| Plan Review Stops For Permit 09060185 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2009-11-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-11-12 |
Time |
18:03 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-11-12 |
Time |
18:03 |
Sent To |
|
|
| Notes |
| 2009-11-12 18:04:09 | ALT MAT'L & METHODS LETTER APPROVED BY DW | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2009-10-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-10-08 |
Time |
17:28 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-10-08 |
Time |
17:28 |
Sent To |
|
|
| Notes |
| 2009-10-08 17:38:14 | ****PASSED WITH PROVISO**** | | | ****REQUIRED BEFORE FINAL INSPECTION*** | | | ****ISSUED AT CONTRACTOR'S RISK**** | | | | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. SUBMIT REQUEST THROUGH ALTERNATE MATERIALS & | | | METHODS, FBC*104.11. SEE FBC715.3, DEMONSTRATE | | | COMPLIANCE WITH FBC TABLE 715.4. | | | | | | 2. REVISE SPRINKLER PERMIT 09080766 TO INCLUDE WATER | | | CURTAIN AND SPRINKLER HEAD SPEC SHEETS. SHOP DRAWING | | | REVIEW (BY DESIGNER OF RECORD) PRIOR TO REVISION | | | SUBMITTAL. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2009-09-24 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-09-24 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-09-24 |
Time |
08:54 |
Sent To |
FIRE |
|
| Notes |
| 2009-09-24 08:56:24 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2007 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. PLEASE PROVIDE INFORMATION REGARDING THE WATER | | | CURTAIN. IT IS NOT CLEAR HOW THIS WILL WORK PROPERLY AS | | | DESIGNED; ISN'T THE WATER TO HIT THE WALL ABOVE THE | | | WINDOW AND THEN RUN DOWN THE WINDOW, WITH MULLIONS ON | | | THE WINDOW PROHIBITED? A BULKHEAD ABOVE THE DOOR/WINDOW | | | HAS BEEN PROPOSED, SO IT IS NOT CLEAR HOW THE WATER | | | CURTAIN ON EITHER SIDE WILL WORK. PROVIDE SPECIFICATION | | | SHEETS FOR THE SPRINKLER HEADS, DIMENSION FOR THE | | | BULKHEAD, AND ANY OTHER INFORMATION REQUIRED TO | | | DEMONSTRATE COMPLIANCE WITH FBC715.4. ALSO, PLEASE NOTE | | | DISTANCE FROM THE PROPOSED WATER CURTAIN SPRINKLER | | | HEADS TO THE EXISTING FIRE SPRINKLERS IN THE CORRIDOR. | | | THIS INFORMATION IS TO BE EITHER PREPARED BY THE FIRE | | | SPRINKLER ENGINEER OR REVIEWED BY THE FIRE SPRINKLER | | | ENGINEER. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2009-07-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2009-07-21 |
Time |
21:35 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2009-07-21 |
Time |
21:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2009-06-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-06-23 |
Time |
12:33 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
2009-06-23 |
Time |
12:03 |
Sent To |
|
|
| Notes |
| 2009-06-23 12:33:33 | BUILDING PLAN REVIEW | | | PERMIT: 09060185 | | | ADD: 222 LAKEVIEW AVE SUITE# 110 | | | CONT: G3 CONSTRUCTION | | | TEL: (561)445-3769 | | | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | | W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER | | | MARCH 1ST, 2009 SHALL BE REVIEWED TO THE 2007 FBC | | | BUILDING WITH 2009 SUPPLEMENTS. | | | | | | 2) SHEET A1.1 INDICATES A NEW TENANT SEPERATION WALL/ | | | CORRIDOR TO BE 1 HR RATED AS PER 708.1 (7), THE PLANS | | | ARE MISSING THE RATING OF THE TENANT ENTRY DOOR# 1 AND | | | THE SIDELIGHTS | | | SEE A3.1 THE DOOR SCHEDULE IS MISSING OPENING | | | PROTECTIVES PER TABLE 715.4. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | SURVEY: | | | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2009-11-03 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2009-11-03 |
Time |
17:31 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2009-11-03 |
Time |
17:01 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2009-07-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-07-21 |
Time |
18:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-07-21 |
Time |
18:27 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2009-07-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-07-03 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-07-03 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2009-07-03 09:30:42 | ** DENIED PLANS * | | | | | | 1) NOTE: THE ELECTRICAL PLANS NEED TO STATE THE | | | FOLLOWING MINIMUM CODES. | | | PLEASE BE SURE THE FOLLOWING ARE STATED ON ELECTRICAL | | | PLANS. | | | 2007 FBC W/ 2009 AMENDMENTS. | | | 2006 NFPA-101 ( PLANS STATE 2007 FOR THIS CODE) | | | 2002 NFPA-72 (OK) | | | 2006 NFPA-1 | | | 2005 NFPA-70 ( PLANS STATE 2007) PLEASE BE ADVISED EVEN | | | ONCE THE CODE CHANGE GOES INTO AFFECT THE IT WILL BE | | | THE 2008 NEC. | | | | | | PER: FBC CHAPTER 35, FS 553.73, FAC 69A-60.004, .003 | | | | | | | | | | | | 2) NOTE: THE PANEL AND TRANSFORMER LOCATION NEEDS TO BE | | | IDENTIFIED AS ELECTRICAL ROOM. PLEASE ALSO NOTE THAT | | | SIGNAGE WILL BE REQUIRED FOR ELECTRICAL ROOM, NO | | | STORAGE OR WORDS TO THAT AFFECT. | | | 110.26, 240.24 | | | | | | 3) NOTE: PLEASE INCLUDE ALL DEVICE LOCATIONS, HEIGHTS, | | | AND MINIMUM LEVELS PER FBC 11-4.28.1,.2 AND .3. | | | THERE ARE SOME DEVICES ON PLANS HOWEVER NO DETAILS OR | | | INFORMATION ON SYMBOL LEGEND. | | | | | | 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE | | | CALCULATIONS IN ACCORDANCE WITH THE FLORIDA BUILDING | | | CODE 13-415.AB.5. PLANS STATE TO SEE DOCUMENTS | | | ATTACHED. THE ATTACHED CALCULATIONS ARE COMCHECK | | | SOFTWARE WHICH IS NOT ADOPTED BY THE STATE OF FLORIDA. | | | PLEASE SEE 13-400 AS THE ONLY ADOPTED PROGRAM IS | | | FLA-COM. | | | PLEASE BE SURE THE RESPONSIBLE DESIGN PROFESSIONAL | | | UNDER FBC 13-101, 103, FS 471,481. | | | | | | | | | | | | ** IMPORTANT ** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2009-09-28 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-09-28 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-09-28 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2009-09-28 12:12:32 | *****PROVISO****** | | | | | | | | | OF THE REVISED SHEETS REVIEWED (A1.1, A3.4), SHEET A1.1 | | | TO BE FIRE-STAMPED WHEN THE BUILDING EXAMINER'S | | | COMMENT(S) HAVE BEEN SATISFIED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2009-07-22 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-07-22 |
Time |
11:39 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-07-22 |
Time |
11:19 |
Sent To |
B |
|
| Notes |
| 2009-07-22 11:32:32 | *****APPROVED***** | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | | BEEN ADDRESSED; PLAN SHEETS A1.1, A1.2, A2.1, A3.1, AND | | | E2 WERE STAMPED, INITIALED, AND DATED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2009-06-30 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-06-30 |
Time |
11:55 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-06-30 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2009-06-30 11:04:30 | *****DENIED***** | | | | | | 1. STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241 - 2004 | | | EDITION. | | | | | | 2. ON SHEET A3.1, GENERAL NOTE #8 AND #9 REFERENCES | | | FLORIDA FIRE PREVENTION CODE - 2004 EDITION. CORRELATE | | | TO CURRENT EDITION AS CORRECTLY SHOWN ON SHEET T UNDER | | | CODES. | | | | | | 3. ON SHEET A3.1, THE NEW FIRE RATED DOOR (DOOR A) | | | SHALL BE 20 MINUTES. | | | | | | 4. WILL THE SCOPE OF WORK HAVE CAUSE FOR THE SPRINKLER | | | HEADS TO BE REMODELED IN ANY MANNER? IF SO, PROVIDE A | | | LAYOUT OF THE FIRE SPRINKLER. (THEY MAY BE SHOWN ON | | | SHEET A2.1, REFLECTED CEILING PLAN). | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2009-11-10 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2009-11-10 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2009-11-10 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2009-11-10 16:03:06 | *****************EXPEDITED****************** | | | GAVE TO RON |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2009-11-02 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2009-11-02 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2009-11-02 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2009-11-02 16:03:08 | *************************EXPEDITED********************* | | | **** | | | GAVE TO RON |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2009-10-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-10-05 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-10-05 |
Time |
10:27 |
Sent To |
B |
|
| Notes |
| 2009-10-05 10:28:17 | TO SH'S DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2009-07-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2009-06-08 |
Time |
11:54 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2009-11-11 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-11-11 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-11-11 |
Time |
10:07 |
Sent To |
B |
|
| Notes |
| 2009-11-11 10:08:19 | PROVISO HAS BEEN ADDRESSED |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2009-11-03 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-11-03 |
Time |
08:37 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-11-03 |
Time |
08:08 |
Sent To |
E |
|
| Notes |
| 2009-11-03 08:37:09 | REVISED M1 DELTA 4, M2 DELTA 1. SEE PROVISO - M1 | | | | | | **PROVISO** | | | WALL ADJACENT TO STORAGE ROOM 106 IS SHOWN ON PAGE A1.1 | | | AS BEING 1-HOUR RATED. REVISE PAGE M1 TO SHOW THE DUCT | | | PENETRATIONS IN THIS WALL TO BE PROTECTED WITH FIRE | | | DAMPERS IN ACCORDANCE WITH FBC-M 607.5 AND FBC-M 607.8. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2009-07-22 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-07-22 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-07-22 |
Time |
10:36 |
Sent To |
FIRE |
|
| Notes |
| 2009-07-22 10:49:08 | **PROVISO** | | | WALL ADJACENT TO STORAGE ROOM 106 IS SHOWN ON PAGE A1.1 | | | AS BEING 1-HOUR RATED. REVISE PAGE M1 TO SHOW THE DUCT | | | PENETRATIONS IN THIS WALL TO BE PROTECTED WITH FIRE | | | DAMPERS IN ACCORDANCE WITH FBC-M 607.5 AND FBC-M 607.8. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2009-07-09 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-07-09 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-07-09 |
Time |
12:56 |
Sent To |
PC |
|
| Notes |
| 2009-07-09 13:06:26 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PLAN SHOWS WHAT APPEARS TO BE TWO FIRE DAMPERS AT | | | THE SUPPLY AND RETURN DUCT PENETRATIONS FOR EXISTING | | | UNIT EM07 BUT THEY ARE NOT LABELED ON THE PLANS. PLEASE | | | IDENTIFY THESE LOCATIONS AND INDICATE WHETHER THESE ARE | | | NEW OR EXISTING DAMPERS IN ACCORDANCE WITH FBC-M 607.8. | | | | | | 2. PAGE M-2 SHOWS A DETAIL FOR MOTORIZED VOLUME DAMPER | | | LOCATION AND SEQUENCE FOR THE BUILDING SMOKE CONTROL | | | SYSTEM. THESE DAMPERS AND ASSOCIATED DUCTS DO NOT | | | APPEAR ON FLOOR PLANS. PLEASE COORDINATE FLOOR PLANS | | | WITH DETAIL AND SEQUENCE TO SHOW COMPLIANCE WITH FBC-M | | | SECTION 513. | | | | | | 3. EXISTING UNIT EM07 SHARES A COMMON RETURN AIR PLENUM | | | WITH OTHER UNITS IN THE CONFERENCE AREA. WHERE MULTIPLE | | | AIR-HANDLING SYSTEMS SHARE COMMON PLENUMS WITH A | | | COMBINED DESIGN CAPACITY GREATER THAN 2,000 CFM,EACH | | | UNIT SHALL BE PROVIDED WITH SMOKE DETECTORS IN | | | ACCORDANCE WITH FBC-M 606.2.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2009-07-22 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-07-22 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-07-22 |
Time |
14:57 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2009-06-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-06-18 |
Time |
12:57 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-06-18 |
Time |
12:57 |
Sent To |
|
|
| Notes |
| 2009-06-18 12:59:42 | PASSED PROVISO: | | | SHT A3.2 DETAIL A6 DOES NOT COMPLY WITH SECTION | | | 11-4-24-5 CLEAR FLOOR SPACE. SEE FIGURES 31 & 32. |
|
|