Review Stop E ELECTRICAL
Rev No 1 Status P Date 2009-06-18 Cont ID  
Sent By dpalmer Date 2009-06-18 Time 11:28 Rev Time 0.00
Received By dpalmer Date 2009-06-18 Time 11:28 Sent To PC
Notes
2009-06-18 11:39:21REDLINED MAY NOT USE RISER TO SUPPORT CONDUCTORS.
 ALSO VIF EQUIPMENT GROUNDING PATH AS RISER SHOWS 3-3/0
 IN 1 1/2 CONDUIT.
 NO EQUIPMENT GROUNDING CONDUCTOR SHOWN. CONNECTORS/
 COUPLINGS APPROVED FOR EQUIPMENT GROUNDING PATH OR
 EQUIPMENT GROUNDING CONDUCTOR REQUIRED.