Plan Review Details - Permit 09060185
Plan Review Stops For Permit 09060185
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-11-12 Cont ID  
Sent By shill Date 2009-11-12 Time 18:03 Rev Time 0.00
Received By shill Date 2009-11-12 Time 18:03 Sent To  
Notes
2009-11-12 18:04:09ALT MAT'L & METHODS LETTER APPROVED BY DW
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2009-10-21 Cont ID  
Sent By shill Date 2009-10-08 Time 17:28 Rev Time 0.00
Received By shill Date 2009-10-08 Time 17:28 Sent To  
Notes
2009-10-08 17:38:14****PASSED WITH PROVISO****
 ****REQUIRED BEFORE FINAL INSPECTION***
 ****ISSUED AT CONTRACTOR'S RISK****
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. SUBMIT REQUEST THROUGH ALTERNATE MATERIALS &
 METHODS, FBC*104.11. SEE FBC715.3, DEMONSTRATE
 COMPLIANCE WITH FBC TABLE 715.4.
  
 2. REVISE SPRINKLER PERMIT 09080766 TO INCLUDE WATER
 CURTAIN AND SPRINKLER HEAD SPEC SHEETS. SHOP DRAWING
 REVIEW (BY DESIGNER OF RECORD) PRIOR TO REVISION
 SUBMITTAL.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2009-09-24 Cont ID  
Sent By shill Date 2009-09-24 Time 08:54 Rev Time 0.00
Received By shill Date 2009-09-24 Time 08:54 Sent To FIRE
Notes
2009-09-24 08:56:24****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2007
 FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE PROVIDE INFORMATION REGARDING THE WATER
 CURTAIN. IT IS NOT CLEAR HOW THIS WILL WORK PROPERLY AS
 DESIGNED; ISN'T THE WATER TO HIT THE WALL ABOVE THE
 WINDOW AND THEN RUN DOWN THE WINDOW, WITH MULLIONS ON
 THE WINDOW PROHIBITED? A BULKHEAD ABOVE THE DOOR/WINDOW
 HAS BEEN PROPOSED, SO IT IS NOT CLEAR HOW THE WATER
 CURTAIN ON EITHER SIDE WILL WORK. PROVIDE SPECIFICATION
 SHEETS FOR THE SPRINKLER HEADS, DIMENSION FOR THE
 BULKHEAD, AND ANY OTHER INFORMATION REQUIRED TO
 DEMONSTRATE COMPLIANCE WITH FBC715.4. ALSO, PLEASE NOTE
 DISTANCE FROM THE PROPOSED WATER CURTAIN SPRINKLER
 HEADS TO THE EXISTING FIRE SPRINKLERS IN THE CORRIDOR.
 THIS INFORMATION IS TO BE EITHER PREPARED BY THE FIRE
 SPRINKLER ENGINEER OR REVIEWED BY THE FIRE SPRINKLER
 ENGINEER.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2009-07-21 Cont ID  
Sent By shill Date 2009-07-21 Time 21:35 Rev Time 0.00
Received By shill Date 2009-07-21 Time 21:35 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2009-06-23 Cont ID  
Sent By jwitmer Date 2009-06-23 Time 12:33 Rev Time 0.50
Received By jwitmer Date 2009-06-23 Time 12:03 Sent To  
Notes
2009-06-23 12:33:33BUILDING PLAN REVIEW
 PERMIT: 09060185
 ADD: 222 LAKEVIEW AVE SUITE# 110
 CONT: G3 CONSTRUCTION
 TEL: (561)445-3769
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC
 BUILDING WITH 2009 SUPPLEMENTS.
  
 2) SHEET A1.1 INDICATES A NEW TENANT SEPERATION WALL/
 CORRIDOR TO BE 1 HR RATED AS PER 708.1 (7), THE PLANS
 ARE MISSING THE RATING OF THE TENANT ENTRY DOOR# 1 AND
 THE SIDELIGHTS
 SEE A3.1 THE DOOR SCHEDULE IS MISSING OPENING
 PROTECTIVES PER TABLE 715.4.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
 SURVEY:
 WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2009-11-03 Cont ID  
Sent By btrobaug Date 2009-11-03 Time 17:31 Rev Time 0.00
Received By btrobaug Date 2009-11-03 Time 17:01 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2009-07-21 Cont ID  
Sent By dpalmer Date 2009-07-21 Time 18:27 Rev Time 0.00
Received By dpalmer Date 2009-07-21 Time 18:27 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2009-07-03 Cont ID  
Sent By dpalmer Date 2009-07-03 Time 09:30 Rev Time 0.00
Received By dpalmer Date 2009-07-03 Time 09:30 Sent To  
Notes
2009-07-03 09:30:42** DENIED PLANS *
  
 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE
 FOLLOWING MINIMUM CODES.
 PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL
 PLANS.
 2007 FBC W/ 2009 AMENDMENTS.
 2006 NFPA-101 ( PLANS STATE 2007 FOR THIS CODE)
 2002 NFPA-72 (OK)
 2006 NFPA-1
 2005 NFPA-70 ( PLANS STATE 2007) PLEASE BE ADVISED EVEN
 ONCE THE CODE CHANGE GOES INTO AFFECT THE IT WILL BE
 THE 2008 NEC.
  
 PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003
  
  
  
 2) NOTE: THE PANEL AND TRANSFORMER LOCATION NEEDS TO BE
 IDENTIFIED AS ELECTRICAL ROOM. PLEASE ALSO NOTE THAT
 SIGNAGE WILL BE REQUIRED FOR ELECTRICAL ROOM, NO
 STORAGE OR WORDS TO THAT AFFECT.
 110.26, 240.24
  
 3) NOTE: PLEASE INCLUDE ALL DEVICE LOCATIONS, HEIGHTS,
 AND MINIMUM LEVELS PER FBC 11-4.28.1,.2 AND .3.
 THERE ARE SOME DEVICES ON PLANS HOWEVER NO DETAILS OR
 INFORMATION ON SYMBOL LEGEND.
  
 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE 13-415.AB.5. PLANS STATE TO SEE DOCUMENTS
 ATTACHED. THE ATTACHED CALCULATIONS ARE COMCHECK
 SOFTWARE WHICH IS NOT ADOPTED BY THE STATE OF FLORIDA.
 PLEASE SEE 13-400 AS THE ONLY ADOPTED PROGRAM IS
 FLA-COM.
 PLEASE BE SURE THE RESPONSIBLE DESIGN PROFESSIONAL
 UNDER FBC 13-101, 103, FS 471,481.
  
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2009-09-28 Cont ID  
Sent By mawillia Date 2009-09-28 Time 12:12 Rev Time 0.00
Received By mawillia Date 2009-09-28 Time 12:02 Sent To  
Notes
2009-09-28 12:12:32*****PROVISO******
  
  
 OF THE REVISED SHEETS REVIEWED (A1.1, A3.4), SHEET A1.1
 TO BE FIRE-STAMPED WHEN THE BUILDING EXAMINER'S
 COMMENT(S) HAVE BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2009-07-22 Cont ID  
Sent By mawillia Date 2009-07-22 Time 11:39 Rev Time 0.00
Received By mawillia Date 2009-07-22 Time 11:19 Sent To B
Notes
2009-07-22 11:32:32*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; PLAN SHEETS A1.1, A1.2, A2.1, A3.1, AND
 E2 WERE STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2009-06-30 Cont ID  
Sent By mawillia Date 2009-06-30 Time 11:55 Rev Time 0.00
Received By mawillia Date 2009-06-30 Time 10:34 Sent To  
Notes
2009-06-30 11:04:30*****DENIED*****
  
 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004
 EDITION.
  
 2. ON SHEET A3.1, GENERAL NOTE #8 AND #9 REFERENCES
 FLORIDA FIRE PREVENTION CODE - 2004 EDITION. CORRELATE
 TO CURRENT EDITION AS CORRECTLY SHOWN ON SHEET T UNDER
 CODES.
  
 3. ON SHEET A3.1, THE NEW FIRE RATED DOOR (DOOR A)
 SHALL BE 20 MINUTES.
  
 4. WILL THE SCOPE OF WORK HAVE CAUSE FOR THE SPRINKLER
 HEADS TO BE REMODELED IN ANY MANNER? IF SO, PROVIDE A
 LAYOUT OF THE FIRE SPRINKLER. (THEY MAY BE SHOWN ON
 SHEET A2.1, REFLECTED CEILING PLAN).
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-11-10 Cont ID  
Sent By lmartine Date 2009-11-10 Time 16:02 Rev Time 0.00
Received By lmartine Date 2009-11-10 Time 16:02 Sent To  
Notes
2009-11-10 16:03:06*****************EXPEDITED******************
 GAVE TO RON

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2009-11-02 Cont ID  
Sent By lmartine Date 2009-11-02 Time 16:02 Rev Time 0.00
Received By lmartine Date 2009-11-02 Time 16:02 Sent To  
Notes
2009-11-02 16:03:08*************************EXPEDITED*********************
 ****
 GAVE TO RON

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2009-10-05 Cont ID  
Sent By dpalmer Date 2009-10-05 Time 10:28 Rev Time 0.00
Received By dpalmer Date 2009-10-05 Time 10:27 Sent To B
Notes
2009-10-05 10:28:17TO SH'S DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2009-07-09 Time   Rev Time 0.00
Received By rmcdouga Date 2009-06-08 Time 11:54 Sent To PC
Notes
2009-06-17 11:54:50TO B9

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2009-11-11 Cont ID  
Sent By rregueir Date 2009-11-11 Time 10:08 Rev Time 0.00
Received By rregueir Date 2009-11-11 Time 10:07 Sent To B
Notes
2009-11-11 10:08:19PROVISO HAS BEEN ADDRESSED

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2009-11-03 Cont ID  
Sent By rregueir Date 2009-11-03 Time 08:37 Rev Time 0.00
Received By rregueir Date 2009-11-03 Time 08:08 Sent To E
Notes
2009-11-03 08:37:09REVISED M1 DELTA 4, M2 DELTA 1. SEE PROVISO - M1
  
 **PROVISO**
 WALL ADJACENT TO STORAGE ROOM 106 IS SHOWN ON PAGE A1.1
 AS BEING 1-HOUR RATED. REVISE PAGE M1 TO SHOW THE DUCT
 PENETRATIONS IN THIS WALL TO BE PROTECTED WITH FIRE
 DAMPERS IN ACCORDANCE WITH FBC-M 607.5 AND FBC-M 607.8.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2009-07-22 Cont ID  
Sent By rregueir Date 2009-07-22 Time 10:49 Rev Time 0.00
Received By rregueir Date 2009-07-22 Time 10:36 Sent To FIRE
Notes
2009-07-22 10:49:08**PROVISO**
 WALL ADJACENT TO STORAGE ROOM 106 IS SHOWN ON PAGE A1.1
 AS BEING 1-HOUR RATED. REVISE PAGE M1 TO SHOW THE DUCT
 PENETRATIONS IN THIS WALL TO BE PROTECTED WITH FIRE
 DAMPERS IN ACCORDANCE WITH FBC-M 607.5 AND FBC-M 607.8.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2009-07-09 Cont ID  
Sent By rregueir Date 2009-07-09 Time 13:06 Rev Time 0.00
Received By rregueir Date 2009-07-09 Time 12:56 Sent To PC
Notes
2009-07-09 13:06:26REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PLAN SHOWS WHAT APPEARS TO BE TWO FIRE DAMPERS AT
 THE SUPPLY AND RETURN DUCT PENETRATIONS FOR EXISTING
 UNIT EM07 BUT THEY ARE NOT LABELED ON THE PLANS. PLEASE
 IDENTIFY THESE LOCATIONS AND INDICATE WHETHER THESE ARE
 NEW OR EXISTING DAMPERS IN ACCORDANCE WITH FBC-M 607.8.
  
 2. PAGE M-2 SHOWS A DETAIL FOR MOTORIZED VOLUME DAMPER
 LOCATION AND SEQUENCE FOR THE BUILDING SMOKE CONTROL
 SYSTEM. THESE DAMPERS AND ASSOCIATED DUCTS DO NOT
 APPEAR ON FLOOR PLANS. PLEASE COORDINATE FLOOR PLANS
 WITH DETAIL AND SEQUENCE TO SHOW COMPLIANCE WITH FBC-M
 SECTION 513.
  
 3. EXISTING UNIT EM07 SHARES A COMMON RETURN AIR PLENUM
 WITH OTHER UNITS IN THE CONFERENCE AREA. WHERE MULTIPLE
 AIR-HANDLING SYSTEMS SHARE COMMON PLENUMS WITH A
 COMBINED DESIGN CAPACITY GREATER THAN 2,000 CFM,EACH
 UNIT SHALL BE PROVIDED WITH SMOKE DETECTORS IN
 ACCORDANCE WITH FBC-M 606.2.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2009-07-22 Cont ID  
Sent By kstevens Date 2009-07-22 Time 14:57 Rev Time 0.00
Received By kstevens Date 2009-07-22 Time 14:57 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2009-06-18 Cont ID  
Sent By kstevens Date 2009-06-18 Time 12:57 Rev Time 0.00
Received By kstevens Date 2009-06-18 Time 12:57 Sent To  
Notes
2009-06-18 12:59:42PASSED PROVISO:
 SHT A3.2 DETAIL A6 DOES NOT COMPLY WITH SECTION
 11-4-24-5 CLEAR FLOOR SPACE. SEE FIGURES 31 & 32.


Account Summary | Usage Policy | Privacy Policy