATIONS FOUND IN ARTICLE XIV OF
 THE ZLDR.
  
 PLEASE SUBMIT TWO (2) COPIES OF A LANDSCAPE PLAN
 SHOWING COMPLIANCE WITH SECTIONS 94-442 AND 94-445 OF
 THE ZLDR.
  
 3. THE SIDE PROPOSED WEST SIDE SETBACK EXCEEDS THE
 MAXIMUM ALLOWED BY CODE AS THE SUBJECT SITE IS A CORNER
 LOT. PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDR), SECTION 94-74:
 SINGLE FAMILY HIGH DENSITY (SF14) RESIDENTIAL DISTRICT
 - MINIMUM SETBACKS FOR PRINCIPAL BUILDING ARE AS
 FOLLOWS:
  
 A. FRONT: 25 FEET;
  
 B. CORNER: 12.5 FEET; TEN FEET IF LOT IS LESS THAN 60
 FEET WIDE;
  
 C. REAR: 15 FEET OR TEN PERCENT OF DEPTH, WHICHEVER IS
 LESS;
  
 D. SIDE: FIVE FEET MINIMUM, 15 FEET TOTAL.
  
 4. THE ELECTRICAL/MECHANICAL FLOOR PLAN INDICATES THAT
 THE A/C UNIT WILL BE RELOCATED DEOM THE N BEDROOM WALL
 TO THE E SIDE. PLEASE INDICATE THE SETBACK DIMENSIONS
 FROM THE RELOCATED A/C UNIT TO ALL ADJACENT PROPERTY
 LINES. PURSUANT THE ZLDR, SECTION 94-305(B)(4):
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET
 INTO A REQUIRED SETBACK.
  
 5. PROVIDE THE DIMENSIONS OF THE PROPOSED RELOCATED
 PARKING SPACES. PURSUANT TO THE ZLDR, SECTION
 94-485(C): RETENTION OF REQUIRED OFF-STREET PARKING
 SPACES. REQUIRED OFF-STREET PARKING SPACES SHALL NOT BE
 REPLACED BY ANY OTHER ON-SITE FACILITY UNLESS EQUAL
 PARKING FACILITIES ARE PROVIDED ELSEWHERE. OFF-STREET
 PARKING SPACES EXISTING ON THE EFFECTIVE DATE OF THE
 ORDINANCE FROM WHICH THIS ARTICLE IS DERIVED SHALL NOT
 BE REDUCED TO AN AMOUNT LESS THAN REQUIRED.
  
 PURSUANT TO THE ZLDR, SECTION 94-486. SPECIFIC PARKING
 REQUIREMENTS; LOADING SPACE REQUIREMENTS FOR INDIVIDUAL
 USES. A MINIMUM OF 2 PARKING SPACES ARE REQUIRED FOR
 SINGLE FAMILY DWELLINGS.
 ....
 WHENEVER TWO OR MORE OF THE USES LISTED IN TABLE XV-6
 ARE PRESENT ON THE SAME LOT OR IN THE SAME STRUCTURE,
 THE NUMBER OF PARKING SPACES REQUIRED SHALL BE THE SUM
 OF SPACES CALCULATED FOR EACH INDIVIDUAL USE.
  
 PUSUANT TO THE ZLDR, SECTION 94-485(N): OFF-STREET
 PARKING DIMENSIONS. ALL PARKING SPACES REQUIRED BY THIS
 ARTICLE SHALL BE AT LEAST EIGHT FEET SIX INCHES IN
 WIDTH AND 18 FEET IN LENGTH; SMALL CAR SPACES SHALL BE
 AT LEAST EIGHT FEET IN WIDTH AND 16 FEET IN LENGTH.
 MINIMUM PARKING SPACE AND AISLE DIMENSIONS ARE SET
 FORTH IN FIGURE XV-2 (ATTACHED).
  
 NOTE: THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
 FOR ADDITIONAL INFORMATION, THE ZONING AND LAND
 DEVELOPMENT REGULATIONS MAY BE VIEWED ONLINE AT
 WWW.MUNICODE.COM OR VISIT THE CITY OF WEST PALM BEACH
 PLANNING DEPARTMENT WEBSITE AT
 WWW.CITYOFWPB.COM/PLAN/INDEX.HTM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE DO NOT HESITATE TO
 CONTACT ME.
  
 MAGGIE CRUZ, ASSOCIATE PLANNER
 PLANNING AND ZONING DEPARTMENT
 TEL: (561) 822-1444 OR (561) 805-6720
 E-MAIL: [email protected]
  
 PLACED BACK IN R3
  