| Notes |
| 2009-06-18 11:39:21 | REDLINED MAY NOT USE RISER TO SUPPORT CONDUCTORS. | | | ALSO VIF EQUIPMENT GROUNDING PATH AS RISER SHOWS 3-3/0 | | | IN 1 1/2 CONDUIT. | | | NO EQUIPMENT GROUNDING CONDUCTOR SHOWN. CONNECTORS/ | | | COUPLINGS APPROVED FOR EQUIPMENT GROUNDING PATH OR | | | EQUIPMENT GROUNDING CONDUCTOR REQUIRED. |
|
|
|